DR is a serie of Digital Room Thermostats, provides a single stage, temperature control. Table 1 shows all the available models. All models can be provided with 24, 120, 220 Vac.
Model | Operation | Cooling / Heating | Compressor delay |
01 | cool + sweep | Compressor | yes |
02 | cool + sweep | Chilled water | no |
03 | cool – fan – dry | Compressor | yes |
04 | cool – fan – dry | Chilled water | no |
05 | cool – fan – dry – heat – auto | Compressor / Heat pump | yes |
06 | cool – fan – dry – heat – auto | Compressor / Electric heater | yes, only for cool |
07 | cool – fan – dry – heat – auto | Hot / Chilled water | no |
These thermostats are mercury free and require no battery. All set points are kept permanently by non-volatile memory.
Model No. Legend
When ordered, put all the information in the Model No. Legend.
POWER SUPPLY | |
24 VAC system | 18 – 30 VAC, 50/60 Hz |
120 VAC system | 96 – 144 VAC, 50/60 Hz |
220 VAC system | 198 – 250 VAC, 50/60 Hz |
TEMPERATURE : | |
Temperature accuracy | ± 1 °C |
Storage temperature | 0 – 70 °C |
Ambient temperature | 10 – 50 °C |
Setting temperature range | 18 – 30 °C (64 – 88 °F) |
HEAT and COOL RELAY : ( P1, P2) | |
Rating (resistive load) | |
· Maximum switching capacity | 3 A 277 VAC |
FAN RELAY: (P3, P4, P5) | |
Rating (resistive load) | |
· Maximum switching capacity | 2 A 277 VAC 3 A 125 VAC |
Read these instructions thoroughly before installing product. Failure to follow these instructions could damage the product or cause a hazardous condition. Check the voltage and current ratings on the product to ensure that it is suitable for your application. Installer must be a trained, experienced service technician. Check product for proper operation after installation.
CAUTION
Damage to heating and cooling system may occur. Disconnect power from the equipment at the main breaker/fuse block while installing the thermostat
Mount the thermostat approximately 5 ft. (1.5m) above the floor in a location that is free from direct sunlight, heat from appliances, hot or cold air from ducts, concealed pipes and chimneys, and drafts or dead spots behind doors or in corners. Do not mount on exterior wall, if possible. Failure to locate thermostat mounting as indicated will result in poor temperature control
Note: Level thermostat mounting is for appearance only and is not required for proper thermostat operation.
Mount and Wire the Thermostat
Fig. 9. For 24 Vac system
All thermostats are factory set up according to the Model No. Legend listed on the back side of the plastic casing. However it can be alternated by the programming
Set up mode
Press and hold TEMP
Display | Not blinking | Blinking |
P1 | Heat /Cool | Cool |
P2 | Electric heater | No electric heater |
P3 | °F | °C |
P4 | No compressor delay | Compressor delay |
P5 | Sweep | No sweep |
P6 | Wireless | Wire |
Note: P6 is not used in this serie.
Example 1: the display shows P1 without blinking means the set up is now for Heat / Cool version.
Change the set up
Power
Press POWER to turn on/off the air conditioner. When turn on, it will operate according to the last program setting.
Mode/Sweep
For Cool + Sweep version, button is a SWEEP button used to turn on/off the sweep motor. For other versions, this is a MODE button used to select the operation mode.
Fan
Press FAN button to select the fan speed in the following sequence.
LED at will show the status of the fan.
Auto mode
The speed will be adjusted according to the difference between the room and the setting temperature.
Temperature setting
Press TEMP D or TEMP Ñ button for setting the temperature in a range of 18 – 30°C or 64 – 88 °F. LED at will show the new setting for 5 seconds.
Compressor delay
In a model with a compressor delay feature, there will be 3-minute time delay before the compressor can restart.
Compressor status
LED at shows the status of the compressor/valve/heater.
Sensor Error Alarm
If the room sensor is open/short-circuit, the controller will stop the compressor or any heating equipment and dot on the 7-segment will blink.
Auto Restart
All the setting parameters are kept in the nonvolatile memory. When there is a power failure and back to normal, the system will resume its operation with the same setting parameters.
DOWNLOAD MANUALS:
Vtronix TF65L-001 Digital Room Thermostats INSTALLATION MANUAL
Vtronix TF65L-001 Digital Room Thermostats INSTALLATION MANUAL
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…