The ZX-RSW-LGE thermostat communicates natively with all LG indoor VRF units, Inverter PTAC and mini-splits thereby enabling the many well-known features of the Verdant system.
The thermostat connects directly to the CN_REMOTE port of the indoor unit. By using the native LG protocol, Verdant’s thermostat is capable of sending vital information to the indoor unit such as guestroom set point and guestroom temperature, allowing the unit to smoothly control the flow of refrigerant, reaching the desired set point with precision.
The thermostat communication with the indoor unit does not interfere with the existing communication bus between outdoor and indoor units. The thermostat communication wiring can be installed once the indoor unit has power without waiting for the completion of the main communication bus.
The CN_REMOTE port on the LG indoor unit is capable of providing the power requirements to the Wireless Receiver. For convenience, the thermostat can be powered using 2 AAA batteries or at 12VDC with a 2-conductor wire from terminals 12 and 13.
An integrated occupancy sensor on the Verdant thermostat allows for energy saving when rooms are unoccupied. Energy saving presets eliminate guesswork and make it easy to adjust the energy saving settings.
A patented “Night Occupancy” feature ensures comfort while occupants are sleeping. Built-in wireless mesh-networking enables optional online management features.
Fully configurable settings allow for customization of energy savings to fit any situation.
Thermostat HVAC Controller Verdant Connector
Case Dimensions (Imperial) | 3.00” x 4.73” x 1.32” | 4.84” x 2.76” x 1.02” | 1.18 x 1.97 x 0.78 |
Case Dimensions (Metric) | 76mm x 120mm x 34mm | 123mm x 70mm x 26mm | 30mm x 50mm x 20mm |
Screen Dimensions (Imperial) | 1.88” x 0.94” | N/A | N/A |
Screen Dimensions (Metric) | 48mm x 24mm | N/A | N/A |
Operating Voltage | 2 “AAA” Cell Batteries | 12VDC | 12VDC |
Control Outputs | 12VDC | 12VDC | |
GND | GND | ||
(B) | (B) | ||
(A) | (A) | ||
Mitsubishi CN_REMO Plug | |||
Occupancy Sensor Beam Width | ±47° (94°) | NA | N/A |
Wireless Frequency | 900MHz | 900MHz | N/A |
Temperature Accuracy | ±1°F | NA | N/A |
FCC ID | XEYZXWU | XEY-ZX-LV | N/A |
IC | 8410A-ZXWU | 8410A-ZXLV | N/A |
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
PURSUANT TO PART 15.21 OF THE FCC RULES, ANY CHANGES OR MODIFICATIONS TO THIS EQUIPMENT NOT EXPRESSLY APPROVED BY VERDANT ENVIRONMENTAL TECHNOLOGIES, INC. MAY VOID VOID THE USER’S AUTHORITY TO OPERATE THE EQUIPMENT.
US PATENTS: 8,369,994; 8,141,791; 7,918,406; 7,841,542; 7,838,803; RE40,437; 7,232,075; 7,185,825; 7,156,318; 7,152,806; 7,145,110; 7,058,477; 7,050,026; 7,028,912; 6,902,117; 6,789,739; 6,786,421; 6,619,555; 6,581,846; 6,578,770; CANADIAN PATENTS: CA2615065; CA2633113; CA2633121; CA2633200; OTHER PATENTS PENDING.
Verdant Energy Management Solutions reserves the right to make changes, without notice, in design or components as progress in engineering and manufacturing methods may warrant. Product appearance may vary.
© Verdant Energy Management Solutions, 2021
Wiring Diagram Verdant LG – HVAC Controller
1 Requires a network access license for each thermostat (Part Number: XMF) and one “Online Connection Kit” (Part Number: OL-KT). Additional fees apply.
030521 Emerson is a trademark of Emerson Electric Co. ©2021 Emerson Climate Technologies, Inc. All rights reserved. Specifications are subject to change without notice.
Download manual:
verdant ZX-RSW-LGE Wireless Energy Management Thermostat Product Specifications Guide
verdant ZX-RSW-LGE Wireless Energy Management Thermostat Product Specifications Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…