Legal information
Publisher/manufacturer Vaillant GmbH
Berghauser Str. 40 D-42859 Remscheid
Telefon +49 21 91 18‑0 Telefax +49 21 91 18‑28 10
info@vaillant.de www.vaillant.de
© Vaillant GmbH 2012
These instructions, or extracts thereof, may only be printed with the written consent of Vaillant GmbH. All designations of products in these instructions are brand names/trademarks of the companies in question.
We reserve the right to make technical changes.
Symbols and signs used
Symbols
The following symbols may appear:
Observing other applicable documents
Document storage
Document handover
Availability of documents
The system operator is responsible for storing the documents so that they are available when required.
Applicability of the instructions
These instructions apply for the following only:
Article number
Required personnel qualifications
This manual is intended for persons with the following qualifications.
Authorized competent person
The installation, assembly and removal, start-up, maintenance, repair, and decommissioning of Vaillant products and accessories must only be carried out by authorized competent persons.
Note
Each competent person is qualified for specific activities on the basis of their training. They must only work on units if they have the required qualification. When working on the units, competent persons must
observe all applicable directives, standards, laws, and other regulations.
General safety information
Installation by skilled tradesmen only
The unit must be installed by a qualified, skilled tradesman, who is responsible for compliance with the applicable requirements, regulations, and directives.
Risk of death from live connections
When working in the electronics box of the boiler, there is a risk of death from electric shock. Continuous voltage is present on the main connection terminals, even if the main switch is turned off.
Material damage due to unsuitable installation room
If you are installing the controller in a moist environment, the electronics may be damaged by moisture.
Danger due to error functions
CE label
CE labeling shows that, based on the type overview, the appliances comply with the basic requirements of the following directives:
Intended use
State-of-the-art
A controller is a state-of-the-art unit manufactured in accordance with recognized safety regulations. Even so, in the event of inappropriate or non-intended use, damage to the appliance and other property may arise. The controller controls a heating installation with a Vaillant heater with an eBUS interface in a way that is room-controlled and time-dependent. The controller can control the hot water generation of a connected domestic hot water cylinder. Operation is permissible with the following components and accessories:
Improper use
Any other use, or use beyond that specified, shall be considered improper use. Any direct commercial or industrial use is also deemed to be improper. The manufacturer/supplier is not liable for any resulting damage. The user alone bears the risk. Improper use of any kind is prohibited.
Other applicable documents
Intended use includes the following
Overview of the equipment
Identification plate
The identification plate is located on the rear of the controller’s electronics module (PCB) and is no longer accessible from the outside after it has been installed on a wall in the living area. The identification plate contains the following information
Information on the identification plate | Meaning |
Serial number | For identification |
VRT XXX | Unit designation |
V | Operating voltage |
mA | Current consumption |
CE label | Unit complies with European standards and directives |
Waste container | Proper disposal of the unit |
Scope of delivery
Quant- ity | Component |
1 | Controller |
1 | Fastening material (2 bolts and 2 wall plugs) |
1 | Operating instructions |
Quant- ity | Component |
1 | Installation instructions |
Electrical installation
When connecting the eBUS line, there is no need to pay at-tention to the polarity. If the two connections are switched around, communication is not affected. If you want to use a VR 66, observe the installation instruc-tions for the VR 66 Control Centre.
Connect the controller to the boiler with a “3-4-5 Terminal”
Connect the controller to the boiler with a “24V=RT terminal”
Electrical installation
When connecting the eBUS line, there is no need to pay at-tention to the polarity. If the two connections are switched around, communication is not affected.
Connect the controller to the boiler with a “3-4-5 Terminal”
Connect the controller to the boiler with a “24V=RT terminal”
When you start the controller for the first time after electrical installation or after replacement, the installation assistant starts automatically. You can use the installation assistant to make the main settings for the heating installation.
Note
To be able to use the controller to set the temperature for the hot water generation and heating circuit, you must set the maximum value for the temperatures on the boiler. To do this, turn the boiler’s rotary knobs as far as they go in a clockwise direction. You can use the installation assistant to make the main settings for the heating installation. The operating concept, an operation example, and the menu structure are all contained in the operating instructions of the controller. All settings that you have made using the installation assist-ant can be changed again at a later time via the access level for the system operator Installer level. The read-out and settings options for the installer level are described in the Access level for the competent person (→ Page 17).
Overview of installation assistant set-up options
Setting | Values | Increment/Select | Factory preset | Setting | |
Min. | Max. | ||||
Language | Languages for selection | English | |||
2) Zone | None, 1, 2 | 0 | |||
3) Control strategy | Two point, analogue | Two point | |||
1) Route adjustment | -5 | +5 | 1 | 0 | |
3) Cylinder | Active, Inactive | Active | |||
1) Appears only if the value Analogue is set for the control strategy. 2) Appears only if a VR 66 is connected. 3) Appears only in the display of the main controller with Zone 1 selected. |
The controller has two operating levels, the access level for the operator and the access level for the competent person. The setting and read-out options for the operator, the oper-ating concept, and an operating example are described in the operating instructions for the controller.
Installer level overview
You can use the left-hand selection button Menu and the list entry Installer level to access the setting and read-out options. Installer level (→ Page 17)
Setting level | Values | Unit | Increment/Select | Factory reset | Setting | |
min. | max. | |||||
Installer level → | ||||||
Enter code | 000 | 999 | 1 | 000 | ||
Installer level → Service information → Enter contact details → | ||||||
Installer | 1 | 11 | Figures | A to Z, 0 to 9, Space | ||
Phone | 1 | 12 | Numbers | 0 to 9, Space, Hyphen | ||
Installer level → Service information → Service date → | ||||||
Next service on | Date | |||||
* If there is no fault, the status is OK. If there is a fault, Fault appears here and you can read the fault message in the Fault messages section. 1) Appears only if the value Analogue is set for the control type. If the VR 66 is connected, the functions shown in italics are only available for Zone 1 and these are only shown in the display for the main controller. |
Setting level | Values | Unit | Increment/Select | Factory reset | Setting | |
min. | max. | |||||
Installer level → System configuration → | ||||||
System | ||||||
Status | Current value* | |||||
Water pressure | Current value | bar | ||||
Hot water | Current value | ℃ | ||||
Controller modules | List | Software version | ||||
Heat generator | ||||||
Status | Current value | Off, Heating, DHW | ||||
VF1 | Current value | |||||
HEATING 1 | ||||||
Auto day temp until | Current value | hr:min | ||||
Day temperature | 5 | 30 | ℃ | 0.5 | 20 | |
Set-back temperature | 5 | 30 | ℃ | 0.5 | 15 | |
Flow temp. target. | Current value | ℃ | ||||
Flow temp. current | Current value | ℃ | ||||
* If there is no fault, the status is OK. If there is a fault, Fault appears here and you can read the fault message in the Fault messages section. 1) Appears only if the value Analogue is set for the control type. If the VR 66 is connected, the functions shown in italics are only available for Zone 1 and these are only shown in the display for the main controller. |
Setting level | Values | Unit | Increment/Select | Factory reset | Setting | |
min. | max. | |||||
Special function | Current function | Cylinder boost, Party function, Away | None | |||
Hot water circuit | ||||||
Cylinder | Inactive | Active | Active, Inactive | Active | ||
Target cylinder temperature | 35 | 70 | ℃ | 1 | 60 | |
Current cylinder temperature | Current value | ℃ | ||||
System | ||||||
Control type | Current value | 2-point, analogue | 2-point | |||
1) Distance Adjustment | -5 | +5 | 1 | 0 | ||
Installer level → Change code → | ||||||
New code | 000 | 999 | 1 | 000 | ||
* If there is no fault, the status is OK. If there is a fault, Fault appears here and you can read the fault message in the Fault messages section. 1) Appears only if the value Analogue is set for the control type. If the VR 66 is connected, the functions shown in italics are only available for Zone 1 and these are only shown in the display for the main controller. |
If there is no fault, the status is OK. If there is a fault, the Fault appears here and you can read the fault message in the Fault Messages section. Appears only if the value Analogue is set for the control type. If the VR 66 is connected, the functions shown in italics are only available for Zone 1 and these are only shown in the display for the main controller.
If there is no fault, the status is OK. If there is a fault, the Fault appears here and you can read the fault message in the Fault Messages section. Appears only if the value Analogue is set for the control type.
If the VR 66 is connected, the functions shown in italics are only available for Zone 1 and these are only shown in the display for the main controller.
If there is no fault, the status is OK. If there is a fault, the Fault appears here and you can read the fault message in the Fault Messages section. Appears only if the value Analogue is set for the control type. If the VR 66 is connected, the functions shown in italics are only available for Zone 1 and these are only shown in the display for the main controller.
The path details given at the start of each function description indicate how you reach this function in the menu structure. The square brackets contain the level of detail to which the function belongs. You can use the left-hand selection button Menu and the list entry Installer level to set the operating and display functions.
The table “Overview of operating levels” shows you which functions are available for Zone 2 via the auxiliary controller.
Service Information
Entering contact details
Menu →Installer level → Service information → Enter contact data
Entering the service date
Menu → Installer level → Service information → Service date
Note
To find out which service date to enter, refer to the instructions for your heater unit.
System configuration, system
Display | Meaning | Connected units | Cause |
Fault, Heater 1 | Fault in Heater 1 | Heat generator 1 | See heater instructions |
Heater 1 connection is missing | Connection fault, Heater 1 | Heat generator 1 | Cable defective, plug connection not correct |
Reading the system status
Menu → Installer level → System configuration [System —-] → Status
Reading the water pressure of the heating system
Menu → Installer level → System configuration [System — -] → Water pressure
This function allows you to read the water pressure of the heating system.
Reading the hot water generation status
Menu → Installer level → System configuration [System — -] → Domestic hot water You can use this function to read the hot water generation status (Charged, Not charged).
Reading the software version
Menu → Installer level → System configuration [System — -] → Control modules You can use this function to read the software version of the display and the heater.
Setting the control Type
Menu → Installer level → System configuration [System — -] → Control type Select this function to set the type of room temperature control:
Setting the distance adjustment
Menu → Installer level → System configuration [System — -] → Distance adjustment
This function allows you to optimally adjust the switching behavior of the controller to the room size or the radiator layout:
System configuration, heater
Reading the status of the heater
Menu → Installer level → System configuration [Heater 1 — –] → Status
This function allows you to read the current status of the heater (boiler). Off, Heating (heating mode), hot water generation.
Reading the value of the temperature sensor VF1
Menu → Installer level → System configuration [Heater 1 — –] → VF1This function allows you to read the current value of the temperature sensor VF1.
System configuration, heating circuit
Reading the end of the current time period
Menu → Installer level → System configuration [HEATING 1 —-] → Auto day temp until
With this function, you can stipulate whether or not a set time period is active for the Automatic mode and how much of the period is still remaining. To do this, the controller must be in “Automatic mode”. The information is specified in hr: min.
Setting the day temperature
Menu → Installer level → System configuration [HEATING 1 —-] → Day temperature This function allows you to set the desired day temperature for the heating circuit.
Setting the set-back temperature
Menu → Installer level → System configuration [HEATING 1 —-] → Set-back temperature This function allows you to set the desired setback temperature for the heating circuit. The setback temperature is the temperature to which the heating is to be reduced at times of low heat demand (e.g. overnight).
Reading the target flow temperature
Menu → Installer level → System configuration [HEATING 1 —-] → Flow temp. target
You use this function to read the target flow temperature for the heating circuit.
Reading the current flow temperature
Menu → Installer level → System configuration [HEATING 1 —-] → Flow temp. current
You use this function to read the current flow temperature for the heating circuit.
Reading the Status of advanced functions
Menu → Installer level → System configuration [HEATING 1 —-] → Advanced functions With this function, you can define whether a special operating
mode (advanced function), such as the Party function, etc. is currently active for a heating circuit.
System configuration, hot water circuit
Activating the cylinder
Menu → Installer level → System configuration [Domestic hot water —-] → Cylinder
Select this function to specify whether a cylinder is connected: Active: Cylinder connected
Setting the target temperature for domestic hot water cylinder (desired hot water temperature)
Menu → Installer level → System configuration [Domestic hot water —-] → Cylinder temp. target
This function allows you to define the set target temperature for a connected domestic hot water cylinder (desired hot water temperature). Set the set target temperature on the controller in such a way that the heat demand of the operator is covered. The temperature for the domestic hot water cylinder must be set to the maximum value in the boiler.
Reading the current temperature of the domestic hot water cylinder
Menu → Installer level → System configuration [Domestic hot water —-] → Cyl. temp. current
You can use this function to read the measured cylinder temperature.
Changing the code for the Installer level
Menu → Installer level → Change code
This function allows you to change the access code for the “Installer level” operating level. If the code is no longer available, you must reset the controller to the factory setting in order to obtain access to Installer
level again.
Rectifying faults
Installation instructions VRT 350 0020131957_01
Rectifying faults
Error messages
If a fault occurs in the heating system, an error message will appear in the controller display instead of the basic display. You can access the basic display again by pressing the function key “Back”. You can also read all current error messages under the following menu point: Menu → Information → System status → Status [Fault] If there is a fault, the status “Fault” is displayed. In this case, the right-hand selector button has the function Display. Press the right-hand selector button to display a list of fault messages.
Note
Not all error messages in the list appear automatically on the display.
Display | Meaning | Connected units | Cause |
Fault, Heater 1 | Fault in Heater 1 | Heat generator 1 | See heater instructions |
Heater 1 connection is missing | Connection fault, Heater 1 | Heat generator 1 | Cable defective, plug connection not correct |
Faults
Fault | Cause | Remedy |
Display is dark | Unit fault | – The power is switched off/on at the heater – Check the power supply for the heater |
No changes in the display via the rotary knob | Unit fault | – The power is switched off/on at the heater |
Fault | Cause | Remedy |
No changes in the display via the selector buttons | Unit fault | – The power is switched off/on at the heater |
Replacing the controller
Removing from the wall
Recycling and disposal
The controller and the associated transport packaging consist largely of recyclable materials.
Unit
If your Vaillant unit is identified with this symbol, it does not belong with your household waste at the end of its useful life. In this case, make sure that the Vaillant unit and any accessories are properly disposed of at the end of their useful life. As this Vaillant unit is covered by the law regarding marketing, return, and environmentally friendly disposal of electrical and electronic equipment (ElektroG in Germany), the
the unit can be disposed of free of charge at a municipal collection point.
Packaging
The approved qualified servicing company that installed the unit will dispose of the transport packaging.
Customer service
To ensure regular servicing, it is strongly recommended that arrangements are made for a Maintenance Agreement. Please contact Vaillant Service Solutions for further details: 0330 100 3461
Vaillant Ltd
Nottingham Road Belper Derbyshire DE56 1JT
Telephone 0330 100 3461 Vaillant Service Solutions 0330 100 3461
Spares Technical Enquiries 017 73 59 66 15
info@vaillant.co.uk technicalspares@groupservice.co.uk
www.vaillant.co.uk
DOWNLOAD MANUALS:
Vaillant VRT 350 ELECTRICAL Thermostat Installation Instructions
Vaillant VRT 350 ELECTRICAL Thermostat Installation Instructions
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…