Action-related warnings
Classification of action-related warnings The action-related warnings are classified in accordance with the severity of the possible danger using the following warning signs and signal words: Warning symbols and signal words
Imminent danger to life or risk of severe personal injury
Danger!
Risk of death from electric shock
Warning
Risk of minor personal injury
Caution
Risk of material or environmental damage
In the event of inappropriate or improper use, damage to the product and other property may arise. The product is intended for using an eBUS interface to control a heating installation with heat generators from the same manufacturer. The radio control, the radio receiver unit, and the wireless outdoor temperature sensor must be installed in a location that receives a sufficiently high signal. The radio control is not intended to be portable.
Intended use includes the following:
General safety information
The danger caused by improper operation
Improper operation may present a danger to you and others, and cause material damage.
Risk of injury caused by batteries
If the batteries are recharged contrary to instructions, there is a risk of serious personal injury. Do not recharge the batteries.
Risk of material damage
Do not short-circuit the connection contacts in the product’s battery compartment.
Risk of material damage caused by acid
Risk of material damage caused by frost
Safety
Operating instructions 0020237621_02 If you cannot ensure the operation, have a competent person drain the heating installation
Notes on the documentation
Observing other applicable documents
You must observe all operating instructions enclosed with the system components.
Storing documents
Keep this manual and all other applicable documents safe for future use.
Validity of the instructions
These instructions apply only to: VRC 700f/4 – article number Great Britain 0020231564
Nomenclature
The following terms are used for simplification:
Function availability
The functions described in these operating instructions are not available for all system configurations. The system control only shows the functions that are available in the system configuration, you have installed
Design of the product
Radio receiver unit
Radio outside temperature sensor
Main function
The system control is a weather-compensated system control with an outdoor temperature sensor installed in the open air. The system control is connected to the outdoor temperature sensor and the heat generator via the radio receiver unit. The system control radio-controls the heating installation and other connected components, e.g. the domestic hot water generation for a connected domestic hot water cylinder or the ventilation of a connected ventilation unit.
Heating
The outdoor temperature sensor measures the outdoor temperature and forwards the values to the system control. When the outdoor temperature is low, the system control increases the flow temperature of the heating installation. If the outdoor temperature increases, the system control reduces the flow temperature. The system control responds to the fluctuations in the outdoor temperature and uses the flow temperature to ensure that the room temperature remains at the desired temperature.
Cooling
The room temperature sensor measures the room temperature and sends the data to the system control. If the room temperature is higher than the desired temperature that is set, the system control switches cooling on.
Ventilation
Using a controlled exchange of air, the ventilation unit ensures that the living rooms are ventilated and aerated. The system controller controls the air volume flow via the ventilation levels that are set.
Domestic hot water generation
A temperature sensor measures the temperature of the water in the domestic hot water cylinder and forwards the values to the system control. If the temperature lies below the set value, the system control increases the temperature in the domestic hot water circuit and therefore heats up the water to the set domestic hot water temperature.
Circulation
The secondary return pipe is connected to the domestic hot water pipe and forms a circuit with the domestic hot water cylinder. The circulation pump pumps the domestic hot water through the domestic hot water pipe, either continuously or on a time-controlled basis. This means that domestic hot water is available at the draw-off points.
Zones
A building is divided into several zones if the heat demand differs between different sections of the building.
Hybrid manager
If a heat pump and an additional boiler are connected, you can use the hybrid manager. If there is a heat demand, the hybrid manager picks the heat generator that is more cost-efficient. The hybrid manager decides which heat generator to operate based on the tariffs that are set in relation to the heat demand.
To ensure that the heat pump and the boiler can work effectively and in synch with one another, the tariffs (→ Page 16) must be set correctly. If the tariffs are set incorrectly, this results in increased costs.
Frost protection function
The frost protection function protects the heating installation and flat from frost damage. The frost protection function monitors the outdoor temperature.
If the outdoor temperature
Avoiding moisture and mold damage
In heavily insulated rooms that only allow a small exchange of air, moisture and mold damage may occur.
Preventing malfunctions
Data plate
The data plate is located on the rear of the system control underneath the unit mounting bracket. The data plate contains the following information
Information on the identific- ation plate | Meaning |
Serial number | for identification; 7th to 16th digits = product article number |
VRC 700f/4 | Product designation |
V | Operating voltage |
mA | Current consumption |
Read the instructions | |
LR06 | Battery type designation |
T60 | Max. permitted environmental temperature: 0 to 60 °C |
Serial number
You can call up the serial number to the display under Menu → Information → Serial number. The 10-digit article number is located in the second line.
CE marking
The CE mark shows that the products comply with the basic requirements of the applicable guidelines as stated on the data plate. The manufacturer hereby declares that the type of radio equipment that is described in these instructions complies with Directive 2014/53/EU. The complete text for the EU Declaration
of Conformity is available at: http://www.vaillantgroup.com
Operating structure
Adjustment and display levels
The product has two adjustment and display levels. The end user level contains information and setting options that you require as the end user. The installer level is reserved for the competent person. It is protected by a code. Only competent persons may change any settings at the installer level. End user level (→ Page 22)
Menu structure design
The menu structure consists of several selection levels and a set level. You can always use the selection button Menu to access selection level 1 from the basic display. You can use the selection button Op. mode to directly access the setting level Operating mode. The lowest level is always the setting level.
Selection level
The scroll bar (1) only appears if there are more list entries that can be shown at once on the display.
Setting level
In the setting level, you can select the values you want to read or change
The system control must retrieve the values from the radio receiver unit first, which can take up to 2 seconds. During that time, the display shows dashes (–) instead of values.
The soft key function for the selection buttons
Both selection buttons have a soft key function, i.e. different functions may be assigned to the selection buttons. If, for example, you press the left-hand selection button, the current function switches from Menu to Back.
Basic display
The basic display appears:
Preferred zone in the basic display
If your heating installation has several zones, the competent person sets the zone whose values are to appear in the basic display.
Preferred operating mode in the basic display
If your heating installation is designed for two of the three operating modes (heating, cooling, or ventilating), you can switch the basic display to the required operating mode. Setting the preferred display (→ Page 16)
Information in the basic display
The basic display shows the most important current settings and values for the heating installation. Various information may appear in the basic display. This
depends on which operating mode you give preference to in the basic display and the mode that this operating mode is in.
Basic display for the Heating operating mode
Mode | Time periods | Symbol | Information field |
Auto | On | | Desired heating temp. appears: – The system control maintains the temper- ature at the desired level. Empty line appears: – The system control does not request any heating energy. |
Off | | ||
Day | |||
Set-back | |||
off | Empty line |
Basic display for the Cooling operating mode
Mode | Time periods | Symbol | Information field |
Auto | On | Desired cooling temp. | |
Off | Empty line | ||
Day | Desired cooling temp. | ||
off | Empty line |
Basic display for the Ventilation operating mode
Mode | Time periods | Symbol | Information field |
Auto | On | Max. vent. stage | |
Off | Max. vent. stage | ||
Day | Ventilation stage | ||
Set-back | Ventilation stage |
Basic display for the Manual cooling advanced function
Mode | Time periods | Information field |
Activated | On | Desired cooling temp. |
Off | Empty line |
Operating concept
The system control is operated using two selection buttons and a rotary knob. You can use the selection buttons to do the following:
The display shows an element that is highlighted by white writing on a black background. A flashing, highlighted value means that you can change the value. If you do not operate the system control for more than 10 seconds, the background lighting switches off. If you do not operate the system control during a period of more than 5 minutes, the basic display appears again. If you do not operate the system control for more than 60 seconds, the system control becomes inoperative and dashes (–) appear on the display instead of values.
Using the rotary knob to make settings in the basic display
If the display shows the basic display, you can use the rotary knob to change the setting for the desired temperature or ventilation level. The setting that you change depends on selecting the preferred display in the basic display, the selected operating mode, and the set mode for the operating mode.The desired temperature in the Heating operating mode
The desired temperature in the Cooling operating mode
Desired day temperature Only today: 18 °C For long-term change, press OK | ||
OK |
Mode | Time periods | Effect |
Auto | On | Switch to another display view with the request: – Permanent change to the Day temp. heating – Change to the Day temp. heating for six hours |
Off | Direct change to the Set-back temp. heat. for six hours | |
Day | Switch to another display view with the request: – Permanent change to the Day temp. heating – Change to the Day temp. heating for six hours | |
Set-back | Direct change to the Set-back temp. heat. for six hours | |
off | None |
Ventilation level in the Ventilation operating mode
Mode | Time periods | Effect |
Auto | On | Direct permanent change to the Day temp. cooling |
Off | None | |
Day | Direct permanent change to the Day temp. cooling | |
off | None |
Mode | Time periods | Effect |
Auto | On | Direct permanent change to the Max. vent. stage: Day |
Off | Direct permanent change to the Max. vent. stge: Night | |
Day | Direct permanent change to the Max. vent. stage: Day | |
Set-back | Direct permanent change to the Max. vent. stge: Night |
The desired temperature in the Manual cooling advanced function
Mode | Time periods | Effect |
Activated | On | Direct permanent change to the Day temp. cooling |
Off | None |
Using the rotary knob to make settings with no effect You cannot influence the following advanced functions by turning the rotary knob:
For example, changing the display contrast
Menu | |||
Information | |||
Desired temperatures Timer programmes | |||
Back | Select |
Menu | |||
Planning days away from home Days at home scheduling Basic settings | |||
Back | Select |
Basic settings | ||
Language Date/time Display | ||
Back | Select |
Display | ||
Display contrast 9 Button lock | ||
Back | Change |
Display | ||
Display contrast 9 Button lock | ||
Cancel | OK |
Display | ||
Display contrast 12 Button lock | ||
Cancel | OK |
Operating and display functions
Note
The functions described in this section are not available for all system configurations. Overview of operating modes and the end user level
Operating modes (→ Page 22)
End user level (→ Page 22)
The path details given at the start of each function description indicate how you reach this function in the menu structure. The description of the functions for ZONE1 also applies to all available zones.
Reading the system status
Menu → Information → System status
Under System status, there is a list containing information that provides an overview of the current system status, and current settings that you can change there.
System
Menu → Information → System status → Fault status
If no maintenance is required and no faults have occurred, the value No fault appears for Fault status. If maintenance is required or a fault has occurred, the value Fault list is shown for Fault status. In this case, the right-hand selection button is for the Display function. If you press the right-hand selection button Display, the list of fault messages appears on the display.
Menu → Information → System status → Green IQ
You can use the function if the connected heat generator Green IQ is capable of this. On: The operating mode controls the heat generator in the heating and cylinder charging mode so that a maximum gross calorific value utilization is achieved. Off: The operating mode is switched off.
Menu → Information → System status → Water pressure
Menu → Information → System status → Curr. room air hum.
ZONE1
Menu → Information → System status → Day temp. heating
The system control has an integrated temperature sensor, which determines the room temperature.
Ventilation
Menu → Information → System status → Air quality sensor 1/2
Display of energy consumption and energy yield
In the display and in the app that can also be used the control displays values for the energy consumption and/or the energy yield. The control displays an estimation of the values for the installation. Among other things, the values are influenced by the following:
External components, such as external heating pumps or valves, and other consumers and appliances in the household are still not taken into consideration.
The deviations between the energy consumption or energy yield that is displayed and the actual energy consumption or energy yield may be significant.
The specifications for the energy consumption or energy yield are not suitable to be used to create or compare energy billing.
Consumption
Some components do not support the calculation of consumption, the total of which is shown on the display. In the instructions for the components, you can find out if and how the individual components determine the consumption.
Menu → Information → Consumption → Current month →Heating → Electricity
Menu → Information → Consumption → Last month → Heating → Electricity
Diagram: Reading the solar yield
Menu → Information → Solar yield
Diagram: Reading the environmental yield
Menu → Information → Environmental yield
The diagram under Environmental yield shows a comparison between the monthly environmental yields for the previous year and for the current year. The total yield is displayed on the bottom right. The highest value achieved in one month for the last two years is displayed in the top right.
Diagram: Reading the electrical consumption
Menu → Information → Electrical consumption
The diagram under Electrical consumption shows a comparison between the monthly consumption of electricity for the previous year and for the current year.
The total yield is displayed on the bottom right. The highest value achieved in one month for the last two years is displayed in the top right.
Diagram: Reading the fuel consumption
Menu → Information → Fuel consumption
The diagram below Fuel consumption shows a comparison between the monthly fuel consumption for the previous year and for the current year. The total yield is displayed on the bottom right. The highest value achieved in one month for the last two years is displayed in the top right.
Diagram: Reading the heat recovery yield
Menu → Information → Heat recovery
The diagram under Heat recovery shows a comparison between the monthly heat recovery yield for the previous year and for the current year. The total yield is displayed on the bottom right. The highest value achieved in one month for the last two years is displayed in the top right.
Read the competent person’s contact details
Menu → Information → Contact details
If the competent person entered their company name and telephone number when they installed the product, you can read this data under Contact details.
Reading the serial number and article number
Menu → Information → Serial number
You can use this function to read the product’s serial number. The article number is found in the second line.
Settings
Setting desired temperatures
This function is used to set the desired temperatures for the zone and hot water generation.
Zone
Menu → Desired temperatures → ZONE1
You can set different desired temperatures for the zone:
Heating
Day temp. heating: Set a comfortable room temperature in the living rooms. Set-back temp. heat.: Set a low room temperature at which the living rooms do not cool down.
Cooling
Day temp. cooling: Set a comfortable room temperature in the living rooms.
Hot water generation
Danger!
Risk of death from legionella. Legionella multiplies at temperatures below 60 °C.
Menu → Desired temperatures → Domestic hot water
You can set the desired Domestic hot water temperature for the domestic hot water circuit. If a heat pump is connected and you have set the desired temperature to above 55 °C, it may be the case that it is the backup boiler that predominantly takes on the task of supplying domestic hot water.
Setting the ventilation level
Menu → Ventilation stage
You can use this function to set how quickly the used room air is replaced with fresh outdoor air. Max. vent. stage: Day: The ventilation guarantees quick
exchange of air. Max. vent. stage: Night: The ventilation guarantees a reduced air change.
Time program
You can use the time program to switch the system control between two implemented settings at specified times. To do this, create the required time periods in the time program.
You can create up to three time periods for each individual day and for predefined blocks (Monday – Friday, Saturday – Sunday, Monday – Sunday). When entering time periods for individual days or blocks, the last information that was entered always applies. If you have not set any time periods, the system controller uses the time periods set in the factory settings.
Note
Once time programs are set, they are retained even if there is a loss of voltage.
Heating operating mode example: Time
period for a day
Time
B Temperature
You can specify the temperatures (Day temp. heating and Set-back temp. heat.) In the Setting the Desired temperatures (→ Page 13) function. You can specify the times for the time periods in the Setting time programs Heating (→ Page 14) function.
Within the time periods, the system controller maintains the room temperature at the set Day temp. heating. Outside of the time periods, the system controller maintains the room temperature at the set Set-back temp. heat.
Setting time programs quickly
If, for example, you require different time periods for just one working day in the week, first set the times for the entire block Monday – Friday. Then set the different time periods for the working day.
Displaying and changing different times in the block
If you view a block in the display and have defined a different time period for a day in this block, the display indicates the time periods in the block with !!. If you press the right-hand selection button Select, a message appears on the display which informs you about different time periods. You do not need to adjust the times. You can use the right-hand selection button OK to display and change the set times for the block marked with !!.
Individual dates vary from the selected time program Mo-Su. | ||
Back | OK |
Setting the Heating time program
Menu → Time programs → ZONE1 – The time programs are only effective for the Heating operating mode in automatic mode. Within the time periods, the system control brings the temperature of the connected rooms to the set desired temperature Day temp. heating. Outside of these time periods, the system control switches to the operating mode that the competent person has set: Eco or Set-back temp. heat.. If the competent person has left the factory setting Eco, the system control switches off the heating function. Setting the Heating operating mode. (→ Page 17)
Setting the Cooling time program
Menu → Time programs → ZONE1: Cooling The time programs are only effective in the Cooling mode and the Manual cooling advanced function. In each set time period, the desired temperature that you set in the Desired temperatures function applies. Within the time periods, the zone cools the living areas to the desired Day temp. cooling temperature. Outside this time period, there is no cooling.
Setting the domestic hot water generation time program
Menu → Time programs → DHW circuit
The time programs are only effective for domestic hot water generation in automatic mode. In each set time period, the desired Domestic hot water temperature applies. At the end of a time period, the system control switches the domestic hot water generation off until the start of the next time period.
Setting the time program Circulation
Menu → Time programs → Circulation The time programs are only effective for circulation in Automatic mode. The set time periods determine the operating times for circulation. Within the time period, the circulation is switched on. Outside the time period, the circulation is switched off.
Setting the Ventilation time program
Menu → Time programs → Ventilation The time programs are only effective for ventilation in automatic mode. In each set time period, the ventilation
level that you set in the Ventilation function applies. Within the time period, the system control regulates the ventilation unit to Max. vent. stage: Day as a maximum. Outside the time period, the system control regulates the ventilation unit to Max. vent. stage: Night as a maximum.
Setting the High tariff time program
Menu → Time programs → High tariff You can use this function to set when the high tariff or the low tariff should be used to calculate the costs. Within the time period: For the high tariff Outside of the time period: For the low tariff The times of high tariffs depend on your energy supply company. If the energy supply company only offers one tariff, you do not need to set any time periods. The cost of electricity is calculated using one tariff. Setting costs (→ Page 16)
Days away from home schedule
Menu → Days away from home schedule You can use this function to set a period of time and a temperature for the days that you are away from home. Heating installation operation during the set time period
While the Days Away from Home scheduling function are activated, it has priority over the set operating mode. At the end of the specified period, or if you cancel the function, the heating installation returns to the pre-set mode.
Day-at-home scheduling
Menu → Days at home schedule In the specified period, the heating installation works in the Automatic mode and uses the day settings for Sunday, which was set using the Time programs function. At the end of the specified period, or if you cancel the function, the heating installation returns to preset mode.
Select language
Menu → Basic settings → Language
You can use this function to change to the language that you want to appear in the display.
Setting your language
Setting the date and time
Note
If you disconnect the entire heating installation from the power supply, the time continues to run correctly for 30 minutes. You then have to reset the date and time.
Setting the date
Menu → Basic settings → Date/time → Date
Select this function to set the current date. All functions contain a date related to the set date.
Setting the time
Menu → Basic settings → Date/time → Time
Activating the automatic or manual changeover to daylight saving time
Menu → Basic settings → Date/time → Daylight saving time You can use this function to set whether the system control automatically changes over to daylight saving time, or whether you want to do this manually.
Auto: The system control automatically changes over to daylight saving time. The system control uses Central European Summer Time: Start = last Sunday in March, end = last Sunday in October. Manual: You have to manually change over to daylight saving time. If the outdoor temperature sensor is equipped with a DCF77 receiver, the time is changed over automatically. This Daylight saving time function is not used.
Set display contrast
Menu → Basic settings → Display → Display contrast You can use this function to set the display contrast in relation to the brightness of the surroundings to ensure that the display is clearly legible.
Activating Button lock
Menu → Basic settings → Display → Button lock You can use this function to activate the button lock. After one minute of not pressing any button or operating the rotary knob, the button lock is active and you can no longer change any functions unintentionally. Each time you actuate the system control, the following message appears in the display Button lock active To unlock, press OK for 3 seconds. If you press and hold the OK button for three seconds, the basic display appears and you can change functions. The button lock becomes active again if you do not press any button or operate the rotary knob for one minute.
To permanently remove the button lock, you must first release the button lock and then select the value off in the Button lock function.
Setting the preferred display
Menu → Basic settings → Display → Preferred display You can use this function to choose whether you see the data for heating, cooling or ventilation in the basic display.
Setting costs
You must specify all tariffs in the unit of currency per kWh for the calculation to be correct. If the tariffs are in the unit of currency per m3 for you, request
that your energy supply company provides the required tariffs in the unit of currency per kWh. If your energy supply company only offers one electricity
tariff, enter the same value for the High-tariff elec. rate (→ Page 16) and Low-tariff elec. rate (→ Page 16) functions. Round the tariff data up or down to one decimal point. To establish the factor that is to be set, multiply the value by 10. Example:
Costs | Factor to be set | |
Tariff for aux. heater (Gas, oil, electricity) | 11.3 currency units/kWh | 113 |
Low-tariff elec. rate (heat pump) | 14.5 currency units/kWh | 145 |
High-tariff elec. rate (heat pump) | 18.7 currency units/kWh | 187 |
Setting the Tariff for the backup boiler
Menu → Basic settings → Costs → Tariff for aux. heater The hybrid manager can use this function to correctly calculate the costs for the backup boiler. To do this, the hybrid manager requires the factor that is to be set. In order to enter the correct factor, you must request the tariff from your energy supply company and calculate the factor in accordance with the example.
Setting the low-tariff electricity rate
Menu → Basic settings → Costs → Low-tariff elec. rate The hybrid manager can use this function to correctly calculate the costs for the backup boiler. To do this, the hybrid manager requires the factor that is to be set. In order to enter the correct factor, you must request the tariff from your energy supply company and calculate the factor in accordance with the example.
Setting the high-tariff electricity rate
Menu → Basic settings → Costs → High-tariff elec. rate The hybrid manager can use this function to correctly calculate the costs for the backup boiler. To do this, the hybrid manager requires the factor that is to be set. In order to enter the correct factor, you must request the tariff from your energy supply company and calculate the factor in accordance with the example.
Set offset room temperature
Menu → Basic settings → Offset → Room temperature The system control can display the current room temperature if it is installed in a living room. A thermometer is integrated in the system control for measuring the room temperature. You can use the offset to correct the measured temperature value.
Set the offset outdoor temperature
Menu → Basic settings → Offset → Outside temperature The thermometer in the system control’s outdoor temperature sensor measures the outdoor temperature. You can use the offset to correct the measured temperature value.
Changing a zone name
Menu → Basic settings → Enter zone name You can now modify the factory-specified zone names as you wish. The name is limited to 10 characters.
Activating Heat Recovery
Menu → Basic settings → Ventilation → Heat recovery The Heat recovery function is set to Auto. This means that an internal control system checks whether heat recovery makes sense, or whether the outdoor air can be guided directly into the living room. For more information, see the operating instructions for recoVAIR…/4 and later models. If you have selected Activate, heat recovery is used constantly.
Setting the room air humidity
Menu → Basic settings → Max. room air humidity If the room air humidity exceeds the value set, a connected dehumidifier is activated. As soon as the value drops below the value that is set, the dehumidifier switches off again.
Resetting to the default setting
You can reset the settings for the Time programs or for Everything is to the default setting. Menu → Basic settings → Default setting → Time programs With Time programs, you reset all the settings you have made in the Time programs function to the default setting. All other settings that include times, such
as Date/time, are not affected. While the system control is resetting the time program settings to the default settings, In progress is shown on the display. The basic display is then shown on the display.
Caution.
Risk of a malfunction. The Default setting Everything function restores all settings to the default settings, including those set by the competent person. It may be the case that it is no longer possible to operate the heating installation after this.
Installer level
The Installer level is reserved for the competent person and is therefore protected by an access code. At this level, the competent person can implement the required settings.
Operating modes
The operating modes can be activated directly from any operating mode using the right-hand selection button Op. mode. If the heating installation is equipped with more than one zone, the activated operating mode only applies to the zone that was preset by the competent person. If more than one zone is activated, you can set a separate operating mode for each zone using the left-hand selection button Menu→ Basic settings. The path details are given at the start of each operating mode the description indicates how you reach this operating mode in the menu structure.
Setting the Heating operating mode
Op. mode → Heating Menu → Basic settings → Operating mode → ZONE1 →
Heating
You can use this function to specify how the heating installation should operate during heating.
off: The zone is switched off in this operating mode and the frost protection function is activated.
Auto: The operating mode brings the zone to the desired temperature set for the Day temp. heating in the time periods that you have set in the time program.
Outside these time periods, the system control regulates the control behavior set by the competent person. Eco The heating function is switched off and the system controller monitors the outdoor temperature. If the outdoor temperature falls below 3 °C, the system control switches the heating function on after the end of the frost protection delay time and brings the room temperature to the set desired temperature Set-back temp. heat.. Despite the heating function being activated, the burner is only active on demand. If the outdoor temperature rises above 4 °C, the system control switches the heating function off but continues to monitor the outdoor temperature.
Set-back: The heating function is switched on and the system control brings the room temperature to the set desired temperature Set-back temp. heat.. Day: The operating mode brings the zone to the desired temperature Day temp. heating, regardless of the time periods that you have set in the time program. Set back: The operating mode brings the zone to the desired temperature Set-back temp. heat., regardless of the time periods that you have set in the time program.
Setting the Cooling operating mode
Op. mode → Cooling Menu → Basic settings → Operating mode → ZONE1 →
Cooling
You can use this function to specify how the heating installation should operate during cooling.
off: The zone is switched off in this operating mode.
Auto: The operating mode brings the zone to the desired temperature Day temp. cooling in the time periods that you have set in the time program. Outside these time periods, the Cooling function is switched off.
Day: The operating mode brings the zone to the desired temperature set for Day temp. cooling, regardless of the time periods that you have set in the time program.
Setting the Ventilation operating mode
The operating instructions for the ventilation unit explain how the ventilation unit works with the ventilation levels. Op. mode → Ventilation You can use this function to define how the ventilation the unit operates during ventilation.
Auto: The operating mode controls the air exchange via the set ventilation level Max. vent. stage: Day in the set time periods that you have defined in the time program. The set ventilation level is Max. vent. stage: Night is effective outside of the time periods. If air-quality sensors are connected to the ventilation unit, the ventilation unit varies the ventilation levels: If the air quality is good, the ventilation unit works at a lower ventilation level than the one that is set. If the air quality is poor, the ventilation unit works at a higher ventilation level. However, the ventilation unit cannot exceed the Max. vent. stage: Day and Max. vent.
stage: Night ventilation levels that are set.
Day: The operating mode constantly controls the exchange of air using the value that you set in the Max. vent. stage: Day ventilation level. Set-back: The operating mode constantly controls the exchange of air using the value that you set in the Max. vent. stage: Night ventilation level.
Setting the operating mode for domestic hot water generation
Op. mode → Domestic hot water You can use this function to specify how the heating installation should operate during domestic hot water generation. off: Domestic hot water generation is switched off and the frost protection function is activated. Auto: The operating mode brings the domestic hot water generation to the desired temperature set for Domestic hot water in the time periods that you have set in the time program. Day: The operating mode brings the domestic hot water generation to the desired temperature set for Domestic hot water, regardless of the time periods that you have set in the time program.
Operating mode for the circulation
The operating mode for circulation always corresponds to the operating mode for hot water. You cannot set a different operating mode.
Advanced functions
The advanced functions can be activated directly from any operating mode using the right-hand selection button Op. mode. If the heating installation is equipped with more than one zone, the activated advanced function only applies to the zone that was preset by the competent person. If more than one zone is activated, you can set a separate advanced function for each zone using the left-hand selection button Menu → Basic settings. The path details are given at the start of each advanced function description to indicate how you can access this advanced function in the menu structure.
Activating manual cooling
Op. mode → Manual cooling If the outdoor temperature is high, you can activate the Manual cooling advanced function. You define for how many days you want to activate the advanced function. If you activate Manual cooling, you cannot use the heating function at the same time. The Manual cooling function takes priority over the heating function. The setting applies for as long as the advanced function is active. The advanced function is deactivated if the days that are set have elapsed or if the outdoor temperature falls below 4 °C. If you want to set the temperature separately for more than one zone, you can set these temperatures using the Desired temperatures function
Activating 1 day at home
Op. mode → 1 day at home Menu → Basic settings → Operating mode → ZONE1 → 1 day at home The 1 day at home advanced function activates the automatic mode in the operating mode Heating with the settings for Sunday. The advanced function is automatically deactivated after 00:00 (midnight) or you can cancel the advanced function first. The heating installation then returns to the pre-set operating mode.
Activating 1 day away from home
Op. mode → 1 day away from home Menu → Basic settings → Operating mode → ZONE1 → 1 a day away from home The 1 day away from home advanced function brings the room temperature to the desired Set-back temperature. Domestic hot water generation and circulation are switched off and frost protection is activated. Ventilation is activated and works at the lowest ventilation level. The advanced function is automatically deactivated after 00:00 (midnight) or you can cancel the advanced function first. The heating installation then returns to the pre-set operating mode.
Activating Ventilation Boost
Op. mode → Ventilation boost Menu → Basic settings → Operating mode → ZONE1 → Ventilation boost This Ventilation boost advanced function switches the
zone off for 30 minutes. The frost protection function is activated, and domestic hot water generation and circulation remain active. Ventilation is activated and works at the highest ventilation level. The advanced function is automatically deactivated after 30 minutes or you can cancel the advanced function first. The heating installation will then return to the pre-set operating mode.
Activating Party Function
Op. mode → Party function Menu → Basic settings → Operating mode → ZONE1 → Party function The advanced function regulates the room temperature to the desired Day temperature, the domestic hot water to the desired Domestic hot water temperature, and the ventilation to ventilation level Max. vent. stage: Day in accordance with the set time periods. The circulation is activated The advanced function is automatically deactivated after six hours or you can cancel the advanced function first. The heating installation will then return to the pre-set operating mode.
Activating Cylinder boost
Op. mode → Cylinder boost The Cylinder boost advanced function heats the water in the domestic hot water cylinder until it reaches the set desired temperature Domestic hot water. The advanced function is active for one hour unless you cancel it sooner. The heating installation then returns to the preset operating mode.
Activating System OFF active
Op. mode → System OFF active The System OFF active advanced function switches off the heating function, the domestic hot water circuit, the circulation, and the cooling. The frost protection function is activated. Ventilation is activated and works at the lowest ventilation level. The advanced function is deactivated by canceling the advanced function. The heating installation will then return to the pre-set mode.
Messages
Maintenance message
Maintenance messages (→ Appendix C) If maintenance is required, the system control displays a maintenance message in the display. To prevent the heating installation from breaking down and to prevent damage, you must pay attention to the maintenance message: Observe the operating instructions for the unit shown. Only carry out the maintenance instructions that are described in the operating instructions for the unit shown. For all other maintenance instructions, inform the competent person.
Fault message
Fault messages (→ Appendix B) A fault message with a fault code (e.g. F.33) and the affected heat generator appear in the system control’s display. Press the Reset selection button. Heat generator fault clearance? appears in the display. Press the OK selection button. Faults are cleared for the heat generator briefly
appears in the display. If the fault persists, inform the competent person. If you would like to see the basic display on the display again, press the left-hand selection button Back. You can read the current fault messages under Menu → Information → System status → Fault status. As soon as a fault message occurs for the heating installation, the setting level displays the value Fault list. The right-hand selection button has been assigned the Display function.
Overview of fault messages (→ Appendix B)
Implementing the setting of the heat pump fails If the fault message Restricted operation/ comfort protection Inactive appears on the display, the heat pump has failed and the system control enters limp home mode. The backup boiler now supplies the heating installation with heating energy. During installation, the competent person has restricted the temperature for limp home mode. You can feel that domestic hot water and heating are not becoming very hot.
While you wait for the competent person to come, you can use the rotary knob to implement the following settings: Inactive: The system control works in limp home mode; heating and domestic hot water become moderately hot. Heating: The backup boiler takes over the heating mode; the heating becomes hot, and the domestic hot water is cold. DHW: The backup boiler takes over the domestic hot water mode; the domestic hot water becomes hot, and the heating is cold.
DHW+heat.: The backup boiler takes over the heating and domestic hot water mode; the heating and the domestic hot water becomes hot. The backup boiler is not as efficient as the heat pump, meaning that using only the backup boiler to generate heat is expensive. If you want to implement settings on the system control, click Back and the basic display appears in the display. After five minutes of no operation, the fault message appears again on the display.
Cleaning the outdoor temperature sensor
Clean the solar cell with a damp cloth and a little solvent-free soap. Do not use sprays, scouring agents, detergents, solvents or cleaning agents that contain chlorine.
Note
After you have cleaned the solar cell, there is a delay before the fault message disappears because the battery has to be recharged first.
Changing the batteries
Danger!
Risk of death caused by unsuitable batteries! If batteries are replaced with the wrong type of battery, there is a risk of explosion. Ensure that you use the correct battery type when replacing batteries. Dispose of used batteries in accordance with the instructions in this manual.
Care
Decommissioning
Guarantee
We only grant a Vaillant manufacturer’s warranty if a suitably qualified engineer has installed the system in accordance with Vaillant instructions. The system owner will be granted a warranty in accordance with the Vaillant terms and conditions. All requests for work during the guarantee period must be made to Vaillant Service Solutions.
Customer service
To ensure regular servicing, it is strongly recommended that arrangements are made for a Maintenance Agreement. Please contact Vaillant Service Solutions for further details: Telephone: 0330 100 3461
Product data in accordance with the EU Ordinance no. 811/2013, 812/2013 On units with integrated weather compensators, including a room thermostat function that can be activated, the seasonal room-heating efficiency always includes the correction factor for controller technology class VI. The seasonal room-heating efficiency may deviate if this function is deactivated.
Temperature control class | VI |
Contribution to the seasonal room-heat- ing energy efficiency ɳs | 4.0 % |
Appendix
Overview of the operating and display functions
Note
The functions and operating modes listed are not available for all system configurations.
Operating modes
Operating mode | Setting | Default setting |
Operating mode | ||
Heating | off, Auto, Day, Set-back | Auto |
Cooling | off, Auto, Day | Auto |
Ventilation | Auto, Day, Set-back | Auto |
Domestic hot water | off, Auto, Day | Auto |
Advanced functions | ||
Manual cooling | active | – |
1 day at home | active | – |
1 day away from home | active | – |
Ventilation boost | active | – |
Party function | active | – |
Cylinder boost | active | – |
System OFF active | active | – |
End user level
The description of the functions for ZONE1 also applies to all available zones
Setting level | Values | Unit | Increment, select | Default setting | |
Min. | Max. | ||||
Information → System status → | |||||
System —- | |||||
Fault status | Current value | No fault, Fault list | |||
Green IQ | Off, On | On | |||
Water pressure | Current value | bar | |||
System status | Current value | Standby, Heat. mode, Cool- ing, DHW | |||
Burner | Current value | On, off | |||
Collector temp. | Current value | ℃ | |||
Solar yield | Current value | kWh | |||
Reset solar yield | Yes, No | No | |||
Environmental yield | Current value | kWh | |||
Curr. room air hum. | Current value | % | |||
Current dew point | Current value | ℃ | |||
triVAI | Current value | ||||
Battery status | Current value | Critical, OK | |||
Signal strength | Current value | 1 | |||
ZONE1 —- | |||||
Day temp. heating | 5 | 30 | ℃ | 0.5 | 20 |
Day temp. cooling | 15 | 30 | ℃ | 0.5 | 24 |
Set-back temp. heat. | 5 | 30 | ℃ | 0.5 | 15 |
Room temperature | Current value | ℃ | |||
Ventilation —- |
Setting level | Values | Unit | Increment, select | Default setting | |
Min. | Max. | ||||
Air quality sensor 1 | Current value | ppm | |||
Air quality sensor 2 | Current value | ppm | |||
Exhaust air humidity | Current value | %rel | |||
Information → Consumption → Current month → | |||||
Heating —- | |||||
Electricity | Total value for the current month | kWh | |||
Fuel | Total value for the current month | kWh | |||
Hot water —- | |||||
Electricity | Total value for the current month | kWh | |||
Fuel | Total value for the current month | kWh | |||
Information → Consumption → Last month → | |||||
Heating —- | |||||
Electricity | Total value for the last month | kWh | |||
Fuel | Total value for the last month | kWh | |||
Hot water —- | |||||
Electricity | Total value since start- up | kWh | |||
Fuel | Total value since start- up | kWh | |||
Information → Consumption → History → | |||||
Heating —- | |||||
Electricity | Total value since start- up | kWh | |||
Fuel | Total value since start- up | kWh | |||
Hot water —- | |||||
Electricity | Total value since start- up | kWh | |||
Fuel | Total value since start- up | kWh | |||
Information → Solar yield → | |||||
Bar chart | Previous year to cur- rent year comparison | kWh/month | |||
Information → Environmental yield → | |||||
Bar chart | Previous year to cur- rent year comparison | kWh/month | |||
Information → Electrical consumption → | |||||
Bar chart | Previous year to cur- rent year comparison | kWh/month | |||
Information → Fuel consumption → |
Setting level | Values | Unit | Increment, select | Default setting | |
Min. | Max. | ||||
Bar chart | Previous year to cur- rent year comparison | kWh/month | |||
Information → Heat recovery → | |||||
Bar chart | Previous year to cur- rent year comparison | kWh/month | |||
Information → Contact details → | |||||
Installer Phone number | Current values | ||||
Information → Serial number | |||||
Product number | Permanent value | ||||
Desired temperatures → ZONE1 → | |||||
Day temp. heating | 5 | 30 | ℃ | 0.5 | 20 |
Day temp. cooling | 15 | 30 | ℃ | 0.5 | 24 |
Set-back temp. heat. | 5 | 30 | ℃ | 0.5 | 15 |
Desired temperatures → Domestic hot water → | |||||
Domestic hot water | 35 | 70 | ℃ | 1 | 60 |
Ventilation stage → | |||||
Max. vent. stage: Day | Depending on the ventilation unit | 1 | Depending on the ventilation unit | ||
Max. vent. stge: Night | Depending on the ventilation unit | 1 | Depending on the ventilation unit | ||
Time programmes → ZONE1 (Heating) → Time programmes → ZONE1: Cooling → Time programmes → Circulation → Time programmes → Ventilation → | |||||
Individual days and blocks | Monday, Tuesday, Wednes- day, Thursday, Friday, Sat- urday, Sunday and Monday – Friday, Saturday – Sunday, Monday – Sunday | Mo – Fr: 06:00- 22:00 Sa: 07:30-23:30 Su: 07:30-22:00 | |||
Period 1: Start – End Period 2: Start – End Period 3: Start – End | 00:00 | 24:00 | h:min | 00:10 | |
Time programmes → Domestic hot water → | |||||
Individual days and blocks | Monday, Tuesday, Wednes- day, Thursday, Friday, Sat- urday, Sunday and Monday – Friday, Saturday – Sunday, Monday – Sunday | Mo to Fr: 05:30- 22:00 Sa: 07:00-23:30 Su: 07.00-22.00 | |||
Period 1: Start – End Period 2: Start – End Period 3: Start – End | 00:00 | 24:00 | h:min | 00:10 | |
Time programmes → Noise reduction operation → |
Setting level | Values | Unit | Increment, select | Default setting | |
Min. | Max. | ||||
Individual days and blocks | Monday, Tuesday, Wednes- day, Thursday, Friday, Sat- urday, Sunday and Monday – Friday, Saturday – Sunday, Monday – Sunday | Mon – Sun: 00:00- 00:00 | |||
Period 1: Start – End Period 2: Start – End Period 3: Start – End | 00:00 | 24:00 | h:min | 00:10 | |
Time programmes → High tariff → | |||||
Individual days and blocks | Monday, Tuesday, Wednes- day, Thursday, Friday, Sat- urday, Sunday and Monday – Friday, Saturday – Sunday, Monday – Sunday | Mo – Su: 11:00- 13:00 | |||
Period 1: Start – End Period 2: Start – End Period 3: Start – End | 00:00 | 24:00 | h:min | 00:10 | |
Days away from home scheduling → | |||||
Start | 01.01.01 | 31.12.99 | dd.mm.yy | Day.Month.Year | 01.01.14 |
End | 01.01.01 | 31.12.99 | dd.mm.yy | Day.Month.Year | 01.01.14 |
Temperature | 5 | 30 | ℃ | 1 | 15 |
Days at home scheduling → | |||||
Start | 01.01.01 | 31.12.99 | dd.mm.yy | Day.Month.Year | 01.01.14 |
End | 01.01.01 | 31.12.99 | dd.mm.yy | Day.Month.Year | 01.01.14 |
Basic settings → Language → | |||||
Selectable language | English | ||||
Basic settings → Date/time → | |||||
Date | 01.01.01 | 31.12.99 | dd.mm.yy | Day.Month.Year | 01.01.15 |
Time | 00:00 | 23:59 | h:min | 00:10 | 08:00 |
Daylight saving time | Manual, Auto | Manual | |||
Basic settings → Display → | |||||
Display contrast | 1 | 15 | 1 | 9 | |
Button lock | off, On | off | |||
Preferred display | Heating, Cooling, Vent. | Heating | |||
Basic settings → Costs → | |||||
Tariff for aux. heater | 1 | 999 | 1 | 12 | |
Low-tariff elec. rate | 1 | 999 | 1 | 16 | |
High-tariff elec. rate | 1 | 999 | 1 | 20 | |
Basic settings → Offset → | |||||
Room temperature | -3.0 | 3.0 | K | 0.5 | 0.0 |
Outside temperature | -3.0 | 3.0 | K | 0.5 | 0.0 |
Basic settings → Operating mode → ZONE1 → | |||||
Heating | off, Auto, Day, Set-back | Auto |
Setting level | Values | Unit | Increment, select | Default setting | |
Min. | Max. | ||||
Cooling | off, Auto, Day | Auto | |||
1 day at home | Active, Not active | Not active | |||
1 day away from home | Active, Not active | Not active | |||
Ventilation boost | Active, Not active | Not active | |||
Party function | Active, Not active | Not active | |||
Basic settings → Enter zone name → | |||||
ZONE1 | 1 | 10 | Let- ter/number | A to Z, 0 to 9, space | ZONE1 |
Basic settings → Ventilation → | |||||
Heat recovery | Auto, Activate, off | Auto | |||
Basic settings → Max. room air humidity → | |||||
Max. room air hum. | 30 | 70 | %rel | 1 | 40 |
Basic settings → Default setting → | |||||
Time programmes | Yes, No | No | |||
Everything | Yes, No | No | |||
Installer level → | |||||
Enter code | 000 | 999 | 1 | 000 |
Symptom | Possible cause | Measure | |
Display remains dark | The batteries are flat | 1. | Change all the batteries. (→ Page 19) |
2. | If the fault persists, inform the competent person. | ||
No changes in the display when | Software error | 1. | Take all the batteries out. |
the rotary knob is turned | 2. | Insert the batteries in the battery compartment, making sure | |
that the poles are the right way round. | |||
3. | If the fault persists, inform the competent person. | ||
No changes in the display via the selection buttons are pressed | Software error | 1. 2. | Take all the batteries out. Insert the batteries in the battery compartment, making sure that the poles are the right way round. |
3. | If the fault persists, inform the competent person. | ||
Display view: No RF commu- nication | The reception strength is too weak | 1. | Take the system control to the radio receiver unit and see if the reception strength increases. |
2. | If the reception strength is greater than 4, have the compet- ent person install the system control in a different location. | ||
3. | If the reception strength when directly next to the radio re- ceiver unit is less than 4, switch off the mains switch for all the heat generators and then wait approximately 1 minute before switching it back on. | ||
4. | If the fault persists, inform the competent person. | ||
Display view: Button lock act- ive To unlock, press OK for 3 seconds, it is not possible to change the settings or values | Button lock is active | 1.
2. | If you would like to change any of the values, follow the in- structions on the display. Also read through the Button lock Activate (→ Page 15) function. |
Display view: Restricted opera- tion/ comfort protection, insuf- ficient heating up of the heating and the domestic hot water | Heat pump does not work | 1. 2.
3. | Inform the competent person. Select the setting for limp home mode until the competent person arrives. To do this, read through the Implementing the setting when the heat pump fails (→ Page 19) function. |
Symptom | Possible cause | Measure | |
Display view: Fault F. Fault: Heat generator 1, the specific fault code (e.g. F.33) and the specific heat generator appear behind F. in the display | Heat generator faults | 1. 2. | Carry out a Reset fault message (→ Page 19). If the fault persists, inform the competent person. |
Display view: Change batteries | The batteries are almost flat | 1. 2. | Change all the batteries. (→ Page 19) If the fault persists, inform the competent person. |
Display view: Clean outside temperature sensor | The battery in the outdoor tem- perature sensor is flat | 1. 2. | Cleaning the outdoor temperature sensor (→ Page 19). If the fault persists, inform the competent person. |
Maintenance messages
The maintenance message Service heat pump 1 is an example of a maintenance message that may appear for heat pumps 1 to 6. The maintenance message Service heat generator 1 is an example of a maintenance message that may appear for heat generators 1 to 6.
# | Message | Description | Maintenance work | Interval | |
1 | Service heat pump 1 | The heat pump requires main- tenance work. | Refer to the operating instruc- tions of the relevant heat pump for information on the mainten- ance work required | See the operating instructions for the heat pump | |
2 | Service heat generator 1 | The heat generator requires maintenance work. | Refer to the operating instruc- tions of the relevant heat gener- ator for information on the main- tenance work required | See the operating instructions for the heat generator | |
3 | Service ventila- tion unit | The ventilation unit requires maintenance work. | Refer to the operating instruc- tions of the ventilation unit for information on the maintenance work required | See the operating instructions for the ventilation unit | |
4 | Service date Next service on | The competent person has entered a date on which main- tenance is due for the heating installation. | Inform the competent person if maintenance work is required | Date entered in the system con- trol |
Vaillant Ltd.
Nottingham Road Belper Derbyshire DE56 1JT
Telephone 0330 100 3461
info@vaillant.co.uk www.vaillant.co.uk
© These instructions, or parts thereof, are protected by copyright and may be reproduced or distributed only with the manufacturer’s written consent.
We reserve the right to make technical changes.
DOWNLOAD MANUALS:
Vaillant VRC 700f-4 Programmable Thermostat Operating Instructions
Vaillant VRC 700f/4 Programmable Thermostat Operating Instructions
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…