The VX3-RSW-MIE thermostat incorporates native connectivity with CITY MULTI® indoor VRF units and M-, P-, and Nv-Series mini splits thereby enabling the many well-known features of the Verdant system. The thermostat connects directly to the CN105 port of the indoor unit. By using the native Mitsubishi Electric protocol, Verdant’s thermostat is capable of sending vital information to the indoor unit such as guestroom set point and actual guestroom temperature, allowing the unit to smoothly control the flow of refrigerant, reaching the desired set point with precision. The thermostat communication with the indoor unit does not interfere with the existing communication bus between outdoor and indoor units. The thermostat communication wiring can be installed once the indoor unit has power without waiting for the completion of the main communication bus. The Mitsubishi Electric CN105 port on the indoor unit is capable of providing the power requirements to the HVAC Controller. For convenience, the thermostat can be powered using 2 AA batteries or at 12VDC with a 2-conductor wire from port J11. An integrated occupancy sensor on the Verdant thermostat allows for energy saving when rooms are unoccupied. Energy-saving presets eliminate guesswork and make it easy to adjust the energy-saving settings. A patented “Night Occupancy” feature ensures comfort while occupants are sleeping. Built-in wireless mesh networking enables optional online management features. Fully configurable settings allow for the customization of energy savings to fit any situation
Case Dimensions (Imperial) | 4.02 x 5.51” x 0.93” | 3.88” x 2.13” x 0.75” | 1.18 x 1.97 x 0.78 |
Case Dimensions (Metric) | 102mm x 140mm x 23.5mm | 98mm x 54mm x 19mm | 30mm x 50mm x 20mm |
Screen Dimensions (Imperial) | 3.63” x 2.13” | N/A | N/A |
Screen Dimensions (Metric) | 92mm x 54mm | N/A | N/A |
Operating Voltage | 2 “AA” Cell Batteries/12VDC | 12VDC | 12VDC | 5VDC |
Communication Interface | 12VDC | 12VDC | |
RX | RX | ||
TX | TX | ||
GND | GND | ||
5VDC | |||
Mitsubishi CN105 Female Plug | |||
Occupancy Sensor Beam Width (Angular degrees) | ±47° (94°) | N/A | N/A |
Wireless Frequency | 902-928MHz | 902-928MHz | N/A |
Temperature Accuracy (Fahrenheit) | ±1°F | N/A | N/A |
FCC ID | XEYWX-DB | XEY-ZX-LV | N/A |
IC | 8410A-WXDB | 8410A-ZXLV | N/A |
CITY MULTI® | M-Series | Nv-Series | P-Series | |
Ceiling Cassette | PLFY-NBMU-E2 PLFY-NEMU PLFY-NFMU TPLFYP EM140A TPLFYP EM141A TPLFYP FM140A TPMFY BM140F |
MLZ-KP SLZ-KA SLZ-KF |
NTXCKS NTXUKS | PKA-KA4.TH PKA-KA6 PKA-KA7 PLA-BA4 PLA-BA6 PLA-EA |
Ceiling Suspended | TPCFYP KM140B | PCA-KA4 PCA-KA4TH PCA-KA6 PCA-KA7 | ||
Ducted | PEFY-NMAU-E3 PEFY-NMHSU PEFY-NMSU-E3 TPEFYP MA143A TPEFYP MH140A TPEFYP MH142A TPEFYP MS140C |
SEZ-KD4.1TH SEZ-KD4R1TH | PEA-AA4 PEA-AA4R1.TH PEA-AA6 PEAD-AA4 PEAD-AA5 PEAD-AA7 TPEAD-AA | |
Floor Mounted | TPFFYP CS140A TPFFYP RE140A | MFZ-KA MFZ-KJ | NTXFKS | |
Horizontal Ducted | NTXDKS | |||
Multiposition | PVFY-NAMU PVFY-E00A PVFY-E00B TPVFYP AM141A | MVZ-AA4 MVZ-AA7 SVZ-KP | NTXAMT | PVA-AA4 PVA-AA7 |
Wall-Mounted |
TPKFYP BM142B TPKFYP HM142A TPKFYP KM142A | MSY-GE-NA-8 MSY-GL MSY-NA-8 MSZD-NA-8 MSZ-EF MSZ-FE-09-NA-8 MSZ-FE-12-NA-8 MSZ-FE-18-NA MSZ-FH MSZ-GE-24NA MSZ-GE-NA9 MSZ-GL MSZ-HM MSZ-JP MSZ-WR |
MSZEF NTXWEL NTXWMT**A111 NTXWMT**A112 NTXWPH NTXWST NTYWST |
PKA-HA4 PKA-HA6 PKA-HA7 |
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS:
PURSUANT TO PART 15.21 OF THE FCC RULES, ANY CHANGES OR MODIFICATIONS TO THIS EQUIPMENT NOT EXPRESSLY APPROVED BY VERDANT ENVIRONMENTAL TECHNOLOGIES, INC. MAY VOID VOID THE USER’S AUTHORITY TO OPERATE THE EQUIPMENT.
DOWNLOAD MANUAL
Verdant VX3-RSW-MIE-W Wireless Energy Thermostat Product Specifications Guide
Verdant VX3-RSW-MIE-W Wireless Energy Thermostat Product Specifications Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…