Categories: Vimar

VIMAR 21814 Tactil KNX Thermostat Instruction Manual

VIMAR 21814 Tactil KNX Thermostat

For all the details about the Well-contact Plus system, refer to the installer manual that can be downloaded from the Software  Product Software Well-contact Plus section of the website: www.vimar.com.

General characteristics and functions

Touch screen thermostat for room temperature control (heating and air conditioning), KNX standard home automation system, class I temperature control device (contribution 1%) in ON/OFF mode, class IV (contribution 2%) in PID mode, can be interfaced with an actuator with proportional analog outputs 01466.1 to make a class V modulating room thermostat (contribution 3%), 1 input for electronic temperature sensor 20432, 19432 or 14432 or wired temperature sensor 02965.1, 1 programmable digital input, RGB LED backlighting – 2 modules.

General characteristics
The thermostat is suitable for controlling room temperature (heating/air-conditioning) in 2 or 4-pipe systems and neutral zone (only in 4-pipe systems), with the “boost” function to activate a second source that makes it possible to reach the desired thermal comfort faster. It can interact with other thermostats and with a monitoring unit (PC with Well-contact Suite software). It can manage 2 climate zones completely independently (equivalent to two thermostats A and B). For each zone, the heating/air-conditioning modes are managed according to the related reference temperature. It has a programmable digital input that can be used for other applications, such as .detecting an open window. The thermostat has an RGB back-lit display with 4 keys to control the temperature set point, to turn the temperature control system on/off and, depending on the type of device (.F or .S or .H) for the specific function that identifies it.

Display icons

Front view

Default behavior

Thermostat OFF  Protection mode
Thermostat ON  Comfort mode

Behavior after bus power on/off
Bus power off: -.
Bus power on the status will be set based on the setting of the parameters and the corresponding telegrams sent over the Bus.

Behavior after reset
As for Bus power-on.
N.B. The thermostat saves the comfort and standby setpoints set manually by the user; if you wish to reset them, set the ETS parameter “Reset Setpoint Shift in Economy Mode=YES”. When switched to “Economy” mode, the thermostat will reset the STBY and CNF values.

General characteristics and functions

Neutral zone
The “Neutral Zone” is an operating mode of the thermostat (only for 4-pipe systems) in which the device keeps the temperature within a temperature range preset by the Winter Setpoint and Summer Setpoint (basically, there is no longer the usual Summer/Winter mode). If the measured temperature is below the Winter Setpoint, the thermostat switches on the heating valve and heats the room until the temperature exceeds the set value (e.g. 20°C for Comfort mode or 18°C for Standby mode). If the measured temperature exceeds the Summer Setpoint then the thermostat switches on the cooling valve and keeps it on until the temperature falls below the set Summer Setpoint value. Within the Neutral Zone, the thermostat does not switch on any valves and the temperature can vary freely; this zone is, therefore, nothing more than the difference between the Summer and Winter Setpoints when the room temperature is between the winter setpoint and the summer one. To avoid excessive temperature fluctuations, set a limited range (≤ 2°C) as shown in the figure below.

Setpoint displayed in Neutral Zone operation
When the thermostat is working in the neutral zone, the setpoint used for the adjustment is always the Current Setpoint, namely the one relating to the last heating/cooling mode that came into operation; the value displayed is instead a new setpoint named “Neutral Zone Setpoint”, which is the average value between the current summer and winter setpoints. Changing the temperature of the “Neutral Zone Setpoint” (with the “+” and “-” buttons on the thermostat) will also cause a change to the value of the “Shift Setpoint” resulting in a shift of the two current summer/winter setpoint values; the room temperature will therefore not become the one set by the guest but that of the summer/winter setpoint which at that moment is closest to the value of the current temperature in the room. Between the two summer/winter setpoints, there is the neutral zone in which the system is not activated.

Mid Season
This function is available from the supervisor only for systems configured with primary and secondary output; when active, it exchanges the 2 main and secondary outputs (and the related parameters too). It is recommended for making minor adjustments (such as +/-2 °C) during mid-season periods where it may be more convenient to operate only the secondary circuit (for instance Split).

Configuration
The KNX 21814 thermostat is configured in Neutral Zone mode if the following object is NOT connected: “Enable A: Summer – Winter – control” or “Enable B: Summer – Winter – control”. The thermostat can operate in Neutral Zone IF:

  • The system has 4 pipes
  • inter Comfort Setpoint < Summer Comfort Setpoint
  • Winter Standby Setpoint < Summer Standby Setpoint
  • Winter Economy Setpoint < Summer Economy Setpoint
  • Antifreeze < Too Hot
    If these conditions are not satisfied, you can still commission the thermostat; if there is an error while starting up, the device will remain in “Protected” mode and an error message will be displayed.

Types of errors at the time of configuration

Error No. Description
E1 Selected 2-pipe system instead of 4-pipe system
E2 Winter Comfort Setpoint ≥ Summer Comfort Setpoint
E3 Winter Standby Setpoint ≥ Summer Standby Setpoint
E4 Winter Economy Setpoint ≥ Summer Economy Setpoint
E5 Antifreeze ≥ Too Hot

N.B. Errors E2, E3, E4, and E5 may also be displayed if the thermostat is programmed in “4-pipe system” mode without the neutral zone according to the type of Setpoint shown in the table.

List of existing communication objects and standard settings

No. ETS name Function Description Type Flag 1 Priority
C R W T U I

1

Internal sensor

Internal probe temperature

To see the temperature read by the thermostat sensor (to see the temperatures measured by thermostats A/B with Well-Contact Suite software, objects nos. 10/11 should be used)

2 byte

C

R

T

Low

2

External sensor

External NTC probe temper- ature

To see the temperature read by the wired NTC probe connected to the thermostat (to see the temperatures measured by thermostats A/B with Well-Contact Suite software, objects nos. 10/11 should be used)

2 byte

C

R

T

Low

3

External Temperature 1

KNX probe temperature on bus

To see the temperature read by a KNX sensor con- nected to the bus (to see the temperatures measured by thermostats A/B with Well-Contact Suite software, objects nos. 10/11 should be used)

2 byte

C

W

U

Low

4

External Temperature 2

KNX probe temperature on bus

To see the temperature read by a KNX sensor con- nected to the bus (to see the temperatures measured by thermostats A/B with Well-Contact Suite software, objects nos. 10/11 should be used)

2 byte

C

W

U

Low

5

External Temperature 3

KNX probe temperature on bus

To see the temperature read by a KNX sensor con- nected to the bus (to see the temperatures measured by thermostats A/B with Well-Contact Suite software, objects nos. 10/11 should be used)

2 byte

C

W

U

Low

6

External Temperature 4

KNX probe temperature on bus

To see the temperature read by a KNX sensor con- nected to the bus (to see the temperatures measured by thermostats A/B with Well-Contact Suite software, objects nos. 10/11 should be used)

2 byte

C

W

U

Low

7

External Temperature 5

KNX probe temperature on bus

To see the temperature read by a KNX sensor con- nected to the bus (to see the temperatures measured by thermostats A/B with Well-Contact Suite software, objects nos. 10/11 should be used)

2 byte

C

W

U

Low

COMMUNICATION OBJECTS

8

External Temperature 6

KNX probe temperature on bus

To see the temperature read by a KNX sensor con- nected to the bus (to see the temperatures measured by thermostats A/B with Well-Contact Suite software, objects nos. 10/11 should be used)

2 byte

C

W

U

Low

9

External Temperature 7

KNX probe temperature on bus

To see the temperature read by a KNX sensor con- nected to the bus (to see the temperatures measured by thermostats A/B with Well-Contact Suite software, objects nos. 10/11 should be used)

2 byte

C

W

U

Low

10

External Temperature 8

KNX probe temperature on bus

To see the temperature read by a KNX sensor con- nected to the bus (to see the temperatures measured by thermostats A/B with Well-Contact Suite software, objects nos. 10/11 should be used)

2 byte

C

W

U

Low

11

Current Temperature

A: Temperature

To see the current temperature associated with ther- mostat-A (weighted average of the various associated probes): this object is used with Well-Contact Suite software to see the temperature measured by thermo- stat A

2 byte

C

R

T

Low

12

Current Temperature

B: Temperature

To see the current temperature associated with ther- mostat-B (weighted average of the various associated probes): this object is used with Well-Contact Suite software to see the temperature measured by thermo- stat B

2 byte

C

R

T

Low

THERMOSTAT A:

13

Comfort

A: Mode – control

To select COMFORT operating mode by sending a 1 bit or to set the thermostat to STANDBY by sending a 0 bit

1 bit

C

W

U

Low

14 Energy Saving A: Mode – control To select ECONOMY operating mode by sending a 1 bit (a 0 bit is ignored) 1 bit C W U Low

15

Protected

A: Mode – control

To select OFF-ANTIFREEZE operating mode (or Too Hot in the case of air conditioning) by sending a 1 bit.

1 bit

C

W

U

Low

16 Off A: Mode – control To select OFF operating mode by sending a 1 bit (a 0 bit is ignored) 1 bit C R W U Low

17

Thermostat Mode

A: Mode – control

To select operating mode by sending a Byte (1 = Comfort, 2 = StandBy, 3 = Economy, 4 = Protection). If you use supervision with Well Contact Suite this object must be associated with a group.

1 byte

C

W

U

Low

 

18

 

Thermostat Mode

 

A: Mode – status

To read the set operating mode by sending a Byte (1 = Comfort, 2 = StandBy, 3 = Economy, 4 = Protection). If you use supervision with Well Contact Suite this object must be associated with a group.

 

1 byte

 

C

 

R

 

 

T

 

 

 

Low

No. ETS name Function Description Type Flag 1 Priority
C R W T U I
19 Status A: Mid season – status To read the seasonal mode set on the thermostat (0 = MS Not Active, 1 = MS Active) 1 bit C R T Low
20 Enable A: Mid season – control To select the seasonal mode set on the thermostat (0 = MS Not active, 1 = MS Active) 1 bit C W U Low
21 Status A: Summer – Winter – status To read the seasonal mode set on the thermostat (0 = Summer, 1 = Winter) 1 bit C R T Low

22

Enable

A: Summer – Winter – control

To set the seasonal mode on the thermostat

(1 = Winter, 0 = Summer). If it is NOT associated with a group then thermostat A will function in Neutral Zone mode.

1 bit

C

W

U

Low

23 Thermostat Off A: OFF communication – bus

– control

This function is useful in the event of faults on the heat- ing system to disable the valves with a 1 bit. 1 bit C W U Low

 

24

 

Dewpoint

 

A: Thermostat – control

If a 1 bit is sent to this object, the thermostat will show the specific icon on the display, turn OFF and stop the air conditioner (this works only in air conditioning mode and serves for example to avoid condensation on the floor) – Note: The thermostat requires a cyclical send to this object, with a time that can be set in the parameter “Dewpoint Supervision Time”

 

1 bit

 

C

 

 

W

 

 

U

 

 

Low

25 NOT USED

26

Current Setpoint

A: Setpoint – status

To read the temperature setpoint set on the thermostat. If you want Well-contact Suite to know the setpoint cur- rently set on the thermostats, this object must be linked to a group

2 byte

C

R

T

Low

 

 

27

 

 

Setpoint Shift

 

 

A: Setpoint – status, control

To read and control a temperature shift with respect to the current setpoint (setpoint set by ETS on the thermo- stat for the various operating modes CMF, STBY, etc.). The temperature shift permitted is limited to the range set by the parameter: Guest Control Permitted.

If parameter Guest Control Permitted is set to Off the “Setpoint Shift” object does not shift the active setpoint.

 

 

2 byte

 

 

C

 

 

R

 

 

W

 

 

T

 

 

 

 

 

 

Low

28 Winter Comfort A: Setpoint – status, control To read and set the Winter Comfort setpoint. 2 byte C R W T U Low
29 Winter Standby A: Setpoint – status, control To read and set the Winter Standby setpoint 2 byte C R W T U Low
30 Winter Energy Saving A: Setpoint – status, control To read and set the Winter Economy setpoint 2 byte C R W T U Low
31 Winter Protected A: Setpoint – status, control To read and set the Winter Antifreeze setpoint 2 byte C R W T U Low
32 Summer Comfort A: Setpoint – status, control To read and set the Summer Comfort setpoint 2 byte C R W T U Low
33 Summer Standby A: Setpoint – status, control To read and set the Summer Standby setpoint 2 byte C R W T U Low
34 Summer Energy Saving A: Setpoint – status, control To read and set the Summer Economy setpoint 2 byte C R W T U Low

35

Summer Protected

A: Setpoint – status, control

To read and set the Summer Too Hot setpoint (power-off of climate control if the window is opened, for instance)

2 byte

C

R

W

T

U

Low

36 NOT USED
37 NOT USED
38 NOT USED
Thermostat A: Valves

39

Cooling/Heating Valve

A: Valve

If the “Valve” parameter is set for 2-pipe systems for valve management: to be used to control the head of a radiating system or the On/Off valve of a fan coil

1 bit

C

R

T

Low

40 NOT USED
41 NOT USED
42 NOT USED
Thermostat A: Fan

43

Proportional (0-100%)

A: Fan Inputs

Used to set a proportional speed for the fan coil fan (if the selected fan is proportional with 3 speeds) via a su- pervisor (e.g., touch screen)

1 byte

C

W

U

Low

No. ETS name Function Description Type Flag 1 Priority
C R W T U I
44 NOT USED
45 V1 speed A: Fan Inputs Used to force activation of fan coil speed V1 (if the selected fan has 3 speeds) 1 bit C W U Low
46 V2 speed A: Fan Inputs Used to force activation of fan coil speed V2 (if the selected fan has 3 speeds) 1 bit C W U Low
47 V3 speed A: Fan Inputs Used to force activation of fan coil speed V3 (if the selected fan has 3 speeds) 1 bit C W U Low

48

Automatic

A: Fan Inputs

Used to force activation of fan coil speed AUTO (if the selected fan has 3 speeds)

1 bit

C

W

U

Low

49 NOT USED

50

Off

A: Fan Outputs

Used to read the deactivation status of all 3 speeds (if the selected fan has 3 speeds). The thermostat sends a 1 bit when the fan is off (fan coil speed 0).

1 bit

C

R

T

Low

51

V1 speed

A: Fan Outputs

This is the object to pair with the relay of speed 1 of the fan coil (to read the status of speed V1 of the fan coil, this object can be polled by the bus)

1 bit

C

R

T

Low

52

V2 speed

A: Fan Outputs

This is the object to pair with the relay of speed 2 of the fan coil (to read the status of speed V2 of the fan coil, this object can be polled by the bus)

1 bit

C

R

T

Low

53

V3 speed

A: Fan Outputs

This is the object to pair with the relay of speed 3 of the fan coil (to read the status of speed V3 of the fan coil, this object can be polled by the bus)

1 bit

C

R

T

Low

COMMUNICATION OBJECTS

54 V1 speed A: Fan Disable To disable speed V1 (if the selected fan has 3 speeds) 1 bit C R W T U Low
55 V2 speed A: Fan Disable To disable speed V2 (if the selected fan has 3 speeds) 1 bit C R W T U Low
56 V3 speed A: Fan Disable To disable speed V3 (if the selected fan has 3 speeds) 1 bit C R W T U Low
Thermostat A: Window

57

Window Sensor

A: Window

Object to be paired with the input to which a win- dow-contact is connected so that the thermostat switches to OFF-PROTECTED when the window is

opened, depending on whether the mode is Air Condi- tioning or Heating

1 bit

C

W

U

Low

Thermostat A: Scenario
58 Scenario A: Scenario To activate a scenario with a 1 Byte message 1 byte C W U Low
Thermostat A: Auto/Man

59

Temperature: Automatic/Manual

A: Manual operation

To see whether the guest has altered the thermostat temperature setpoint with respect to the default setting

1 bit

C

R

T

Low

60

Fan coil: Automatic/Manual

A: Manual operation

To see whether the guest has altered the fan coil speed with respect to the default setting

1 bit

C

R

T

Low

61

Temperature: Disable Local operation

A: Manual operation

Activating this object prevents the guest from altering the setpoint temperature by means of the thermostat buttons with respect to the value set by the bus

1 bit

C

W

U

Low

62

Fan coil: Disable Local Operation

A: Manual operation

Activating this object prevents the guest from altering the fan coil speed by means of the thermostat buttons with respect to the value set by the bus

1 bit

C

W

U

Low

Thermostat A: Floor Probe Alarm
63 Temperature Floor A: Alarm If the temperature limitation is active an alarm is sent when the temperature exceeds the set threshold 1 bit C R T Low
THERMOSTAT B:

64

Comfort

B: Mode – control

To select COMFORT operating mode by sending a 1 bit or to set the thermostat to STANDBY by sending a 0 bit

1 bit

C

W

U

Low

65 Energy Saving B: Mode – control To select ECONOMY operating mode by sending a 1 bit (a 0 bit is ignored) 1 bit C W U Low
No. ETS name Function Description Type Flag 1 Priority
C R W T U I

66

Protected

B: Mode – control

To select ANTIFREEZE operating mode (or Too Hot in the case of air conditioning) by sending a 1 bit.

1 bit

C

W

U

Low

67 Off B: Mode – control To select OFF operating mode by sending a 1 bit (a 0 bit is ignored) 1 bit C R W U Low

68

Thermostat Mode

B: Mode – control

To select operating mode by sending a Byte (1 = Comfort, 2 = StandBy, 3 = Economy, 4 = Protection). If you use supervision with Well Contact Suite this object must be associated with a group.

1 byte

C

W

U

Low

 

69

 

Thermostat Mode

 

B: Mode – status

To read the set operating mode by sending a Byte (1 = Comfort, 2 = StandBy, 3 = Economy, 4 = Protection). If you use supervision with Well Contact Suite this object must be associated with a group.

 

1 byte

 

C

 

R

 

 

T

 

 

 

Low

70 Status B: Mid season – status To read the seasonal mode set on the thermostat (0 = MS Not Active, 1 = MS Active)
71 Enable B: Mid season – control To select the seasonal mode set on the thermostat (0 = MS Not active, 1 = MS Active)
72 Status B: Summer – Winter – status To read the seasonal mode set on the thermostat (0 = Summer, 1 = Winter) 1 bit C R T Low

73

Enable

B: Summer – Winter – control

To set the seasonal mode on the thermostat

(1 = Winter, 0 = Summer). If it is NOT associated with a group then thermostat B will function in Neutral Zone mode.

1 bit

C

W

U

Low

74 Thermostat Off B: OFF communication – bus

– control

This function is useful in the event of faults on the heat- ing system to disable the valves with a 1 bit. 1 bit C W U Low

 

75

 

Dewpoint

 

B: Thermostat – control

If a 1 bit is sent to this object, the thermostat will show the specific icon on the display, turn OFF and stop the air conditioner (this works only in air conditioning mode and serves for example to avoid condensation on the floor) – Note: The thermostat requires a cyclical send to this object, with a time that can be set in the parameter “Dewpoint Supervision Time”

 

1 bit

 

C

 

 

W

 

 

U

 

 

Low

76 NOT USED

77

Current Setpoint

B: Setpoint – status

To read the temperature setpoint set on the thermostat. If you want Well-contact Suite to know the setpoint cur- rently set on the thermostats, this object must be linked to a group

2 byte

C

R

T

Low

 

78

 

Setpoint Shift

 

B: Setpoint – status, control

To read and control a temperature shift with respect to the current setpoint (setpoint set by ETS on the thermo- stat for the various operating modes CMF, STBY, etc.). The temperature shift permitted is limited to the range set by the parameter: Guest Control Permitted. If param- eter Guest Control Permitted is set to Off the “Setpoint Shift” object does not shift the active setpoint.

 

2 byte

 

C

 

R

 

W

 

T

 

 

 

Low

79 Winter Comfort B: Setpoint – status, control To read and set the Winter Comfort setpoint. 2 byte C R W T U Low
80 Winter Standby B: Setpoint – status, control To read and set the Winter Standby setpoint 2 byte C R W T U Low
81 Winter Energy Saving B: Setpoint – status, control To read and set the Winter Economy setpoint 2 byte C R W T U Low
82 Winter Protected B: Setpoint – status, control To read and set the Winter Antifreeze setpoint 2 byte C R W T U Low
83 Summer Comfort B: Setpoint – status, control To read and set the Summer Comfort setpoint 2 byte C R W T U Low
84 Summer Standby B: Setpoint – status, control To read and set the Summer Standby setpoint 2 byte C R W T U Low
85 Summer Energy Saving B: Setpoint – status, control To read and set the Summer Economy setpoint 2 byte C R W T U Low

86

Summer Protected

B: Setpoint – status, control

To read and set the Summer Too Hot setpoint (power-off of climate control if the window is opened, for instance)

2 byte

C

R

W

T

U

Low

87 NOT USED
Thermostat B: Valves

90

Cooling/Heating Valve

B: Valve

If the “Valve” parameter is set for 2-pipe systems for valve management: to be used to control the head of a radiating system or the On/Off valve of a fan coil

1 bit

C

R

T

Low

No. ETS name Function Description Type Flag 1 Priority
C R W T U I
Thermostat B: Fan

94

Proportional (0-100%)

B: Fan Inputs

Used to set a proportional speed for the fan coil fan (if the selected fan is proportional or 8-bit with 3 speeds) via a supervisor (e.g., touch screen)

1 byte

C

W

U

Low

95 NOT USED
96 V1 speed B: Fan Inputs Used to force activation of fan coil speed V1 (if the selected fan has 3 speeds) 1 bit C W U Low
97 V2 speed B: Fan Inputs Used to force activation of fan coil speed V2 (if the selected fan has 3 speeds) 1 bit C W U Low
98 V3 speed B: Fan Inputs Used to force activation of fan coil speed V3 (if the selected fan has 3 speeds) 1 bit C W U Low

99

Automatic

B: Fan Inputs

Used to force activation of fan coil speed AUTO (if the selected fan has 3 speeds)

1 bit

C

W

U

Low

100

Proportional (0-100%)

B: Fan Outputs

Used to read the proportional speed of the fan coil fan (if the selected fan is proportional or 8-bit with 3 speeds). This object is used for controlling proportional actuators.

1 byte

C

R

T

Low

101

Off

B: Fan Outputs

Used to read the deactivation status of all 3 speeds (if the selected fan has 3 speeds). The thermostat sends a 1 bit when the fan is off (fan coil speed 0).

1 bit

C

R

T

Low

COMMUNICATION OBJECTS

102

V1 speed

B: Fan Outputs

This is the object to pair with the relay of speed 1 of the fan coil (to read the status of speed V1 of the fan coil, this object can be polled by the bus)

1 bit

C

R

T

Low

103

V2 speed

B: Fan Outputs

This is the object to pair with the relay of speed 2 of the fan coil (to read the status of speed V2 of the fan coil, this object can be polled by the bus)

1 bit

C

R

T

Low

104

V3 speed

B: Fan Outputs

This is the object to pair with the relay of speed 3 of the fan coil (to read the status of speed V3 of the fan coil, this object can be polled by the bus)

1 bit

C

R

T

Low

105 V1 speed B: Fan Disable To disable speed V1 (if the selected fan has 3 speeds) 1 bit C R W T U Low
106 V2 speed B: Fan Disable To disable speed V2 (if the selected fan has 3 speeds) 1 bit C R W T U Low
107 V3 speed B: Fan Disable To disable speed V3 (if the selected fan has 3 speeds) 1 bit C R W T U Low
Thermostat B: window

 

108

 

Window Sensor

 

B: Window

Object to be paired with the input to which a win- dow-contact is connected so that the thermostat switches to OFF-PROTECTED when the window is

opened, depending on whether the mode is Air Condi- tioning or Heating

 

1 bit

 

C

 

 

W

 

 

U

 

 

Low

Thermostat B: scenario
109 Scenario B: Scenario To activate a scenario with a 1 Byte message 1 byte C W U Low
Thermostat B: Auto/Man

110

Temperature: Automatic/Manual

B: Manual operation

To see whether the guest has altered the thermostat temperature setpoint with respect to the default setting

1 bit

C

R

T

Low

111 Fan coil: Automatic/Manual B: Manual operation To see whether the guest has altered the fan coil speed with respect to the default setting 1 bit C R T Low

112

Temperature: Disable Local operation

B: Manual operation

Activating this object prevents the guest from altering the setpoint temperature by means of the thermostat buttons with respect to the value set by the bus

1 bit

C

W

U

Low

113

Fan coil: Disable Local Operation

B: Manual operation

Activating this object prevents the guest from altering the fan coil speed by means of the thermostat buttons with respect to the value set by the bus

1 bit

C

W

U

Low

No. ETS name Function Description Type Flag 1 Priority
C R W T U I
Thermostat B: Floor Probe Alarm
114 Temperature Floor B: Alarm If the temperature limitation is active an alarm is sent when the temperature exceeds the set threshold 1 bit C R T Low
GLOBAL
107 NOT USED
108 NOT USED
121 Value Humidity To know and view the humidity read by a KNX probe connected to the bus 1 byte C W U Low
121 Value Humidity To know and view the humidity read by a KNX probe connected to the bus (*) 2 byte C W U Low
122 Make up room (MUR) 1 bit C W U Low
123 Do not disturb (DND) 1 bit C W U Low

124

Scenario (Star version)

1 bit

C

W

U

Low

Number of communication objects Max. number of group addresses Max. number of associations
109 254 255

General

ETS text Values available Comment
[Default value]

 

Type of thermostat

You can choose be- tween the .F, .S and

.H articles that can be recognised by the icon on the top left of the device

 

 

 

Value shown on the display

0 = Show Room tem- perature You can choose whether to view on the display: the tem- perature measured, the fan coil speed and the valve status, no information, the temperature delta compared to the Setpoint set by the project
1 = Current setpoint
2 = Display Off
3 = View Setpoint Dif- ference
[0]

Visibility of operating modes

Yes

Possibility of disabling the operating mode setting button on the display

No
[Yes]

 

Heating icon visible

Yes

Possibility of disabling the heating icon on the display

No
[Yes]

 

Cooling icon visible

Yes

Possibility of disabling the air conditioning icon on the display

No
[Yes]

Button Activation

0 = Enable You can choose whether to make the thermostat buttons operative
1 = Disable
[0]
Temperature Unit of meas- ure 0 = Celsius

Only for the display

1 = Fahrenheit
[0]

Percentage displayed

0 = None To view the humidity on the display as a percentage or a 2 Byte value
1 = Humidity
2 = Percentage
[1]

Mid Season Management

0 = Enable To invert primary and secondary
1 = Disable
[0]

External Temperature Sensor

Yes To enable a possible external temperature sensor
No
[Yes]

 

 

 

Brightness control

0 = Manual

You can choose between Automatic control, based on the brightness sensor

on the thermostat, or Manual, for which we recommend you set the Brightness level OFF < than the Brightness level ON.

1 = Automatic

[0]

Display table

Backlighting
Backlighting Parameters

ETS text Values available

[Default value]

Comment

 

Background colour

0 = Default Colours

To choose whether to use default colours or to cus- tomise them by setting RGB values

1 = Customised Colours
[0]

Colour

To set the colour

Digital Input
Digital Input Parameters

ETS text Values available Comment
[Default value]

Input Function

0 = General Use If set as “General use”, it also sends 0/1 over the bus towards a supervisor
1 = Window Sensor
[0]

 

 

 

 

 

Function (for gener- al use)

0 = Switching on Rising Edge Rising edge = close contact
1 = Toggle on Rising Edge Falling edge = open contact

2 = Switching on Falling Edge

Switching = sends a 1 bit value (On/Off) on opening and the opposite on closing

3 = Toggle on Falling Edge

Toggle = on every defined edge (opening or closure), On and then Off is sent to the cycle

4 = Status Send

To send the contact status upon each switching and also cyclically.
[0]
Window Sensor Mode (for thermo- stat-A and thermo- stat-B) 0 = Deactivated Defines whether the window sensor is normally open or closed.
1 = Normally Open
2 = Normally Closed
[0]

Internal/External Temperature Sensor (Thermostat-A, Thermostat-B)
Sensor parameters

Thermostat-B)

Sensor parameters

ETS text Values available Comment
[Default value]

 

 

 

 

Send on Change

 

0.. 1.0 °C

 

Sets the minimum measured tem- perature change with respect to the setpoint that will

cause the thermostat to send the current value over the bus to a supervisor.

ETS text Values available Comment
[Default value]

Temperature Offset

-2 °C…. +2 °C Calibration of thermo- stat reading

(or of average of probes)

[0]

 

[0 = Off]

 

 

Cyclic Send Time

0…30 min.

0=Off.

Activates cyclic send of object no. 0 “In- ternal Sensor” or no. 1 “External Sen- sor” (both for the thermostat A and for  thermostat  B)

[0 = Off]

Continued
Note: If you use the Well Contact Suite supervision system to update the value displayed by the supervision station of the “A/B Current Temperature” linked to objects nos. 10 and 11, you must enable cyclic send or send on change. In the event of a conjunction of a high number of thermostats, it is not advisable to enable numerous cyclic sends with timing that is too low to avoid overloading the BUS communications.

Thermostat (A/B) Guest control permitted

ETS text Values available Comment ETS text Values available Comment
[Default value] [Default value]
0 = Off 0.1, 0.2….1 For thermostat, A setpoint shift step upon receipt of control on objects 115 and 116
1 = 1.0 °C Setpoint shift step
2 = 2.0 °C [1]
Determine how much the
3 = 3.0 °C
Guest control per- guest can change the set-
mitted 4 = 4.0 °C point from the value set on
the thermostat (up/down)
5 = 5.0 °C
6 = None Limitation
[3]

Current Temperature (A/B)

ETS text Values available Comment
[Default value]

 

Temperature sen- sor weightings

0… 100

For the thermostat’s internal sensor, the Vimar wired NTC probe (if present) and the KNX probes, this determines the relative importance for calculating the weighted av- erage of the measured tem- peratures

[0]

 

 

Cyclic Send Time

0 = Off

Sets the frequency in minutes with which the thermostat (A/B) must send the measured tem- perature value (or the weighted average of the probes) over the bus to a supervisor. Activates cyclic send of object no. 10 and

11 “Current Temperature” of thermostat A/B

11 = 30 min.

[0 = Off]

 

 

Send on Change

0 = Off Sets the temperature difference measured by the thermostat (A/B) that results in the read val- ue (or the weighted average of the probes) being sent over the bus towards a supervisor. Acti- vates cyclic send of object no. 10 and 11 “Current Tempera- ture” of thermostat A/B

1.0 = 1.0 °C

[0 = Off]

Setpoint (A/B) Setpoint parameters

ETS text Values available Comment
[Default value]

 

Mode at bus power on

1 = Comfort

 

Thermostat operating mode at bus power on

2 = Standby
3 = Energy saving
4 = Protect
255 = Last Mode Selected
[255]

 

 

Time between Heating and Cooling

1 min.

 

To avoid the formation of condensation with radiating systems during changes of season

10 min.
15 min.
20 min.
25 min.
30 min.
45 min.
60 min.
[30]

 

 

 

 

Dewpoint Supervision Time

0 = Off

Sets the time within which the thermostat must receive a message to the “Dewpoint” object from

a device connected to a humidistat.

A bit set to “1” will stop heating/air conditioning and set to “0” will cause it to restart. If messages have not arrived, when this time has elapsed heating/air con- ditioning will restart

30 sec
1 min.
2 min.
3 min.
4 min.
5 min.
10 min.
15 min.
20 min.
25 min.
30 min.
[0 = Off]

 

 

 

 

Cyclic Send Time

0 = Off

 

 

 

Sets the time for cyclic sending of temperature setpoint over bus towards a supervisor

30 sec.
1 min.
2 min.
3 min.
4 min.
5 min.
10 min.
15 min.
20 min.
25 min.
30 min.
[0 = Off]

 

 

 

 

Send on Change

0 = Off

 

 

Sets the minimum temper- ature change made by the guest with respect to the setpoint that results in the current setpoint being sent over the bus towards a supervisor

0.1 °C
0.2 °C
0.3 °C
0.4 °C
0.5 °C
0.6 °C
0.7 °C
0.8 °C
0.9 °C
1.0 °C
[0 = Off]

 

 

Reset Setpoint Shift in Economy Mode

Yes

By selecting “Yes”, when the thermostat goes into Energy Saving (Economy) mode, the setpoint set by the user in Comfort and Standby mode is reset to the design default value. This function is useful for hotel appli- cations and with the Well Contact Suite supervision software.

No

[Yes]

Important: The “Time between Heating and Cooling” parameter is the wait time it takes for the thermostat to switch from summer-winter and vice versa. This parameter is especially useful in some underfloor radiant systems where you set a high time value to prevent the formation of condensation; this applies especially when the thermostats work with a neutral zone and so there could be multiple seasonal changes in a single day. If instead, depending on the type of system, you want a faster response of the thermostat, it is necessary to reduce the value of this parameter.

Temperature Setpoint (A/B) Sensor parameters

ETS text Values available Comment
[Default value]
Winter Comfort Setpoint [20] See “Range” table
Winter Standby Setpoint [18] See “Range” table
Winter Energy Saving Setpoint [15] See “Range” table

 

 

 

Antifreeze

0 = Control Off

If you set “On” you can set the temperature the

thermostat goes to in “Protected” mode; if you set “Off”, when the thermostat is in “Protected” mode it will turn off tempera- ture control and will not send the current setpoint temperature

1 = Control On

[1 = 011]

Summer Comfort Setpoint [25] See “Range” table
Summer Standby Setpoint [28] See “Range” table
Summer Energy Saving Setpoint [30] See “Range” table

Setpoint range

Temp. °C Temp. °C Temp. °C Temp. °C
5         16        27        38
6         17        28        39
7         18        29        40
8         19        30        41
9         20        31        42
10        21        32        43
11        22        33        44
12        23        34        45
13        24        35       
14        25        36       
15        26        37       

CAUTION: When the thermostat is in Neutral Zone mode, the breadth of this must be progressively increasing for the different operating modes of Comfort (minimum neutral zone breadth), Standby, Energy Saving, and Protected. This setting made with ETS ensures that, when the thermostat changes operating mode, the active setpoint is always at a suitable value and the thermostat does not start cooling if it was heating before or vice versa, causing considerable energy consumption.

ETS text Values available Comment
[Default value]
If you set “On”
0 = Control Off you can set the temperature the
thermostat goes to in
“Protected” mode; if
Too hot 1 = Control On you set “Off”, when the thermostat is in
“Protected” mode it
will turn off tempera-
[1 = On] ture control and will not send the current
setpoint temperature

Note: In the case of a 4-pipe system, the winter setpoint cannot take a higher value than the summer setpoint.

 

Window sensor (A/B) Sensor parameters

ETS text Values available Comment
[Default value]

Window sensor delay

0 = Off Sets the time delay that heating/air conditioning stops after window open detection
8 = 120 sec.
[4 = 30]

Control parameters

ETS text Values available Comment
[Default value]

Control Temperature

0 = Control On/Off

Set according to the type of control required for the heat- ing/air conditioning system

1 = Integral Band
2 = Proportional/Integral Band
[0]

 

 

 

 

 

 

Value Proportional Cooling

1.0 °C

 

 

 

 

 

 

To be set according to the characteristics of the system and the room (consult a heating engineer)

1.1 °C
1.2 °C
1.3 °C
1.4 °C
1.5 °C
1.6 °C
1.7 °C
1.8 °C
2.0 °C
2.2 °C
2.5 °C
3.0 °C
3.5 °C
4.0 °C
4.5 °C
5.0 °C
[3.0 °C]

Continuous integral proportional: PI control with proportional valve

The parameters of the proportional and integral coefficients Kp and Ki are set using the ETS software: the proportional coefficient Kp for heating corresponds to the “Heating Proportional Value” parameter while the coefficient for cooling is set using the “Cooling Proportional Value” parameter. The integral time Ti is set with the “Heating Integral Value” and “Cooling Integral Value” parameters for heating and cooling, respectively. The PI control parameters should be set according to the type of heating or cooling system used, the size of the room and its thermal insulation.
IMPORTANT: Generally, when using fan coils, PI control is not used. The valve is typically managed with On/Off control and an On/Off valve or proportional valve (0%-100%); the fine adjustment is then made using the fan speed.

Proportional integral PWM: PI control with On/Off valve

Communication objects and ETS parameters

ETS text Values available Comment
[Default value]

 

 

 

 

 

 

 

Integral Cooling Value

5 min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To be set according to the characteristics of the system and the room (consult a heating engineer)

6 min.
7 min.
8 min.
9 min.
10 min.
12 min.
15 min.
17 min.
20 min.
25 min.
30 min.
40 min.
50 min.
60 min.
90 min.
120 min.
[20 min.]

 

 

 

 

 

 

 

Proportional Heating Value

0 = Off
1.0 °C
1.1 °C
1.2 °C
1.3 °C
1.4 °C
1.5 °C
1.6 °C
1.7 °C
1.8 °C
2.0 °C
2.2 °C
2.5 °C
3.0 °C
3.5 °C
4.0 °C
4.5 °C
5.0 °C
[3.0 °C]

 

 

 

 

 

 

 

Integral Heating Value

0=Off
5 min.
6 min.
7 min.
8 min.
9 min.
10 min.
12 min.
15 min.
17 min.
20 min.
25 min.
30 min.
40 min.
50 min.
60 min.
90 min.
120 min.
[20 min.]

 

Differential Coefficient

0.1… 1.0 °C

For On/Off type control: set the thermostat (A/B) hysteresis that determines activation/deactivation of

the system with reference to the difference between the setpoint and the measured temperature

[1=0.2]

Valve (A/B) Valve parameters

ETS text Values available Comment
[Default value]

 

 

System Layout

0 = 2-Pipe Circuit On/ Off

 

 

Select according to the type of installed system

1 = 4-Pipe Circuit On/ Off
2 = 2 Pipes Proportional
3 = 4 Pipes Proportional
[0]

Cyclic Send Time in Cooling

0 = Off.. 30 min. Sets the valve status send time to the associated actu- ators (parameter required for certain types of valves, for example Theben proportion- al valves, etc.)
[0]
Cyclic Send Time in Heating 0 = Off.. 30 min.
[0]

2nd Heating/Cooling Stage (A/B) “Boost
The second stage is used to control a second heating or cooling source that allows the “boost” function. The “boost” function enables the second auxiliary source when the current temperature differs from the current setpoint by more than the set threshold. In this way, the main heating/cooling stage is assisted by the auxiliary source to reach the desired setpoint value faster. This feature is particularly useful for improving comfort in dynamic lens systems such as underfloor systems.

2nd Stage Parameters

ETS text Values available Comment
[Default value]

 

 

 

 

 

 

 

 

2nd Stage Cooling Valve

Disabled

Second cooling stage off

Enable 2-point On-Off Control

Control with object that sends on/off for valve status

Enable 2-point Control 0-100%

Control with object that sends 0% for valve off status and 100% for valve on status
Cooling Threshold:

– 0.5°C

– 1.0°C

– 1.5°C

– 2.0°C

– 2.5°C

– 3.0°C

– 3.5°C

– 4.0°C

– 4.5°C

– 5.0°C

 

 

Value of the trigger threshold in cooling mode

 

 

 

 

 

 

 

 

 

2nd Stage Heating Valve

Disabled

Second heating stage off.

Enable 2-point On-Off Control

Control with object that sends on/off for valve status

Enable 2-point Control 0-100%

Control with object that sends 0% for valve off status and 100% for valve on status
Heating Threshold:

– 0.5°C

– 1.0°C

– 1.5°C

– 2.0°C

– 2.5°C

– 3.0°C

– 3.5°C

– 4.0°C

– 4.5°C

– 5.0°C

 

 

Value of the trigger threshold in heating mode

Fan (A/B)
Fan parameters

ETS text Values available Comment ETS text Values available Comment
[Default value] [Default value]

 

 

 

 

Type

 

0 = Off

No thermostat controlled fan coil.

Disables the graphics for the fan on the thermostat too. Useful when controlling only the solenoid valve for a radiator system

 

 

 

 

 

Time in Fan Man. Mode (min.)

 

 

0…255

 

Duration of “Manual Forcing” for the fan speed if the guest has forced the speed; after this time the thermostat returns to automatic mode. If the parameter is set to “0” it is interpreted as “Time = infinite” and the fan speed, set manually, stays on. To restore automatic opera- tion the guest must return the fan speed to AUTO by manually operating on the thermostat display.

1 = Three Speeds Fan coil Fan coil with 3 speeds
2 = Proportional

(0 – 100%)

Proportional-speed fan coil

 

 

[0]

[1]

Maximum Fan Speed

0 Sets maximum fan coil speed.

Set “0” to control only the solenoid valve for a radiator system

1
2
3
[3]

Objects

0 = 1-bit object Select type of object (1 bit for On/Off, 8 bits for propor- tional 1-100%)

 

 

 

Threshold for Fan Speed. 2

0.2 °C

 

 

Sets the difference between the current temperature and the setpoint that triggers start of speed V-2

1 = 8-bit object (1-100%)
0.3 °C
0.5 °C
[0]
1.0°C

Cyclic Send Time

0 = Off Set cyclical sending over the bus for the fans
1.5°C
11 = 30 min.
2.0 °C
[0 = Off]
2.5 °C

Threshold for Speed at 100%

0 = 2 °C

Absolute difference between setpoint and current tem- perature above which the speed goes to 100%

3.0 °C
1 = 3 °C
3.5 °C
2 = 4 °C
4.0 °C
4 = 5 °C
[1.0]
[4]

 

 

 

Threshold for Fan Speed. 3

0.2 °C

 

 

Sets the difference between the current temperature and the setpoint that triggers start of speed V-3

 

Minimum Fan Speed

0 = 10%

 

Minimum operating speed on fan activation

0.3 °C
1 = 20%
0.5 °C
2 = 30%
1.0°C
3 = 40%
1.5°C
4 = 50%
2.0 °C
[0]
2.5 °C

Fans independent of the valve

Yes

Possibility of controlling the fans even with the valve off

3.0 °C
3.5 °C No
4.0 °C
[No]
[2.0]

Automatic speed disabling

Yes Possibility of disabling the fan button on the display and objects 43 and 90 (Au- tomatic)

 

 

 

Fan Speed Hysteresis

0.1 °C

 

 

 

Hysteresis for the

above-mentioned speed values

0.2 °C No
0.3 °C
[No]
0.4 °C
0.5 °C
0.6 °C
0.7 °C
0.8 °C
0.9 °C
1.0 °C
[1=0.1]
Switching Time between Speeds (min) 0…255 Time, in minutes, it takes to switch from one speed to another.
[2]

Continued
IMPORTANT: If you set “Switching Time between Speeds (min)” to 0 and leave a low value of “Fan Speed Hysteresis” (<0.5°C) there may be, near the speed change threshold temperatures, continual and repeated switching of the fan coil speeds that could damage it.

Communication objects and ETS parameters

Manual operation of the fans
The user selects the speed used by the thermostat only when the valve is on; if the valve is off at the time of selection, the thermostat saves the setting and uses it again the next time the valve is on. On the display, the fan speed changes from “AUTO” to “OFF”. The selection made by the user remains active until the end of the time (in minutes) set by the “Time in Manual Fan Mode (min)” parameter or the fan speed is set manually onto with the button or remotely via the communication object.

Caution: If the “Time in Manual Fan Mode (min)” parameter is equal to 0 it means that the manual operation of the fan is never turned off by time.

Automatic three-speed fan coil operation

In the case of a three-speed fan coil in “AUTO” mode, the fan coil speed is controlled automatically by the thermostat. The speed automatically goes from the higher to the lower speed gradually as the measured temperature approaches the value set as the setpoint. The threshold to determine the speed to set is linked to the following parameters: “Threshold for the Speed of Fan 2” and “Threshold for the Speed of Fan 3” while speed 1 is active when the valve is turned on and the “Switching time between speeds (min)“ has passed. An example of operation is shown in the following figure where SV2 and SV3 are respectively “Threshold for the Speed of Fan 2” and “Threshold for the Speed of Fan 3”; ΔTR is instead the “Differential Coefficient” of the on/off setting.

Note: In the example shown in the figure, the effect of the “Fan Speed Hysteresis” parameter was overlooked and the “Switching time between speeds” parameter was set = 0.
When the measured temperature reaches the setpoint the thermostat switches off the fan, sends a 1 bit on the Bus for object no. 45 or no. 92 “Off – Fan Outputs” (V0), switches on V0 and switches off V1. When the temperature deviates from the desired value, the valve is turned on and the speed V1, after the value of “Switching time between speeds”, is activated. In the following example figures, this parameter is set to 0.
N.B.: Fore reasons tied to the safety of systems, if the valve is active the user will be unable to set “OFF” from the thermostat. It will therefore be necessary to turn off the valve by setting the thermostat to another mode or by modifying its setpoint.

Communication objects and ETS parameters

Switching Time Between Speeds
This is the time you need to wait for the activation of the speed after switching on the valve (allows the fan coil battery to reach the correct temperature before circulating the air). This parameter is also used between one-speed change and another to avoid continual speed switching near the thresholds.

Proportional fan coil operation
Proportional fan operation is similar to that of the three-speed fan coil. When the valve is OFF the proportional speed is equal to 0%; when the valve is ON the value of the proportional speed depends on the difference between the setpoint and the temperature measured in the room. The greater the difference, the higher the set proportional value of the speed. When this difference exceeds the value of the “Threshold for Speed at 100%” the proportional output of the fan is set to the highest possible speed that is 100%; when the difference is minimal the proportional speed is set to “Minimum Fan Speed”. The operation of the proportional fan, as for the three speeds, can be set automatically or, in manual mode, to the value invoked by the thermostat button or set by the object “Proportional (0-100%) – Fan Inputs”

N.B.: Fore reasons tied to the safety of systems, if the valve is active the user will be unable to set “OFF” from the thermostat. It will therefore be necessary to turn off the valve by setting the thermostat to another mode or by modifying its setpoint.

Scenario (A/B)
16 scenarios are available. 16 different scenarios can therefore be saved on the device output. With Enable Scenario Learning you can also set the status of the output for the desired scenario with a message from the bus (scene learn).

Scenario parameters

ETS text Values available Comment
[Default value]

Scenario Learning

0 = disable To enable scenario thermo- stat learning
1 = enable
[0]

 

Scenario

0=disabled

To define the operating mode when the scenario is called up.

1=Comfort
2=Standby
3=Energy saving
4=Protected
[0]

 

…Scenario 16

0=disabled

To define the operating mode when the scenario is called up.

1=Comfort
2=Standby
3=Energy saving
4=Protected
[0]

Temperature Protection (A/B)
This function is used to limit the temperature of the area controlled by the thermostat

Temperature Protection Parameters
With the “Temperature Channel” parameter you select the temperature to be monitored; when, in heating, it exceeds the value selected with the “Temperature Limit” parameter, the thermostat changes its operating mode and switches OFF sending an alarm signal with the object Floor Temperature Alarm. The thermostat comes out of the alarm condition when the temperature drops below the set threshold and the user changes the thermostat operating mode. The typical application for this function is that of limiting the maximum temperature of the floor.

ETS text Values available Comment
[Default value]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature Channel

0 = Disabled Limitation disabled

1 = Internal Sensor

The internal sensor is used for temperature limitation

2 = External Sensor

The external sensor is used for tempera- ture limitation

3 = External

Temperature 1

The External Tem- perature 1 is used for temperature limitation

4 = External

Temperature 2

The External Tem- perature 2 is used for temperature limitation

5 = External

Temperature 3

The External Tem- perature 3 is used for temperature limitation

6 = External

Temperature 4

The External Tem- perature 4 is used for temperature limitation

7 = External

Temperature 5

The External Tem- perature 5 is used for temperature limitation

8 = External

Temperature 6

The External Tem- perature 6 is used for temperature limitation

9 = External

Temperature 7

The External Tem- perature 7 is used for temperature limitation

10=External Temperature 8

The External Tem- perature 8 is used for temperature limitation
[0]

 

Temperature Limit

10…70 °C

Limit of the tempera- ture channel beyond which the limitation trips

[35]

FAQ

  1. Which thermostat objects must be used in the ETS project?
    For each one, should a dedicated ETS group be created or should “common groups” be created? For the objects listed below, you must create a separate group for each datapoint of each thermostat: In general:
    • Thermostat A: 13 – 63.
    • Thermostat B: 64 -113.
      Specifically:
    • 12 if Thermostat B is present.
      39 if it is a 4 PIPE system and there is a COOLING valve.  for thermostat B.
    • 43 if proportional fan coil present. 94 for Thermostat B.
    • 57 if a window contact that must deactivate climate control is present, 108 for Thermostat B.
      Note.
      You could also create a general group with the Summer/ Winter control of all the thermostats (DATAPOINT 22 for Thermostats A and 72 for Thermostats B), but if it is a system in which there is the Well-contact Suite supervision software we recommend that you create a group for each single Thermostat A and for each single Thermostat B.
  2. What does the “Thermostat Mode” object represent?
    It refers exclusively to the mode the thermostat is currently in (or the mode you want to put it into given that the corresponding object is also present in write mode). It does not indicate whether it is summer or winter. The possible options are:
    • 01 = Comfort
    • 02 = StandBy
    • 03 = Economy
    • 04 = Protect/Off
      To see whether the thermostat is in Off mode you can go and read object 16 “Off A: Mode – control” or object 67 “Off B: Mode – control” which will answer 1 if the thermostat is Off or 0 if it is in another operating mode.
  3. What difference is there between the “Protected” object and “Off” in “Antifreeze-Too Hot” operation?
    The “Protected” object is used and acts as Off in the event that the “Temperature Setpoint” parameters and the items “Antifreeze” and “Too Hot” are set to “Control Off”. So in this case when the object “Protected” is activated, the thermostat entirely disables temperature control and does not even send its current setpoint over the bus. In normal installations it is therefore recommended to set “Control On” on the parameters “Antifreeze” and “Too Hot” and to set the corresponding two temperatures. This avoids the risk of frozen pipes in the winter and excessive room overheating in the summer. The “Off” mode on the other hand also inhibits “Too Hot” and “Antifreeze” and should never be used in normal installations. The “Off Mode“ object turns off the thermostat even if the temperature falls below zero (i.e. it does not activate Heating/Air conditioning). It is advisable to use the “Protected” object, which switches the thermostat to Off or protected (Antifreeze) depending on how the relevant parameters are set (summer or winter)
  4. What is the function of the “Thermostat Off” object and what applications can it have?
    Thermostats have various objects created for operation with our Well-contact Suite hotel software. The “Thermostat Off” object blocks thermostat bus communication (both reception and transmission). This function is dedicated to Vimar supervision software.
  5. What is the function of the “Off” mode and what applications does it have? The “Off Mode” object turns off the thermostat even if the temperature falls below zero (i.e. it does not activate Heating/Air-conditioning). It is advisable to use the “Protected” object, which switches the thermostat to Off or protected (Antifreeze) depending on how
    the relevant parameters are set (summer or winter).
  6. What is the function of the “Comfort” object? Unlike the “Energy Saving”, “Protected” and “Off” objects, which do not permit the sending of a “0” bit, if the “Comfort object is set to “1”, the thermostat switches to comfort mode at the design temperature or at the custom temperature previously set by the guest. If this object is set to “0” the thermostat switches to standby mode (at the design temperature
    or at the custom temperature previously set by the guest).
  7. What is the function of the “Summer Protected” object?
    It is the protected mode setpoint in air conditioning operation. It corresponds to protected mode in heating operation (with air conditioning operation it cools if the temperature exceeds the setpoint whereas with heating operation it heats if the temperature falls below the setpoint).
  8. On thermostats 20542, 16922 and 14522 a single bit as used to activate/deactivate antifreeze. What is used now?
    The “Protected” object (summer or winter) is used.
    Note.
    Antifreeze (or its analogue “Too Hot”) must be active in the object parameters so as not to obtain an Off.
  9. On thermostats 20542, 16922 and 14522, to deactivate “Antifreeze” mode it was sufficient to send a “0”. What needs to be done with the new thermostats?
    Do you need to change mode, for instance “Economy”?
    Yes, the installer decides whether the user can turn the system off or set it to “Antifreeze” mode. Depending on the set ETS parameters, the thermostat switches to “Antifreeze” mode and returns to the previous mode only when the window is opened and closed, whereas if the thermostat is set to “Protected” mode from the bus, it will subsequently be necessary to change the mode.
  10. On thermostats 20542, 16922 and 14522, a single bit was used to read the antifreeze status; in supervision single bits (“0” or “1”) and not bytes are required. Where is this object/status to be found?
    The KNX system uses the 1-byte object “Thermostat Mode” to read the status of the thermostat. If you do not want to use the Byte, you can set the 1-bit mode change object to read. However, this is not the ideal solution because the bits will have to be read explicitly given that the information is not
    sent automatically.
  11. Are there any particular precautions to take when using the 0-100% proportional valve control?
    Never use the “Control Value” object. This is a debug object left inside the application for KNX certification purposes. In this specific case replace it with “Cooling Valve” to obtain the desired function.
    However, some types of valves with proportional control require a cyclic refresh of the control value. In this case it is necessary to activate cyclic sending of the control value to the valve. To control the proportional solenoid valves you must use the “Cooling/Heating Valve” object in read/write mode (which appears only for “2-Pipe Proportional” systems, selected by the parameter “Valves”) or objects “Cooling Valve” and “Heating Valve” will appear if “System Type” is set with the “Proportional 4-Pipe Circuit” parameter.
  12. When the “Output active in heating/air conditioning” appears, does this indicate the winter mode?
    This icon does not indicate summer/winter mode. It appears whenever the thermostat is controlling the relay or corresponding valve; it disappears when the desired temperature has been reached. If the room temperature has already reached the desired value, the icon is not displayed (operation is similar to that of conventional thermostats). The object to be associated with the summer/winter change of season is a different object from the one used for reading the season: nos. 22 and 21 and nos. 73 and 72.
  13. We need to have a group that goes to “0” when the thermostat is set to “Off” (by the guest or the supervisor) and returns to “1” when the thermostat is returned to “CMF”. How can we do this?
    This is an application that allows the input of a Daikin with KNX interface to be forced so that it turns the machine off if the thermostat is Off and back on if it is “CMF” without necessarily starting the system (heating is subsequently activated depending on the messages sent by the thermostat to the valve). In practice the guest wants to use the thermostat for On/Off control of a device that has its own temperature control function. To do this you have to use an object (such as a KNX logic) that sends an On/Off message according to the thermostat mode (using the “Mode” object).
  14. How should a window’s N.C. contact be managed when it is connected to the thermostat for window open signalling?
    The input to which the window contact is connected must be set with the “Status Send” function so that one message is sent when it is opened and another one when it is closed. If an N.C. contact is used, it will be necessary to set “Off” for the falling edge (opening of window and contact) and “On” for the rising edge (closing of the window and contact). If the contact is an N.O. type, the two parameters must be set respectively to “On” and “Off” (when the window is opened the contact is closed and vice versa). If you set the input as “Window Sensor”, opening the window will stop the thermostat writing an “04” byte (antifreeze) to the datapoint “Mode status” and “00” to the datapoint “Cooling/Heating Valve” (closes the valve); closing the window will set the previous status; you can also choose a delay time for opening
    the window after which the thermostat will stop. If together with this internal thermostat management you also want a “0” bit to be sent to the bus when the window is opened and a “1” bit when it is closed, you must set the thermostat IN input as “General Use” so as also to display object no. 110 “Input”. If the window contact is connected to the thermostat’s input, this new object must be associated with a
    group with the “Window Sensor” object, whereas if you use the IN input of another KNX device this will be associated with the “Window Sensor” object.
  15. Which functions are considered most important for use of the thermostats on hotel systems with the Well-contact Suite management/supervision (and other) software?
    • Current Temperature: this is useful for displaying the thermostat temperature in the software (it is advisable to set cyclic sending amongst the parameters; to be considered in the event of a large number of devices).
    • Thermostat Mode or alternatively Comfort, Energy Saving, Protection: these are important for sending thermostat operating mode controls via Well-contact Suite.
    • Thermostat Mode – status: this is important to see the current operating mode of the thermostats in the software.
    • Summer/Winter status: this is important to see the current seasonal operating mode of the thermostats in the software.
    • Enable Summer/Winter: this is essential for sending seasonal thermostat operating mode controls via Wellcontact Suite software.
    • Current Setpoint: this is useful for displaying the set thermostat temperature in the software (it is advisable to set cyclic sending amongst the parameters; to be considered in the event of a large number of devices).
    • Winter Comfort Setpoint, Winter Standby Setpoint, Winter Energy Saving Setpoint, Winter Protected Setpoint, Summer Comfort Setpoint, Summer Standby Setpoint, Summer Energy Saving Setpoint, Summer Protected Setpoint (objects from 28 to 35 and from 79 to 86): they are useful for displaying and setting the various “Basic Setpoints” in the two seasonal operating modes in the software.
      Note. To be able to view the values, you have to set the read flag for these properties manually in ETS
    • Management case studies Heating/air conditioning speed for thermostats: Proportional Three Speed Control  Proportional (0-100%) – Fan Inputs: useful for sending the proportional speed maximum value.
    • Proportional (0-100%) – Fan Outputs: useful for displaying the proportional speed maximum value in the software. On/Off management  Speed V1 – Fan Inputs, Speed V2 – Fan Inputs, Speed V3 – Fan Inputs, Automatic – Fan Inputs: useful for sending speed force controls to the thermostat or for forcing automatic control.
    • Off – Fan Outputs, Speed V1 – Fan Outputs, Speed V2 – Fan Outputs, Speed V3 – Fan Outputs: useful for displaying the current speed of the fan coil.
    • Speed V1 – Disable Fan, Speed V2 – Disable Fan, Speed V3 – Disable Fan: useful for sending speed to disable controls.
    • Window Sensor (objects 57 and 108): viewing the status of the window combined with the thermostat on the supervision software (for example on the computer of a hotel reception desk) requires you to
    • Set the input contact as “General use” and use it as an open window sensor; Assign the address of the desired group to the “Window Sensor” object
    • Assign to this address the “Contact” Address/Object type inside the Well-Contact Suite software. Temperature: Automatic/Manual: useful for displaying whether the setpoint has been set from software or manually using the thermostat buttons. m. Fan coil: Automatic/Manual: useful for displaying whether the current fan coil speed is managed automatically by the thermostat or has been forced.  Temperature: Disable Local Operation: useful for displaying and sending controls from software regarding whether or not it is possible to set the current setpoint on the thermostat manually.
    • Fan coil: Disable Local Operation: useful for displaying and sending controls from software regarding whether or not it
      is possible to set the speed manually from the thermostat.
  16. To perform supervision of thermostats using Vimar Wellcontact Suite software, what communication objects need to be set?
    YOU have to set to “Read” the relevant flags of objects from 28 to 35 and from 79 to 86 for every 21814 thermostats.
  17. What is the parameter “Time in Manual Fan Mode” used for?
    It is a time indicated in the parameters for which the thermostat remains in “Manual forcing” if the guest has manually forced the temperatures or speed of the fan coil: when this time has elapsed the thermostat returns to automatic. If the parameter is set to “0” it is interpreted as “Time = infinite” and the manual forcing stays on.
  18. An object is needed that goes to “1” if one of the 3 speeds is activated and returns to “0” if V 1/2/3 are deactivated.
    Use the object “Cooling/Heating valve”.
  19. Is it possible to take an object to “0” when a speed V-0 is set from the thermostat?
    No, it is not possible to set the speed V-0 manually.
  20. Is the object “Thermostat Mode – Mode” (objects 17 and 68) usable only by Well-Contact Suite or also by other supervision software?
    The object “Thermostat Mode – Mode” is a KNX standard object, with coding defined by the standard (HVAC Operating Mode 20.102), therefore it can also be used by other supervision software; there is also a related object for reading the mode (objects 18 and 69).
    • 0 = Automatic
    • 1 = Comfort
    • 2 = StandBy
    • 3 = Economy
    • 4 = Protection
    • 5-255 = Reserved values
  21. Is it possible to manage a general valve if there is more than one thermostat?
    This function is possible only with a logic module. It is also possible to use a Well-contact Suite functional logic, which will operate only if the supervision software is active and communicating with the bus.
  22. Is it possible to control a proportional-type fan coil with one or two supply values?
    The thermostat normally controls supply at three levels of intensity: 33%, 67%, 100%. As can be seen in the following image, setting the maximum speed to 1 or 2 results in one or two thresholds (respectively 33% or 33-67%). Other supply-level settings are not possible. For the TACTIL thermostat 21814, you can still control the proportional fan coil with a minimum speed settable from 10% to 50% and with a maximum speed up to 100%
  23. Is it possible to control an On/Off type radiant heating system and a fan coil air-conditioning system with 3 speeds?
    You have to work prevalently with the thermostat object “Enable Summer/Winter”. Firstly, the type of system must be 4 pipes On/Off. Next, configure all the standard data points required by the thermostat to operate correctly. Add the following groups: group 1 “Enable – Summer/Winter”: to perform the season change on the thermostat and disable the 3 speeds:
    • “Speed V1 – Disable fan”
    • “Speed V2 – Disable fan”
    • “Speed V3 – Disable fan”
    • “Status – Summer/winter” group 2
    • To operate the radiating system with On/Off valve in winter
    • “Heating valve – valve”
    • Relay” (the relay of the device controlling the underfloor system valve)
      Note: you can add to the group the object “Fan coil: Disable Local Operation” to disable the user interface of the fan coil during the winter season. group 3
      To operate the fan coil general On/Off valve in the summer:
    • “Cooling valve – Valve”
    • “Relay” (the relay of the device controlling the fan coil valve). group 4
      To control the fan coil speed V1 in summer:
    • “Relay” (the relay of the device controlling the speed-1 of the fan coil)
    • “Speed V1 – Fan Outputs”. group 5
    • To control the fan coil speed V2 in summer
    • “Relay” (the relay of the device controlling the speed-2 of the fan coil)
    • “Speed V2 – Fan Outputs”. group 6
    • To control the fan coil speed V3 in summer:
    • “Relay” (the relay of the device controlling the speed-3 of the fan coil)
    • “Speed V3 – Fan Outputs”. In this configuration, when the thermostat is in Winter mode, group 1 goes to “1” so the fan coil speeds are forcibly disabled to block their operation and the thermostat operates in On/Off only on the radiant heating valve as it is configured for 4-pipe On/Off systems with group 2; in Summer group 1 goes to “0” and the 3 speeds can again be controlled from
      the bus; furthermore, the thermostat will operate with the general fan coil cooling valve of group 3. Groups 4, 5 and 6 are those of the 3 speeds and objects for the thermostat and they can be controlled from the thermostat when the first group goes to “0” by setting the thermostat in summer mode.
  24. What objects are used to read the thermostat temperatures from the Well-Contact Suite software?
    For thermostats 21814, objects 11 and 12 (weighted averages of the temperatures that can be associated) are used to read respectively the current temperatures of thermostats A/B, and not objects 0 and 10 of the device (which are the precise measurement data for the individual internal/external probes).
  25. Is it possible to eliminate the adjustment range in Comfort mode, which can be expanded at the most to ± 5°C?
    It is possible by setting the parameter “Guest Control Permitted” to “No Limitation”.
  26. If a 0-100% proportional fan coil rather than a three-speed fan coil is controlled, will values 0-100% be sent to the fan coil?
    Yes, if the “Type” fan parameter is selected on the “Proportional (0-100%)”.
  27. How is the “Dewpoint” object used?
    This object is used in systems with underfloor cooling and is associated with a KNX humidistat capable of detecting a level of humidity at which condensation may form on the floor. By activating the ETS group for this object, the thermostat will automatically go to “Off” mode, stopping air conditioning. It is possible to set a time limit after which the thermostat will automatically go to “Off” if a message has not arrived from the KNX humidistat. This operation does not occur in heating mode.
  28. How does the “Comfort” object work?
    If “1” is sent to this object, the thermostat goes to “CMF” mode (unless the window has been opened in the event of window-contact control); if “0” is sent the thermostat goes to “Standby” mode
  29. IS it possible for a thermostat to control a 0-100% proportional valve and an On/Off valve simultaneously?
    No, it is not possible as setting the thermostat for proportional control disables On/Off control on the valve object. With two-zone thermostats (02952, 20430 and similar), it is possible to operate “Thermostat-A” in one mode and “Thermostat-B” in the other, but the guest would have to set both each time to activate both the proportional valve and the On/Off valve.
  30. Can the thermostat be controlled by supervisors such as the KNX touch screen?
    Yes, the thermostats are KNX standard so a KNX-certified supervisor is capable of managing them.
  31. How can operations performed by the guest on the thermostat (change of temperature and functions) be inhibited?
    Using the objects “Temperature: Disable Local Operation” and “Fan coil: Disable Location Operation” you can block changes to fan coil temperature and speed. It is not possible to block the operating mode because the guest cannot decide this directly. For example, the guest can force the thermostat to Off only by opening the window or can set it to standby only by leaving the room (removing the card from the pocket reader).
  32. If a 1-bit thermostat comfort/stby object is associated with the “Guest in room” pocket object, when the Wellcontact Suite software is started up, the thermostats that were in “Economy” or “Protected/Off” mode return automatically to STBY with higher setpoints.
    The “U” flag must be disabled in ETS for the thermostat object. If the “Guest in room” pocket object is associated with the 1bit “Stby/Comfort” thermostat object, when a guest enters the room goes to “Comfort” mode. If within the same group the “R” read flag is enabled on the pocket object to allow the presence of a guest in the room to be interrogated by the WCS software, when it starts, the software performs interrogation polling on this group and the pocket response with a “0” bit for the “Guest in room” object. If the flag “U” is active in that thermostat object, it takes the pocket response as an update for its operating mode and goes to Stby when
    perhaps it had been set to “Economy” mode or “Protected/ Off” mode for an extended period of non-use of the room.
  33. How can I update the thermostat setpoints and measured temperatures on a supervisor (e.g. Well-contact Suite)?
    To have the new setpoint status once a new setpoint has been set on the supervisor (regardless of the mode currently being used) you must go to the “SETPOINT” and “SENSOR PARAMETERS” parameters of the thermostat and set the values of “Send on Change” and “Cyclic Send Time” as preferred: if the system is very large you should perhaps set the send on difference to 0.3-0.5°C and not set the periodic send every x minutes so as not to overload the Bus with messages.
  34. Is it possible to operate a thermostat in such a way that in the summer it controls a 0-100% proportional valve and in the winter a simple head in On/Off mode?
    Yes, this can be done by means of special programming of the thermostat and relay device that we will now look at in greater detail, providing the On/Off head is not controlled by the relay on the thermostat (which does not have the logic the function described below) but by a relay of other devic as an 01523.1 or a 14457, etc.. YOU have to set the thermostat VALVE parameter to “4 pipe proportional with
    proportional/integral control” mode. This way you have 2 separate “1 byte proportional valve” objects for each season and will use only the one for the summer (whereas for the winter you will not use the corresponding 1 byte object). For winter mode, set the thermostat FAN parameters as “Maximum speed 1”, in other words use the corresponding object of “Speed-1” given that when the winter valve is activated by a thermostat heating request, this object will certainly also be activated. Given that the thermostat season change object goes to “1” in winter status and “0” if you set the summer season, you can then work with a relay, for example, a 01523.1 on which you can activate the parameter “1 OBJECT LOGIC function” (setting it in “AND” mode). You can then create a first group with the “On/Off control” of the relay together with the “Speed 1” object of the thermostat (this serves to control the heating head) and then another group with “object no. 18 summer/winter status” of the associated thermostat together with the object “Logic 1” of relay 01523.1. In functional terms, in winter the “logic 1 of 01523.1” group is activated, so when the other group (i.e. that of the thermostat object + relay On/Off control) also goes to 1, the relay 01523.1 will switch towards the head. In summer the first of the two groups will be constantly at “0”, so the On/Off messages reaching the 2nd group from the thermostat object will not cause the relay to move.
  35. Is it possible to control a fan coil by using any free relays of the various devices without using the 4 I/O device (art. 01522.1) or the relay actuator (art. 01523.1)?
    Yes, it is possible; however, to prevent the user via supervision from mistakenly activating a speed relay while a similar relay is also activated by the thermostat, it is necessary in the ETS project to avoid pairing the force–speed objects nos. 45 – 48.
  36. In a hotel, the thermostats set to OFF/Economy mode suddenly all go into STBY mode; why is that?
    The mode change has been generated by the Well-contact Suite software reopening which on starting up queries all the room pockets to update its supervision on the presence or absence of guests in the rooms; the pockets respond with a bit=0 on the presence, but this is the same group that is also linked to the 1 bit object of the CMF/STBY control of the thermostats and bit=0 on that group entails an interpretation of the thermostat of the type “guest not in room, go onto STBY “. The problem can be solved by disabling the Update flag “U” on the 1 bit object of “comfort/stby” of the thermostat that is active by default; in this way, when the Well-contact Suite software queries the pockets, they respond with a bit=0 on the group but since that flag is OFF, the thermostat will keep its mode without going onto STBY.
  37. If the thermostat is operating in Neutral Zone mode and the guest changes the current setpoint by adjusting the thermostat, what happens? Are the setpoints previously set by ETS or by Well-contact Suite also changed?
  38. No, nothing in particular happens. Acting on the thermostat changes only the Current Setpoint and not the single mode/ season setpoints, the thermostat functions according to the set setpoint and the room temperature so it will activate the heating, cooling or remaining in the neutral zone depending on the heating and air-conditioning setpoints of the current mode.
  39. You cannot change the thermostat mode from the Well-Contact Suite software (neither from supervision nor from the Master-thermostat); What can be done?
    To send mode messages to the thermostats, the Wellcontact Suite software uses communication objects No. 17 for thermostat-A and No. 68 for thermostat-B.
  40. Is it possible to control a fan coil via a relay belonging to different devices and not to a 4-output module?
    Yes, it is possible. The thermostat automatically performs an interlocking function between the relays of the various speeds so it deactivates the relay in use before activating that of the new speed to switch on; to prevent the guest from accidentally activating the 2 relays at the same time causing failure of the Fan coil, in the ETS project it is necessary not to pair the speed-forcing objects to avoid the guest forcing one speed when another one is already in use (it is not possible to interlock relays of different devices).
  41. . Can the various Setpoint communication objects beadded to the same ETS group?
    No, each thermostat communication object must be added to its own dedicated group.
  42. Using the Setpoint Shift object and resetting this setting when you switch the thermostat to ECONOMY or OFF/ PROTECTED mode.
    If with a supervisor device (touch screen, web server, etc.) you change the current setpoint of a thermostat, in which the Reset Setpoint Shift in Economy Mode parameter is set = yes, via the SETPOINT SHIFT object and, at a later time, you bring it into ECONOMY mode, when the thermostat is put back in STBY or CMF mode the value previously set by the supervisor will not be maintained (conversely, if you write the value directly on the SUMM/WINT COMFORT SETPOINT object or on SUMM/WINT STBY SETPOINT there will not be a reset when the mode changes).
  43. Is it possible to have a Boost function to supplement the heating? And will this make it possible to determine the 3 speeds of the fan coil?
    The section of the parameters referred to as “2nd HEATING/ COOLING STAGE” illustrates how the thermostat is able to activate an additional system, which will only be on/off, or a control of a proportional valve 0-100% by means of the objects Nos. 36 and 37 which will appear by activating this Boost function. The thermostat is not able to manage the Boost function by determining the speeds with 3 relays so
    either it will be on/off or proportional 0-100% (whose possible value is either 0% for power-off or 100% for fully open).
    Is it possible to have the thermostat 21814 send a 1-bit ON message when the thermostat turns off all the speeds?
    Yes, and this function is required by some temperature control gateways to manage the Off of the fan coils when the thermostat has switched off the speeds: the communication object is called “OFF – Fan outputs” and the thermostat automatically sends a bit=1 when the fans are turned off and bit=0 when they are turned back on.
  44. If the speeds of the fan coils are forced to OFF, will the thermostat reset to AUTO when it changes mode or simply when Well-contact Suite queries the room pocket to know whether the guest is present in the room?
    When Well-contact Suite queries a pocket it responds with a bit equal to 0/1 on the same control group as the CMF/ STBY mode of the thermostat causing the mode control to be sent again. The thermostat is designed to reset forcing when it receives a mode control so it eliminates the forcing- OFF of the fans; to work around this problem, in the ETS project you can remove the “U” flag of the object of CMF/
    STBY and reprogram t e thermostat so that the response sent from the pocket t  the Well-contact Suite software is ignored.
  45. How does the “Neutral Zone” mode function for a 4-pipe system?
    If the “Enable Summer/Winter” object of thermostat A and/ or thermostat B is not paired with any ETS group, the thermostat in question will function in Neutral Zone mode; in this mode, it will be the thermostat that activates the Air- Conditioning or Heating circuit depending on the room temperature, the Summer and Winter setpoints for the currently selected mode (CMF/STBY/etc.) with a room temperature range, called Neutral Zone, within which neither circuit will be activated. If the end user increases or decreases the setpoint by using the thermostat it will not change the two summer/winter setpoints but will change a setpoint that is halfway between those two values which is the central reference of the neutral zone; raising or lowering this value will also automatically increase or decrease the two setpoints related to summer/winter for the active mode (CMF/STBY) so as to keep the neutral zone unchanged. The thermostat activates the heating or air-conditioning according to the two summer/winter setpoints so, if the room temperature is not in the neutral zone, the thermostat will take as a reference the setpoint that is closest to the current temperature (summer/ winter) resulting in the activation of the heating or air-conditioning circuit.

Viale Vicenza 14 36063 Marostica VI – Italy www.vimar.com

Reference:

Download Manual:

VIMAR 21814 Tactil KNX Thermostat Instruction Manual

VIMAR 21814 Tactil KNX Thermostat Instruction Manual

wpx_thermostats

Recent Posts

Johnson Controls T7000e LCD Digital Thermostat Installation Guide

Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide

1 year ago

Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’S GUIDE

Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE

1 year ago

Hetta HS01RF WIRELESS THERMOSTAT KIT USER MANUAL

Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…

1 year ago

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat USER MANUAL

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…

1 year ago

Honeywell RLV450 PROGRAMMABLE THERMOSTAT USER GUIDE

Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…

1 year ago

Honeywell RLV431 Programmable Thermostat User Guide

Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…

1 year ago