If a Warmer or Cooler button is pressed during an active ADR event, then the user is presented with this opt-out screen.
If a pricing triggered ADR event is enabled, there will be a green leaf on the top bar along with the actual cost of energy. This will be accompanied by associated text as shown below
The Deadband is the number of degrees or minutes that the thermostat waits before it initiates the stages of heating or cooling. 1st Stage Deadband Specifies the minimum temperature difference between the room temperature and the desired setpoint before the first stage of heating or cooling is allowed to turn on. For example, if the heat setpoint is 68° and the 1st Stage deadband is set to 2 degrees, the room temperature will need to drop to 66 degrees before the heat turns on.
Number of degrees past 1st stage before 2nd stage turns on. (0 – 10 deg. F)
Number of minutes past 1st stage before 2nd stage turns on. (0 – 60 mins.) The 3rd and 4th stage deadband settings have the same adjustable steps as 2nd stage headband. Timers & Deadbands Installation Settings (Continued) (The 2nd stage deadband must also be met)
Deadband or Setpoint.
Free Cooling requires additional dampers and duct work to be installed. Additionally, the thermostat is wired in a different manner for this feature to function properly. Before enabling this feature, please make sure these steps are completed
Turns on Free Cooling
Free Cooling shuts off above this outdoor temperature. (40 – 80 degrees
If you don’t have a compressor, set Mechanical Cooling to “NO”, Y1 will then be used to control the Free Cooling Damper(s) and Y2 will be disabled. If set to “YES”, mechanical (compressor) cooling will be controlled by the Y2 terminal. (See page 67 for wiring diagram Mechanical air conditioning is turned on with a 2nd stage demand for cooling and the Free Cooling, outdoor air damper is closed.
Turns on Heat Pump Lockout
Heat Pump will not run below this temp. (20 – 75 deg. F)
Turns on Aux Heat Lockout.
Aux Heat will not run above this temp. (0 – 75 deg. F) GAS/EL or HP dip switch must be set for HP and GAS or ELEC dip switch must be set for ELEC
This feature is for heat pump applications only. This will only appear if the GAS/EL or HP dip switch is set for HP and the GAS or ELEC dip switch is set for Gas. When Dual Fuel is ON, an outdoor temperature or, if Change With Outdoor is set to OFF a demand for third stage heat will be used to stop running the heat pump and switch to a fossil fuel source of heat. NOTE: Once the change to fossil fuel is made, the heat demand must finish with fossil fuel. Additional heat demands within 10 minutes will also use fossil fuel, regardless of outdoor temperature or stage demand.
Allows the W3/AUX output to be used for Heating, Humidification, or Dehumidification.
IMPORTANT: Aux Output Usage must be set for Hum or Dehum before any settings will take effect in the Humidity Main Menu
The AUX Output polarity may be set for Normally Open or Normally Closed to accommodate different types of humidification and dehumidification equipment.
Runs the fan for a short time after Cooling or electric strip heat turns off to increase system efficiency. (0 – 120 Secs.)
When a remote sensor is connected to the thermostat, the user may choose which sensor source is used to measure room temperature.
The wired sensor may be used as follows:
The thermostat and wired sensor may be calibrated -7 to +7 degrees F. The integral humidity sensor may be calibrated -20% to +20% RH
The installer or service technician can use this feature to test the functions without any time delays of the thermostat
A Dealer may enter their company contact information for the customer to use when they need service. This will appear when the “Who To Call For Service” button is pressed in the Information Menu.
Use the keyboard to enter your information
Press to upgrade the thermostat firmware. The SD Card must be in the thermostat SD Card reader and contain the valid firmware. If an error message appears, confirm with ColorTouch Assistant that firmware is up to date or simply try reinserting the SD card. If you are connected to Skyport Wi-Fi and you receive an Alert that new firmware is available, simply press the Upgrade Firmware button to upgrade wirelessly. Note: Occasionally an update that requires a large amount of data is not possible to do wirelessly. In this case an update using an SD card will be required
Press to delete the custom photos you uploaded to the thermostat
If needed, the clock may be calibrated up to -10 to +10 minutes per month
Press to reset the thermostat back to the factory settings
If needed, press here to restart the thermostat.
It is here that you will find helpful information regarding the connectivity status of your thermostat, including the thermostat’s ID.
Choose your network from the list and enter the network password. If your network does not appear in the list, hit the refresh button.
Turning on the local API allows 3rd party software to interface with your thermostat, such as a home automation system
This is the default with the local API OFF.
To turn on the HTTP Local API select Local API
Press BACK to return to previous screen.
If a Secure API is preferred, then select API Protocol
Upon pressing API Protocol, the following screen will appear
Then select HTTPS and press BACK
Upon pressing BACK, the screen will look like this
Select Basic Auth User, and enter the appropriate information on the screen below and press DONE to save.
Select Basic Auth Password as the next step
Select Basic Auth Password and enter the appropriate information on the screen below and press DONE to save.
The last step is to turn the Local API as shown below.
Pressing this button will let you know if you are paired with a Skyport account. If not, then you may follow prompt and instructions to create an account and add the thermostat to the account
To initiate the Emergency Heat feature, Press the Emergency Heat button. During Emergency Heat operation the thermostat will turn on the fan and auxiliary stages of heat when there is a demand for heat. The 1st stage of heating and all stages of cooling will be unavailable. To exit Emergency Heat, press the Emergency Heat button
ColorTouch Assistant may be downloaded at no charge at: www.venstar.com/thermostats/colortouch/assistant
The ColorTouch Assistant allows you to use your computer to:
Uploading Photos and Settings to your thermostat
Import Settings from SD Card When you are finished adding and editing photos and settings, click on Save to SD. When prompted, remove the SD card from the SD card reader on your computer.
Insert the SD card into the SD Card Slot
Press
Your thermostat will automatically save your new photos and settings in it’s internal memory. When finished, you may remove the SD card. It is not needed for normal thermostat operation
Remove and Replace the old thermostat
To install the thermostat properly, please follow these step by step instructions. If you are unsure about any of these steps, call a qualified technician for assistance
Wire Connections
If the terminal designations on your old thermostat do not match those on the new thermostat, refer to the chart below or the wiring diagrams that follow.
Before you go any further, determine what your existing wiring and equipment situation is
NOTE: The backplate does not fully cover a full size vertical junction box. The ACC-WPLWH Venstar Wallplate or a single-gang, horizontally mounted junction box would be needed for that type of installation
To remove the thermostat backplate:
Using the Finger Pull Areas, pull the front housing away from the backplate
Dip switches are located on the back of the thermostat
This dip switch configures the thermostat to control a conventional gas/electric system or a heat pump. If your system is anything other than a heat pump, leave this switch set for GAS/EL.* *For some commercial heat pumps, this switch may need to be set for GAS/EL. Consult the commercial heat pump literature.
When the GAS/EL or HP dip switch is configured for HP, this dip switch (O or B) must be set to control the appropriate reversing valve. If O is chosen, the W1/O/B terminal will energize in cooling. If B is chosen, the W1/O/B terminal will energize in heating
When GAS/EL or HP is set for GAS/EL:
This switch (GAS or ELEC) controls how the thermostat will control the Fan (G) terminal in heating mode. When GAS is chosen, the thermostat will not energize the Fan (G) terminal in heating. When ELEC is chosen the thermostat will energize the fan in heating.
When GAS/EL or HP is set for HP:
This switch (GAS or ELEC) defines the Aux Heat type. When GAS is chosen, the auxiliary heat will not be allowed to run during heat pump operation. When using a Dual Fuel system, set this switch for GAS. When ELEC is chosen, up to two stages of auxiliary strip heat will be allowed to run
Conventional Heating and Cooling Systems
Heat Pump Systems
Heat Pump Systems with Dual Fuel
Free Cooling utilizes the Y1 terminal for the operation of 1st stage cooling. If mechanical (compressor) cooling is also present, the mechanical cooling is connected to the Y2 terminal in this instance. Free Cooling may be used with a Gas/Electric or Heat Pump system. Temperature Sensor: ACC-TSEN Temperature Sensor 10K ohm sensor at 77F/25C. Negative Temperature Coefficient.
One-Year Warranty – This Product is warranted to be free from defects in material and workmanship. If it appears within one year from the date of original installation, whether or not actual use begins on that date, that the product does not meet this warranty, a new or remanufactured part, at the manufacturer’s sole option to replace any defective part, will be provided without charge for the part itself provided the defective part is returned to the distributor through a qualified servicing dealer. THIS WARRANTY DOES NOT INCLUDE LABOR OR OTHER COSTS incurred for diagnosing, repairing, removing, installing, shipping, servicing, or handling of either defective parts or replacement parts. Such costs may be covered by a separate warranty provided by the installer. THIS WARRANTY APPLIES ONLY TO PRODUCTS IN THEIR ORIGINAL INSTALLATION LOCATION AND BECOMES VOID UPON REINSTALLATION. LIMITATIONS OF WARRANTIES – ALL IMPLIED WARRANTIES (INCLUDING IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE AND MERCHANTABILITY) ARE HEREBY LIMITED IN DURATION TO THE PERIOD FOR WHICH THE LIMITED WARRANTY IS GIVEN. SOME STATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS, SO THE ABOVE MAY NOT APPLY TO YOU. THE EXPRESSED WARRANTIES MADE IN THIS WARRANTY ARE EXCLUSIVE AND MAY NOT BE ALTERED, ENLARGED, OR CHANGED BY ANY DISTRIBUTOR, DEALER, OR OTHER PERSON WHATSOEVER. ALL WORK UNDER THE TERMS OF THIS WARRANTY SHALL BE PERFORMED DURING NORMAL WORKING HOURS. ALL REPLACEMENT PARTS, WHETHER NEW OR REMANUFACTURED, ASSUME AS THEIR WARRANTY PERIOD ONLY THE REMAINING TIME PERIOD OF THIS WARRANTY.
THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR:
DOWNLOAD MANUAL
VENSTAR SKYPORT15 Thermostat Instruction Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…