The Verdant VX Series Hilton Connected Room Thermostat allows guests to control temperature directly from the Hilton Honors app. An Integrated occupancy sensor allows for optional energy saving when rooms are unoccupied. A patented “Night Occupancy” feature ensures comfort while guests are sleeping. Fully confi gurable settings allow for customization of energy savings to fi t any situation.
Wiring Table – 24V AC
Wire Color | Terminal Letter | Terminal Connection |
BLACK | C | COMMON |
RED | R | 24V |
YELLOW | Y | COMPRESSOR |
WHITE | W | HEAT |
ORANGE | O OR B | REVERSE VALVE |
GREEN | GH | FAN HIGH |
PURPLE | GL | FAN LOW |
BROWN | AUX | OCCUPANCY OUT |
Wiring Table – 24V DC
Wire Color | Terminal Letter | Terminal Connection |
BLACK | R | 24V |
RED | C | COMMON |
YELLOW | Y | COMPRESSOR |
WHITE | W | HEAT |
ORANGE | O OR B | REVERSE VALVE |
GREEN | GH | FAN HIGH |
PURPLE | GL | FAN LOW |
BROWN | AUX | OCCUPANCY OUT |
Wiring Table – 24V AC
Wire Color | Terminal Letter | Terminal Connection |
BLACK | C | COMMON |
RED | R | 24V |
Wiring Table – 24V DC
Wire Color | Terminal Letter | Terminal Connection |
BLACK | R | 24V |
RED | C | COMMON |
Case Dimensions (Imperial) | 4.02 x 5.51” x 0.93” | 3.875” x 2.125” x 0.75” |
Case Dimensions (Metric) | 102mm x 140mm x 23.5mm | 98mm x 54mm x 19mm |
Screen Dimensions (Imperial) | 3.63” x 2.13” | N/A |
Screen Dimensions (Metric) | 92mm x 54mm | N/A |
Operating Voltage | 3V DC – 2 “AA” Cell Batteries | 24V AC/DC (HVAC Unit) |
Control Outputs | Fan High (GH) | |
Fan Low (GL) | ||
Compressor (Y) | ||
Heat Pump (OB) | ||
Heat (W) | ||
Occupancy Out (Aux) | ||
Occupancy Sensor Beam Width | ±47° (94°) | N/A |
Wireless Frequency | 902-928MHz | 902-928MHz |
Temperature Accuracy | ±1°F | N/A |
FCC ID | XEYWX | XEYV8ACCC |
IC | 8410A-WX | 8410A-V8ACCC |
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS:
PURSUANT TO PART 15.21 OF THE FCC RULES, ANY CHANGES OR MODIFICATIONS TO THIS EQUIPMENT NOT EXPRESSLY APPROVED BY VERDANT ENVIRONMENTAL TECHNOLOGIES, INC. MAY VOID VOID THE USER’S AUTHORITY TO OPERATE THE EQUIPMENT..
Verdant Environmental Technologies, Inc.
DOWNLOAD MANUAL
Verdant VX-TW-HCR-B Wireless Room Thermostat Product Specifications Guide
Verdant VX-TW-HCR-B Wireless Room Thermostat Product Specifications Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…