Verdant VX Series Thermostat delivers unprecedented energy savings without compromising guest comfort. Integrated occupancy sensor allows saving energy when rooms are unoccupied. Energy saving presets eliminate the guesswork and make it easy to adjust the energy saving settings. Patented “Night Occupancy” feature ensures comfort while guests are sleeping.
Built-in wireless mesh-networking enables optional remote management features. Fully configurable settings allow customizing the energy savings to fit any situation.
Wiring Table – 24V AC
Wire Color | Terminal Letter | Terminal Connection |
BLACK | C | COMMON |
RED | R | 24V |
YELLOW | Y | COMPRESSOR |
WHITE | W | HEAT |
ORANGE | O or B | REVERSE VALVE |
GREEN | GH | FAN HIGH |
PURPLE | GL | FAN LOW |
Wiring Table – 24V DC
Wire Color | Terminal Letter | Terminal Connection |
BLACK | R | 24V |
RED | C | COMMON |
YELLOW | Y | COMPRESSOR |
WHITE | W | HEAT |
ORANGE | O or B | REVERSE VALVE |
GREEN | GH | FAN HIGH |
PURPLE | GL | FAN LOW |
Thermostat
Case Dimensions (Imperial) | 5.125 x 4.6875” x 1.25” |
Case Dimensions (Metric) | 130mm x 119mm x 32mm |
Screen Dimensions (Imperial) | 3.4375″ x 1.5″ |
Screen Dimensions (Metric) | 87mm x 38mm |
Operating Voltage | 24V AC/DC |
Control Outputs | Fan High (GH) |
Fan Low (GL) | |
Compressor (Y) | |
Heat Pump (OB) | |
Heat (W) | |
Occupancy Sensor Beam Width | ±47° (94°) |
Wireless Frequency | 900MHz |
Temperature Accuracy | ±1°F |
FCC ID | XEYVX |
IC | 8410A-VX |
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
PURSUANT TO PART 15.21 OF THE FCC RULES, ANY CHANGES OR MODIFICATIONS TO THIS EQUIPMENT NOT EXPRESSLY APPROVED BY VERDANT ENVIRONMENTAL TECHNOLOGIES, INC. MAY VOID VOID THE USER’S AUTHORITY TO OPERATE THE EQUIPMENT.
US PATENTS: 8,369,994; 8,141,791; 7,918,406; 7,841,542; 7,838,803; RE40,437; 7,232,075; 7,185,825; 7,156,318; 7,152,806; 7,145,110; 7,058,477; 7,050,026; 7,028,912; 6,902,117; 6,789,739; 6,786,421; 6,619,555; 6,581,846; 6,578,770; CANADIAN PATENTS: CA2615065; CA2633113; CA2633121; CA2633200; OTHER PATENTS PENDING.
Verdant Environmental Technologies, Inc. reserves the right to make changes, without notice, in design or components as progress in engineering and manufacturing methods may warrant. Product appearance may vary.
© Verdant Environmental Technologies, Inc. 2014
Verdant Environmental Technologies, Inc. • 5667 Royalmount Avenue, Montreal, QC, Canada, H4P 2P9 • TEL: 514.344.4448 • FAX: 514.344.5977 • EMAIL: sales@verdant.info
* Requires an optional “Online Connection Kit” (Part Number: V8-OL-KT) and a service subscription. Additional fees apply.
Download manual:
Verdant VX-TR-KT Wired Energy Management Thermostat Product Specifications Guide
Verdant VX-TR-KT Wired Energy Management Thermostat Product Specifications Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…