Description | |
Gas or Oil Heat | Yes |
Electric Furnace | Yes |
Heat Pump (No Aux. or Emergency Heat) | Yes |
Heat Pump (With Aux. or Emergency Heat) | No |
Multi-Stage Systems | No |
Heat Only Systems | Yes |
Heat Only Systems – Floor or Wall Furnace | Yes |
Cool Only | Yes |
Millivolt | Yes |
Power Type
Battery Power
Hardwire (Common Wire)
Hardwire (Common Wire) with
Battery Backup
A trained, experienced technician must install this product.
Carefully read these instructions. You could damage this product or cause a hazardous condition if you fail to follow these instructions.
The thermostat should be installed approximately 4 to 5 feet above the floor. Select an area with average temperature and good air circulation.
Installation Tip
Pick an installation location that is easy for the user to access. The temperature of the location should be representative of the building.
Do not install thermostats in locations
For vertical mount put one screw on the top and one screw on the bottom. For horizontal mount put one screw on the left and one screw on the right.
Electrical Hazard
Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.
Mercury Notice
All of our products are mercury-free.
However, if the product you are replacing contains mercury, dispose of it properly. Your local waste management authority can give you instructions on recycling and proper disposal.
Mount Thermostat
Align the 4 tabs on the subbase with corresponding slots on the back of the thermostat, then push gently until the thermostat snaps in place.
Battery Installation
Battery installation is recommended even if the thermostat is hardwired (C terminal connected). When the
Important: High-quality alkaline batteries are recommended. Rechargeable batteries or low-quality batteries do not guarantee a 1-year life span.
Gas or Electric Setup
Important
The low battery indicator is displayed when the AA battery power is low. If the user fails to replace the battery within 21 days, the screen will only show the low battery indicator but maintain all functionality. If the user fails to replace the batteries after an additional 21 days (days 22-42 since first “low battery” display) the setpoints will change to 55˚F (Heating) and 85˚F (Cooling). If the user adjusts the setpoint away from either of these, it will hold for 4 hours and then return to either 55˚F or 85˚F. After day 63 the batteries must be replaced immediately to avoid freezing or overheating because the thermostat will shut the unit off until the batteries are changed.
Removing The Private
Label Badge
About The Badge
All of our thermostats use the same universal magnetic badge. Visit the company website to learn more about our free private label program.
Caution:
Electrical Hazard
Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.
Warning:
All components of the control system and the thermostat installation must conform to Class II circuits per the NEC Code.
Wiring
Installation Tip
Do not overtighten terminal block screws, as this can damage the terminal block. A damaged terminal block can keep the thermostat from fitting on the subbase correctly or cause system operation issues.
Max Torque = 6in-lbs.
Terminal Designations
Wiring Tips
RH & RC Terminals
For single transformer systems, leave the jumper wire in place between RH and RC. Remove jumper wire for two transformer systems.
Heat Pump Systems
If wiring to a heat pump, use a small piece of wire (not supplied) to connect terminals W and Y.
C Terminal
The C (common wire) terminal does not have to be connected when the thermostat is powered by batteries.
Wire Specifications
Use shielded or non-shielded 18-22 gauge thermostat wire.
Tech Settings
Swing & Limit Settings
Tech Settings | LCD Will Show | Adjustment Options | Default | |
Room Temperature Calibration | This feature allows the installer to change the calibration of the room temperature display. For example, if the thermostat reads 70 degrees and you would like it to read 72 then select +2. | CA 0 | You can adjust the room temperature display to read 4 above or below the factory-calibrated reading. | O |
Compressor Short Cycle Delay | The compressor’s short cycle delay prevents the compressor from switching on and off too often. | 0 Cd | Selecting “ON” will not allow the compressor to be turned on for 5 minutes after the last time the compressor was switched off. Select “OFF” to remove this delay. | ON |
F or C | Select F for Fahrenheit temperature readout or select C for Celsius read out. | FC F | F for Fahrenheit C for Celsius | F |
Swing & Limit Settings | LCD Will Show | Adjustment Options | Default | |
Cooling Swing | The swing setting often called “cycle rate”, “differential” or “anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles. | CO 05 | The cooling swing setting is adjustable from 0.2˚ to 2˚. For example: A swing setting of 0.5˚will turn the cooling on at approximately 0.5˚ above the setpoint and turn the cooling off at approximately 0.5˚ below the setpoint. | 0.5 |
Cooling Setpoint Limit | This feature allows you to set a minimum cool setpoint value. The setpoint temperature can’t be lowered below this value. | L 44 | Use the and key to select the minimum cool setpoint. | 44 |
Heating Swing | The swing setting often called “cycle rate”, “differential” or “anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles. | HE 04 | The heating swing setting is adjustable from 0.2˚ to 2˚. For example: A swing setting of 0.5˚will turn the heating on at approximately 0.5˚ below the setpoint and turn the heating off at approximately 0.5˚ above the setpoint. | 0.4 |
Heating Setpoint Limit | This feature allows you to set a maximum heat setpoint value. The setpoint temperature can’t be raised above this value. | H 90 | Use the and key to select the maximum heat setpoint. | 90 |
Swing Setting Tip
The temperature swing, sometimes called differential or cycle rate, can be customized for this individual application. For most applications choose a swing set that is as wide as possible without making the occupants uncomfortable.
Download Manual:
Vive Comfort TP-N-701 Non-Programmable THERMOSTAT Installation Manual
OTHER MANUALS
Vive Comfort TP-N-701 Non-Programmable Thermostat Operational Manual
Vive Comfort TP-N-701 Non-Programmable THERMOSTAT Installation Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…