The TE80SB Thermostat provides universal replacement of single-stage, 24Vac (20 mA to 1.5A) thermostats used in electric, gas, and oil heating and cooling systems. This thermostat is mercury free and requires no batteries. The thermostat also can be used to control single-stage heat pumps. The TE80SB uses advanced proportional plus integral (P+I) control for optimum temperature control and comfort.
Table 1. Description of Thermostat.
Model | Mounting | System Selection | Fan Selection | Powering Method | Backlight |
TE80SB | VERTICAL | COOL-OFF-HEAT | ON-AUTO | Power Stealing | Backlight |
Table 2. Thermostat specifications.
Power Power Supply | 24 Vac nominal, 18-30 Vac, 50/60 HZ. |
Electrical Rating Heating rating Cooling rating Fan rating Note: The fan load plus the higher of the heating or cooling load must not exceed 1.5 Amp continuous | 0.02 to 1.5 A continuous 0.02 to 1.5 A continuous 0.02 to 0.5 A continuous |
TEMPERATURE RATINGS Temperature setting range Ambient temperature range Shipping temperature range | 40 to 99 °F (4 to 37 °C) 40 to 110 °F (4 to 43 °C) 14 to 140 °F (-10 to 60 °C) |
OPERATING RELATIVE HUMIDITY | 5 to 90% RH, non-condensing |
CYCLE RATES Cooling mode Heating mode | 4 Cycles Per Hour 1,3,4,5,6,9,12 Selectable Cycles Per Hour |
Read these instructions thoroughly before installing product. Failure to follow these instructions could damage the product or cause a hazardous condition. Check the voltage and current ratings on the product to ensure that it is suitable for your application. Installer must be a trained, experienced service technician. Check product for proper operation after installation.
CAUTION
Damage to heating and cooling system may occur. Disconnect power from the equipment at the main breaker/fuse block while installing the thermostat.
Mounting Location.
Mount the thermostat approximately 5 ft. (1.5m) above the floor in a location that is free from direct sunlight, heat from appliances, hot or cold air from ducts, concealed pipes and chimneys, and drafts or dead spots behind doors or in corners. Do not mount on exterior wall, if possible. Failure to locate thermostat mounting as indicated will result in poor temperature control.
NOTE: Level thermostat mounting is for appearance only and is not required for proper thermostat operation.
Mounting Thermostat
Take out the back plate by removing the locking screw (if any) at the bottom of the thermostat. Use a flat head screwdriver to unlock the snaps. Lift and pull it up to remove back plate. Using back plate as a guide, mark two mounti holes on the wall. Drill two mounting holes. Place anchors (provided) into the holes until flush with the hole. Position back plate on the wall and thread the wires from the heating and cooling equipment through the wiring hole. Holding the back plate in place on the wall, secure it to the wall using mounting screws (provided).
Wiring
Pull the connector from the back of the thermostat by inserting screwdriver at the base of the connector and gently lift up.
Color-coded 18-22 gauge wire is recommended for wiring. All wiring must follow local electrical code located near each terminal.
Loosen the terminal screw, strip the wire and connect the wire as shown in fig 7. Firmly tighten the terminal screw when finished.
WARNING
Fire Hazard.
Failure to set the set-up switch to the E position when electric resistance heat is used may result in the overheating of the electric heater elements due to improper fan operation.
The set-up switch is an internal switch (E,F) located near the wiring terminals. It is used to select proper fan operation for the heating system being used.
Place the terminal back to the thermostat, make sure it has the same orientation like in the picture described at the back. Snap the thermostat to its back plate.
Secure the thermostat by tightening the screw provided to protect the thermostat from unwanted access.
The following instructions provide information to test the heating/cooling equipment and to change operating parameters from the factory settings.
Enter Installer Setup
Now follow the following steps to change each of the settings. Each time you press
Testing Heating / Cooling Equipment. (OP:01)
While in the installer setup, slide the mode switch to heat to operate the heating equipment or cool to operate the cooling equipment. The display will show either 00 or 01 on the lower right area and either heat or cool as selected by the mode switch.
Setting °C / °F Indication. (OP:02)
While in the installer setup,
Setting Heating Cycle Rate. (OP:03)
In cooling, the cycle rate is fixed at 4 Cycles per hour. To set the cycle rate in heating; while in installer setup,
Table 4. Recommended cycle rate (CPH).
SYSTEM | CPH SETTING |
Steam Gravity | 1 |
Hydronic heat | 3 |
Gas or Oil forced air | 6 |
Electric heat | 9 |
Note: If the equipment manufacturer recommends a different rate use the rate specified by the equipment manufacture.
Setting cooling algorithm. (OP:04)
The cooling algorithm can be selected as normal or aggressive. For aggressive, the system will cool down the room to setting point faster than normal algorithm. However, an overshoot might be occurred in some situations.
Setting Cooling Delay Time. (OP:05)
In some applications, there is a necessity to delay the operation of the cooling equipment for protection purposes. While in the installer setup,
Temperature offset. (OP:06)
The temperature can be offset from +3 to -4 °F to eliminate the effect of installing location (e.g. direct sunlight). The thermostat will indicate room temperature by using actual reading plus (or minus ) the offset value.
Time format. (OP:07)
The clock on the display can be selected to show either 24-hour or AM/PM format. While in the installer setup,
NOTE : The default setting is 1: AM/PM format.
Exit Installer Setup.
Press D key again to save all settings and exit to the normal operating mode.
NOTE: After return to normal operation, change the set point to the desired room temperature, otherwise the programmed set point will be used.
System Setting
Use mode switch for selecting system operation.
Fan Setting
Fan switch settings are
For cooling mode:
The fan starts and stops with cooling equipment.
For heating mode:
Minimum Off Timer
For cooling, when the thermostat calls for operation while theminimum off timer is not expired, the star symbol keeps flashing.
Back Lighting
The thermostat features a backlight that will illuminate all the time. The user can easily see the LCD screen under dim light situation.
Select system switch in heat or cool mode. Press “PROG” to enter program mode. Display will prompt to select day.
Press
Default setting:
Note : Default setting can be restored to memory by pressing HOLD and RUN buttons at the same time for 3 seconds.
ADJUSTING TEMPERATURE | CLOCK ADJUSTMENT |
Adjusting the temperature during any program will make the thermostat to temporarily use this set point until the next program. | The clock needs to be adjusted when installed. The clock will be retained for a few hours in case of power interruption. |
Press ‘CLOCK’ in normal mode to adjust the clock. | |
During any program, press D or Ñ keys to change set point. Flashing ‘KEY’ icon indicates temporary mode. | Press |
The next program timer will cancel the temporary mode. ‘KEY’ the icon will stop flashing and set point will be updated to programmed data. | Press |
Press the ‘RUN’ button to cancel the temporary mode and follow the program schedule. | Press |
Note : Press HOLD and CLOCK buttons at the same time to toggle between °C / °F. | |
Press ‘CLOCK’ to confirm and exit. | |
HOLD TEMPERATURE | |
Press the ‘HOLD’ button to maintain a setpoint for an extended period of time, for example, when going on vacation. | |
Pressing | Note : Press CLOCK and RUN buttons at the same time to toggle between AM/PM and 24H format. |
To cancel, press the ‘HOLD’ button again until the key icon has disappeared. Set point will be updated to the programmed data. | |
Note that only the HOLD button can be used to exit the HOLD temperature. |
Cooling Checkout
WARNING! Do not operate in cooling mode when the outdoor temperature is below 50 °F ( 10 °C) otherwise the compressor might be damaged.
Heating Checkout
Fan Checkout
The attached 1000 ohm, the 3-watt resistor is used in certain applications to assure compatibility with power-stealing thermostats where Fan does not come ON during call for Heat or Cool. Note that the resistor has to be installed at the fan terminals and not at the thermostat terminals.
To install the Resistor
VTRONIX TE80SB-501 Programmable Digital Thermostat INSTALLATION MANUAL
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…