Classification of action-related warnings The action-related warnings are classified in accordance with the severity of the possible danger using the following warning signs and signal words
Intended use
In the event of inappropriate or improper use, damage to the product and other property may arise. The product is intended for using an eBUS interface to control a heating installation with heat generators from the same manufacturer.
Intended use includes the following:
This product can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabil-ities or lack of experience and knowledge if they have been given supervision or instruc-tion concerning use of the product in a safe way and understand the hazards involved. Children must not play with the product. Cleaning and user maintenance work must not be carried out by children unless they are supervised. Any other use that is not specified in these in-structions, or use beyond that specified in this document shall be considered improper use. Any direct use in industrial or commercial processes is also deemed to be improper. Caution. Improper use of any kind is prohibited.
General safety information
Notes on the documentation
Observing other applicable documents
Storing documents
Keep this manual and all other applicable documents safe for future use.
Validity of the instructions
These instructions apply only to:
Nomenclature
The following terms are used for simplification:
Function availability
The functions described in these operating instructions are not available for all system configurations. The system control only shows the functions that are available in the system configuration you have installed.
Design of the product
The system control is a weather-compensated system con-trol with an outdoor temperature sensor installed in the open air. The system control is connected to the outdoor temperature sensor and the heat generator. The system control controls the heating installation and other connected components, e.g. the domestic hot water generation for a connected do-mestic hot water cylinder or the ventilation of a connected ventilation unit.
Heating
The outdoor temperature sensor measures the outdoor temperature and forwards the values to the system control. When the outdoor temperature is low, the system control in-creases the flow temperature of the heating installation. If the outdoor temperature increases, the system control reduces the flow temperature. The system control responds to the fluctuations in the outdoor temperature and uses the flow temperature to ensure that the room temperature remains at the desired temperature.
Cooling
The room temperature sensor measures the room temper-ature and sends the data to the system control. If the room temperature is higher than the desired temperature that is set, the system control switches cooling on.
Ventilation
Using a controlled exchange of air, the ventilation unit en-sures that the living rooms are ventilated and aerated. The system control controls the air volume flow via the ventilation levels that are set.
Domestic hot water generation
A temperature sensor measures the temperature of the wa-ter in the domestic hot water cylinder and forwards the val-ues to the system control. If the temperature lies below the set value, the system control increases the temperature in the domestic hot water circuit and therefore heats up the wa-ter to the set domestic hot water temperature.
Circulation
The secondary return pipe is connected to the domestic hot water pipe and forms a circuit with the domestic hot water cylinder. The circulation pump pumps the domestic hot water through the domestic hot water pipe, either continuously or on a time-controlled basis. This means that domestic hot water is available at the draw-off points.
Zones
Hybrid manager
If a heat pump and an additional boiler are connected, you can use the hybrid manager. If there is a heat demand, the hybrid manager picks the heat generator that is more costefficient. The hybrid manager decides which heat generator to operate based on the tariffs that are set in relation to the heat demand. To ensure that the heat pump and the boiler can work effectively and in synch with one another, the tariffs (→ Page 14) must be set correctly. If the tariffs are set incorrectly, this results in increased costs.
Frost protection function
The frost protection function protects the heating installation and flat from frost damage. The frost protection function monitors the outdoor temperature.
If the outdoor temperature
Preventing malfunctions
Avoiding moisture and mould damage
Conditions: Ventilation unit is connected
Identification plate
The identification plate is located inside the product and is not accessible from the outside.
Serial number
You can call up the serial number to the display under Menu → Information → Serial number. The 10-digit article number is located in the second line.
CE label
The CE label shows that the products comply with the basic requirements of the applicable directives as stated on the identification plate. The declaration of conformity can be viewed at the manufacturer’s site.
The product has two adjustment and display levels. The end user level contains information and setting options that you require as the end user.
End user level (→ Page 19)
The installer level is reserved for the competent person. It is protected by a code. Only competent persons may change any settings in the installer level.
Menu structure design
Selection level
Setting level
Soft key function for the selection buttons
Both selection buttons have a soft key function, i.e. different functions may be assigned to the selection buttons. If, for example, you press the left-hand selection button, the current function switches from Menu to Back.
The basic display appears:
Preferred zone in the basic display
If your heating installation has several zones, the competent person sets the zone whose values are to appear in the basic display.
Preferred operating mode in the basic display
If your heating installation is designed for two of the three operating modes (heating, cooling or ventilating), you can switch the basic display to the required operating mode. Setting the preferred display (→ Page 14)
Information in the basic display
The basic display shows the most important current settings and values for the heating installation. Various information may appear in the basic display. This depends on which operating mode you give preference to in the basic display and the mode that this operating mode is in.
Basic display for the Heating operating mode
Mode | Time periods | Symbol | Information field |
Auto | On | | Desired heating temp. appears: |
– The system control maintains the temper- ature at the desired level. | |||
Off | | ||
Day | |||
Empty line appears: | |||
– The system control does not request any heating energy. | |||
Set-back | |||
off | Empty line |
Basic display for the Cooling operating mode
Mode | Time periods | Symbol | Information field |
Auto | On | | Desired cooling temp. |
Off | | Empty line | |
Day | Desired cooling temp. | ||
off | Empty line |
Basic display for the Ventilation operating mode
Mode | Time periods | Symbol | Information field |
Auto | On | | Max. vent. stage |
Off | Max. vent. stage | ||
Day | Ventilation stage | ||
Set-back | Ventilation stage |
Basic display for the Manual cooling advanced function
Mode | Time periods | Information field |
Activated | On | Desired cooling temp. |
Off | Empty line |
Operating concept
The system control is operated using two selection buttons and a rotary knob. You can use the selection buttons to do the following:
You can use the rotary knob to do the following:
Using the rotary knob to make settings in the basic display
If the display shows the basic display, you can use the rotary knob to change the setting for the desired temperature or ventilation level. The setting that you change depends on selecting the preferred display in the basic display, the selected operating mode and the set mode for the operating mode.
Desired temperature in the Heating operating mode
Mode | Time periods | Effect |
Auto | On | Switch to another display view with the request: – Permanent change to the Day temp. heating – Change to the Day temp. heating for six hours |
Off | Direct change to the Set-back temp. heat. for six hours |
Mode | Time periods | Effect |
Day | Switch to another display view with the request: – Permanent change to the Day temp. heating – Change to the Day temp. heating for six hours | |
Set-back | Direct change to the Set-back temp. heat. for six hours | |
off | None |
Desired temperature in the Cooling operating mode
Mode | Time periods | Effect |
Auto | On | Direct permanent change to the Day temp. cooling |
Off | None | |
Day | Direct permanent change to the Day temp. cooling | |
off | None |
Ventilation level in the Ventilation operating mode
Mode | Time periods | Effect |
Auto | On | Direct permanent change to the Max. vent. stage: Day |
Off | Direct permanent change to the Max. vent. stge: Night | |
Day | Direct permanent change to the Max. vent. stage: Day | |
Set-back | Direct permanent change to the Max. vent. stge: Night |
Desired temperature in the Manual cooling advanced function
Mode | Time periods | Effect |
Activated | On | Direct permanent change to the Day temp. cooling |
Off | None |
Using the rotary knob to make settings with no effect You cannot influence the following advanced functions by turning the rotary knob:
Operating and display functions
Example, changing the display contrast
Reading the system status
Menu → Information → System status – Under System status, there is a list containing information that provides an overview of the current system status, and current settings that you can change there.
ZONE1
Ventilation
Display of energy consumption and energy yield
In the display and in the app that can also be used, the control displays values for the energy consumption and/or the energy yield. The control displays an estimation of the values for the installation. Among other things, the values are influenced by the following:
Consumption
Some components do not support the calculation of consumption, the total of which is shown on the display. In the instructions for the components, you can find out if and how the individual components determine the consumption.
You can use this function to read the total electrical consumption for heating in the last month.
Diagram: Reading the solar yield
Diagram: Reading the environmental yield
Diagram: Reading the electrical consumption
Diagram: Reading the fuel consumption
Diagram: Reading the heat recovery yield
Read competent person contact details
Menu → Information → Contact details – If the competent person entered their company name and telephone number when they installed the product, you can read this data under Contact details.
Reading the serial number and article number
Menu → Information → Serial number – You can use this function to read the product’s serial number. The article number is found in the second line.
Setting desired temperatures
This function is used to set the desired temperatures for the zone and hot water generation.
Zone
Heating
Cooling
Hot water generation
Menu → Desired temperatures → Domestic hot water – You can set the desired Domestic hot water temperature for the domestic hot water circuit. If a heat pump is connected and you have set the desired temperature to above 55 °C, it may be the case that it is the back-up boiler that predominantly takes on the task of supplying domestic hot water.
Setting the ventilation level
Time programme
Heating operating mode example: Time period for a day
You can specify the temperatures (Day temp. heating and Set-back temp. heat.) in the Setting the Desired temperatures (→ Page 11) function. You can specify the times for the time periods in the Setting time programmes Heating (→ Page 12) function.
Setting time programmes quickly
If, for example, you require different time periods for just one working day in the week, first set the times for the entire block Monday – Friday. Then set the different time period for the working day.
Setting the Heating time programme
Menu → Time programmes → ZONE1 – The time programmes are only effective for the Heating operating mode in automatic mode. Within the time periods, the system control brings the temperature of the connected rooms to the set desired temperature Day temp. heating. Outside of these time periods, the system control switches to the operating mode that the competent person has set: Eco or Set-back temp. heat.. If the competent person has left the factory setting Eco, the system control switches off the heating function. Setting the Heating operating mode. (→ Page 15)
Setting the Cooling time programme
Menu → Time programmes → ZONE1: Cooling – The time programmes are only effective in the Cooling mode and the Manual cooling advanced function. In each set time period, the desired temperature that you set in the Desired temperatures function applies. Within the time periods, the zone cools the living areas to the desired Day temp. cooling temperature. Outside this time period, there is no cooling.
Setting the domestic hot water generation time programme
Menu → Time programmes → DHW circuit – The time programmes are only effective for domestic hot water generation in automatic mode. In each set time period, the desired Domestic hot water temperature applies. At the end of a time period, the system control switches the domestic hot water generation off until the start of the next time period.
Setting the time programme Circulation
Menu → Time programmes → Circulation – The time programmes are only effective for circulation in Automatic mode. The set time periods determine the operating times for circulation. Within the time period, the circulation is switched on. Outside the time period, the circulation is switched off.
Setting the Ventilation time programme
Menu → Time programmes → Ventilation – The time programmes are only effective for ventilation in automatic mode. In each set time period, the ventilation level that you set in the Ventilation function applies. Within the time period, the system control regulates the ventilation unit to Max. vent. stage: Day as a maximum. Outside the time period, the system control regulates the ventilation unit to Max. vent. stge: Night as a maximum.
Setting the High tariff time programme
Menu → Time programmes → High tariff – You can use this function to set when the high tariff or the low tariff should be used to calculate the costs. Within the time period: For the high tariff Outside of the time period: For the low tariff The times of high tariff depend on your energy supply company. If the energy supply company only offers one tariff, you do not need to set any time periods. The cost for the electricity is calculated using one tariff. Setting costs (→ Page 14)
Days away from home scheduling
Day at home scheduling
Menu → Days at home scheduling – In the specified period, the heating installation works in the Automatic mode mode and uses the day settings for Sunday, which were set using the Time programmes function. At the end of the specified period, or if you cancel the function, the heating installation returns to the preset mode.
Select language
Menu → Basic settings → Language – You can use this function to change to the language that you want to appear in the display.
Setting your language
Setting the time
Activating the automatic or manual changeover to daylight saving time
Set display contrast
Menu → Basic settings → Display → Display contrast
– You can use this function to set the display contrast in relation to the brightness of the surroundings to ensure that the display is clearly legible.
Activating Button lock
Menu → Basic settings → Display → Button lock
– You can use this function to activate the button lock. After one minute of not pressing any button or operating the rotary knob, the button lock is active and you can no longer change any functions unintentionally. Each time you actuate the system control, the following message appears in the display Button lock active To unlock, press OK for 3 seconds. If you press and hold the OK button for three seconds, the basic display appears and you can change functions. The button lock becomes active again if you do not press any button or operate the rotary knob for one minute. To permanently remove the button lock, you must first release the button lock and then select the value off in the Button lock function.
Setting the preferred display
Menu → Basic settings → Display → Preferred display
You can use this function to choose whether you see the data for heating, cooling or ventilation in the basic display.
Setting costs
You must specify all tariffs in the unit of currency per kWh for the calculation to be correct. If the tariffs are in the unit of currency per m3 for you, request that your energy supply company provides the required tariffs in the unit of currency per kWh. If your energy supply company only offers one electricity tariff, enter the same value for the High-tariff elec. rate (→ Page 14) and Low-tariff elec. rate (→ Page 14) functions. Round the tariff data up or down to one decimal point. To establish the factor that is to be set, multiply the value by 10.
Example:
Costs | Factor to be set | |
Tariff for aux. heater (Gas, oil, electricity) | 11.3 currency units/kWh | 113 |
Low-tariff elec. rate (heat pump) | 14.5 currency units/kWh | 145 |
High-tariff elec. rate (heat pump) | 18.7 currency units/kWh | 187 |
Setting the tariff for the back-up boiler
Menu → Basic settings → Costs → Tariff for aux. heater – The hybrid manager can use this function to correctly calculate the costs for the back-up boiler. To do this, the hybrid manager requires the factor that is to be set. In order to enter the correct factor, you must request the tariff from your energy supply company and calculate the factor in accordance with the example
Setting the low-tariff electricity rate
Menu → Basic settings → Costs → Low-tariff elec. rate
The hybrid manager can use this function to correctly calculate the costs for the back-up boiler. To do this, the hybrid manager requires the factor that is to be set. In order to enter the correct factor, you must request the tariff from your energy supply company and calculate the factor in accordance with the example.
Setting the high-tariff electricity rate
Menu → Basic settings → Costs → High-tariff elec. rate
The hybrid manager can use this function to correctly calculate the costs for the back-up boiler. To do this, the hybrid manager requires the factor that is to be set. In order to enter the correct factor, you must request the tariff from your energy supply company and calculate the factor in accordance with the example.
Set offset room temperature
Menu → Basic settings → Offset → Room temperature
Set offset outdoor temperature
Menu → Basic settings → Offset → Outside temperature
The thermometer in the system control’s outdoor temperature sensor measures the outdoor temperature. You can use the offset to correct the measured temperature value.
Changing a zone name
Menu → Basic settings → Enter zone name
You can now modify the factory-specified zone names as you wish. The name is limited to 10 characters.
Activating Heat recovery
Menu → Basic settings → Ventilation → Heat recovery
The Heat recovery function is set to Auto. This means that an internal control system checks whether heat recovery makes sense, or whether the outdoor air can be guided directly into the living room. For more information, see the operating instructions for recoVAIR…/4 and later models. If you have selected Activate, heat recovery is used constantly.
Setting the room air humidity
Menu → Basic settings → Max. room air humidity
If the room air humidity exceeds the value set, a connected dehumidifier is activated. As soon as the value drops below the value that is set, the dehumidifier switches off again.
Resetting to default setting
Menu → Basic settings → Default setting → Everything –
While the system control is restoring the factory settings, Reset to default setting In progress is shown in the display. The installation assistant is then shown in the display; it must only be operated by a competent person.
Installer level
The Installer level is reserved for the competent person and is therefore protected by an access code. At this level, the competent person can implement the required settings.
The operating modes can be activated directly from any operating mode using the right-hand selection button Op. mode. If the heating installation is equipped with more than one zone, the activated operating mode only applies for the zone that was preset by the competent person. If more than one zone is activated, you can set a separate operating mode for each zone using the left-hand selection button Menu→ Basic settings. The path details given at the start of each operating mode description indicate how you reach this operating mode in the menu structure.
Setting the Heating operating mode
Setting the Cooling operating mode
Op. mode → Cooling Menu → Basic settings → Operating mode → ZONE1 → Cooling
Setting the Ventilation operating mode
The operating instructions for the ventilation unit explain how the ventilation unit works with the ventilation levels.
Day: The operating mode constantly controls the exchange of air using the value that you set in the Max. vent. stage: Day ventilation level.
Set-back: The operating mode constantly controls the exchange of air using the value that you set in the Max. vent. stge: Night ventilation level.
Setting the operating mode for domestic hot water generation
Op. mode → Domestic hot water
– You can use this function to specify how the heating installation should operate during domestic hot water generation. off: Domestic hot water generation is switched off and the frost protection function is activated.
Auto: The operating mode brings the domestic hot water generation to the desired temperature set for Domestic hot water in the time periods that you have set in the time programme. Day: The operating mode brings the domestic hot water generation to the desired temperature set for Domestic hot water, regardless of the time periods that you have set in the time programme.
Operating mode for circulation
The operating mode for circulation always corresponds to the operating mode for hot water. You cannot set a different operating mode.
Advanced functions
The advanced functions can be activated directly from any operating mode using the right-hand selection button Op. mode. If the heating installation is equipped with more than one zone, the activated advanced function only applies for the zone that was preset by the competent person. If more than one zone is activated, you can set a separate advanced function for each zone using the left-hand selection button Menu → Basic settings. The path details given at the start of each advanced function description indicate how you can access this advanced function in the menu structure.
Activating manual cooling
Op. mode → Manual cooling
– If the outdoor temperature is high, you can activate the Manual cooling advanced function. You define for how many days you want to activate the advanced function. If you activate Manual cooling, you cannot use the heating function at the same time. The Manual cooling function takes priority over the heating function. The setting applies for as long as the advanced function is active. The advanced function is deactivated if the days that are set have elapsed or if the outdoor temperature falls below 4 °C. If you want to set the temperature separately for more than one zone, you can set these temperatures using the Desired temperatures function.
Op. mode → 1 day at home Menu → Basic settings → Operating mode → ZONE1 → 1 day at home
– The 1 day at home advanced function activates the automatic mode in the operating mode Heating with the settings for the Sunday. The advanced function is automatically deactivated after 00:00 (midnight) or you can cancel the advanced function first. The heating installation then returns to the pre-set operating mode.
Activating 1 day away from home
Op. mode → 1 day away from home Menu → Basic settings → Operating mode → ZONE1 → 1 day away from home
– The 1 day away from home advanced function brings the room temperature to the desired Set-back temperature. Domestic hot water generation and circulation are switched off and the frost protection is activated. Ventilation is activated and works at the lowest ventilation level. The advanced function is automatically deactivated after 00:00 (midnight) or you can cancel the advanced function first. The heating installation then returns to the pre-set operating mode.
Activating Ventilation boost
Op. mode → Ventilation boost Menu → Basic settings → Operating mode → ZONE1 → Ventilation boost
This Ventilation boost advanced function switches the zone off for 30 minutes. The frost protection function is activated, and domestic hot water generation and circulation remain active. Ventilation is activated and works at the highest ventilation level. The advanced function is automatically deactivated after 30 minutes or you can cancel the advanced function first. The heating installation will then return to the pre-set operating mode.
Activating Party function
Op. mode → Party function Menu → Basic settings → Operating mode → ZONE1 → Party function – The advanced function regulates the room temperature to the desired Day temperature, the domestic hot water to the desired Domestic hot water temperature and the ventilation to ventilation level Max. vent. stage: Day in accordance with the set time periods. The circulation is activated. The advanced function is automatically deactivated after six hours or you can cancel the advanced function first. The heating installation will then return to the pre-set operating mode.
Activating Cylinder boost
Op. mode → Cylinder boost – The Cylinder boost advanced function heats the water in the domestic hot water cylinder until it reaches the set desired temperature Domestic hot water. The advanced function is active for one hour unless you cancel it sooner. The heating installation then returns to the preset operating mode.
Activating System OFF active
Maintenance message
To prevent the heating installation from breaking down and to prevent damage, you must pay attention to the maintenance message:
Fault message
Implementing the setting if the heat pump fails
If the fault message Restricted operation/ comfort protection Inactive appears on the display, the heat pump has failed and the system control enters limp home mode. The back-up boiler now supplies the heating installation with heating energy. During installation, the competent person has restricted the temperature for limp home mode. You can feel that the domestic hot water and heating are not becoming very hot. While you wait for the competent person to come, you can use the rotary knob to implement the following settings: Inactive: The system control works in limp home mode; heating and domestic hot water become moderately hot. Heating: The back-up boiler takes over the heating mode; the heating becomes hot, the domestic hot water is cold. DHW: The back-up boiler takes over the domestic hot water mode; the domestic hot water becomes hot, the heating is cold. DHW+heat.: The back-up boiler takes over the heating and domestic hot water mode; the heating and the domestic hot water become hot. The back-up boiler is not as efficient as the heat pump, meaning that using only the back-up boiler to generate heat is expensive. If you want to implement settings on the system control, click Back and the basic display appears in the display. After five minutes of no operation, the fault message appears again in the display.
Caring for the product
Decommissioning
Recycling and disposal
Guarantee and customer service
We only grant a Vaillant manufacturers warranty if a suitably qualified engineer has installed the system in accordance with Vaillant instructions. The system owner will be granted a warranty in accordance with the Vaillant terms and conditions. All requests for work during the guarantee period must be made to Vaillant Service Solutions.
Customer service
To ensure regular servicing, it is strongly recommended that arrangements are made for a Maintenance Agreement. Please contact Vaillant Service Solutions for further details: Telephone: 0330 100 3461
Technical data
On units with integrated weather compensators, including a room thermostat function that can be activated, the seasonal room-heating efficiency always includes the correction factor for controller technology class VI. The seasonal room-heating efficiency may deviate if this function is deactivated.
Operating mode | Setting | Default setting |
Operating mode | ||
Heating | off, Auto, Day, Set-back | Auto |
Cooling | off, Auto, Day | Auto |
Ventilation | Auto, Day, Set-back | Auto |
Domestic hot water | off, Auto, Day | Auto |
Advanced functions | ||
Manual cooling | active | – |
1 day at home | active | – |
1 day away from home | active | – |
Ventilation boost | active | – |
Party function | active | – |
Cylinder boost | active | – |
System OFF active | active | – |
END USERS
Setting level | Values | Unit | Increment, select | Default setting | |
Min. | Max. | ||||
Information → System status → | |||||
System —- | |||||
Fault status | Current value | No fault, Fault list | |||
Green IQ | Off, On | On | |||
Water pressure | Current value | bar | |||
System status | Current value | Standby, Heat. mode, Cool- ing, DHW | |||
Burner | Current value | On, off | |||
Collector temp. | Current value | ℃ | |||
Solar yield | Current value | kWh | |||
Reset solar yield | Yes, No | No | |||
Environmental yield | Current value | kWh | |||
Reset env.yield | Yes, No | No | |||
Curr. room air hum. | Current value | % | |||
Current dew point | Current value | ℃ | |||
triVAI | Current value | ||||
ZONE1 —- | |||||
Day temp. heating | 5 | 30 | ℃ | 0.5 | 20 |
Day temp. cooling | 15 | 30 | ℃ | 0.5 | 24 |
Set-back temp. heat. | 5 | 30 | ℃ | 0.5 | 15 |
Room temperature | Current value | ℃ | |||
Ventilation —- | |||||
Air quality sensor 1 | Current value | ppm |
Setting level | Values | Unit | Increment, select | Default setting | |
Min. | Max. | ||||
Air quality sensor 2 | Current value | ppm | |||
Exhaust air humidity | Current value | %rel | |||
Information → Consumption → Current month → | |||||
Heating —- | |||||
Electricity | Total value for the current month | kWh | |||
Fuel | Total value for the current month | kWh | |||
Hot water —- | |||||
Electricity | Total value for the current month | kWh | |||
Fuel | Total value for the current month | kWh | |||
Information → Consumption → Last month → | |||||
Heating —- | |||||
Electricity | Total value for the last month | kWh | |||
Fuel | Total value for the last month | kWh | |||
Hot water —- | |||||
Electricity | Total value since start- up | kWh | |||
Fuel | Total value since start- up | kWh | |||
Information → Consumption → History → | |||||
Heating —- | |||||
Electricity | Total value since start- up | kWh | |||
Fuel | Total value since start- up | kWh | |||
Hot water —- | |||||
Electricity | Total value since start- up | kWh | |||
Fuel | Total value since start- up | kWh | |||
Information → Solar yield → | |||||
Bar chart | Previous year to cur- rent year comparison | kWh/month | |||
Information → Environmental yield → | |||||
Bar chart | Previous year to cur- rent year comparison | kWh/month | |||
Information → Electrical consumption → | |||||
Bar chart | Previous year to cur- rent year comparison | kWh/month | |||
Information → Fuel consumption → | |||||
Bar chart | Previous year to cur- rent year comparison | kWh/month |
Setting level | Values | Unit | Increment, select | Default setting | |
Min. | Max. | ||||
Information → Heat recovery → | |||||
Bar chart | Previous year to cur- rent year comparison | kWh/month | |||
Information → Contact details → | |||||
Installer Phone number | Current values | ||||
Information → Serial number | |||||
Product number | Permanent value | ||||
Desired temperatures → ZONE1 → | |||||
Day temp. heating | 5 | 30 | ℃ | 0.5 | 20 |
Day temp. cooling | 15 | 30 | ℃ | 0.5 | 24 |
Set-back temp. heat. | 5 | 30 | ℃ | 0.5 | 15 |
Desired temperatures → Domestic hot water → | |||||
Domestic hot water | 35 | 70 | ℃ | 1 | 60 |
Ventilation stage → | |||||
Max. vent. stage: Day | Depending on the ventilation unit | 1 | Depending on the ventilation unit | ||
Max. vent. stge: Night | Depending on the ventilation unit | 1 | Depending on the ventilation unit | ||
Time programmes → ZONE1 (Heating) → Time programmes → ZONE1: Cooling → Time programmes → Circulation → Time programmes → Ventilation → | |||||
Individual days and blocks | Monday, Tuesday, Wednes- day, Thursday, Friday, Sat- urday, Sunday and Monday – Friday, Saturday – Sunday, Monday – Sunday | Mo – Fr: 06:00- 22:00 Sa: 07:30-23:30 Su: 07:30-22:00 | |||
Period 1: Start – End Period 2: Start – End Period 3: Start – End | 00:00 | 24:00 | h:min | 00:10 | |
Time programmes → Domestic hot water → | |||||
Individual days and blocks | Monday, Tuesday, Wednes- day, Thursday, Friday, Sat- urday, Sunday and Monday – Friday, Saturday – Sunday, Monday – Sunday | Mo to Fr: 05:30- 22:00 Sa: 07:00-23:30 Su: 07.00-22.00 | |||
Period 1: Start – End Period 2: Start – End Period 3: Start – End | 00:00 | 24:00 | h:min | 00:10 | |
Time programmes → High tariff → | |||||
Individual days and blocks | Monday, Tuesday, Wednes- day, Thursday, Friday, Sat- urday, Sunday and Monday – Friday, Saturday – Sunday, Monday – Sunday | Mo – Su: 11:00- 13:00 |
Setting level | Values | Unit | Increment, select | Default setting | |
Min. | Max. | ||||
Period 1: Start – End Period 2: Start – End Period 3: Start – End | 00:00 | 24:00 | h:min | 00:10 | Mo – Su: 11:00- 13:00 |
Days away from home scheduling → | |||||
Start | 01.01.01 | 31.12.99 | dd.mm.yy | Day.Month.Year | 01.01.14 |
End | 01.01.01 | 31.12.99 | dd.mm.yy | Day.Month.Year | 01.01.14 |
Temperature | 5 | 30 | ℃ | 1 | 15 |
Days at home scheduling → | |||||
Start | 01.01.01 | 31.12.99 | dd.mm.yy | Day.Month.Year | 01.01.14 |
End | 01.01.01 | 31.12.99 | dd.mm.yy | Day.Month.Year | 01.01.14 |
Basic settings → Language → | |||||
Selectable language | English | ||||
Basic settings → Date/time → | |||||
Date | 01.01.01 | 31.12.99 | dd.mm.yy | Day.Month.Year | 01.01.15 |
Time | 00:00 | 23:59 | h:min | 00:10 | 08:00 |
Daylight saving time | Manual, Auto | Manual | |||
Basic settings → Display → | |||||
Display contrast | 1 | 15 | 1 | 9 | |
Button lock | off, On | off | |||
Preferred display | Heating, Cooling, Vent. | Heating | |||
Basic settings → Costs → | |||||
Tariff for aux. heater | 1 | 999 | 1 | 12 | |
Low-tariff elec. rate | 1 | 999 | 1 | 16 | |
High-tariff elec. rate | 1 | 999 | 1 | 20 | |
Basic settings → Offset → | |||||
Room temperature | -3.0 | 3.0 | K | 0.5 | 0.0 |
Outside temperature | -3.0 | 3.0 | K | 0.5 | 0.0 |
Basic settings → Operating mode → ZONE1 → | |||||
Heating | off, Auto, Day, Set-back | Auto | |||
Cooling | off, Auto, Day | Auto | |||
1 day at home | Active, Not active | Not active | |||
1 day away from home | Active, Not active | Not active | |||
Ventilation boost | Active, Not active | Not active | |||
Party function | Active, Not active | Not active | |||
Basic settings → Enter zone name → | |||||
ZONE1 | 1 | 10 | Let- ter/number | A to Z, 0 to 9, space | ZONE1 |
Basic settings → Ventilation → | |||||
Heat recovery | Auto, Activate, off | Auto |
Setting level | Values | Unit | Increment, select | Default setting | |
Min. | Max. | ||||
Basic settings → Max. room air humidity → | |||||
Max. room air hum. | 30 | 70 | %rel | 1 | 40 |
Basic settings → Default setting → | |||||
Time programmes | Yes, No | No | |||
Everything | Yes, No | No | |||
Installer level → | |||||
Enter code | 000 | 999 | 1 | 000 |
Troubleshooting
Symptom | Possible cause | Measure |
Display remains dark | Software error | 1. Switch off the mains switch on all heat generators for approx. 1 minute and then switch them on again. 2. If the fault persists, inform the competent person. |
No changes in the display when the rotary knob is turned | Software error | 1. Switch off the mains switch on all heat generators for approx. 1 minute and then switch them on again. 2. If the fault persists, inform the competent person. |
No changes in the display when the selection buttons are pressed | Software error | 1. Switch off the mains switch on all heat generators for approx. 1 minute and then switch them on again. 2. If the fault persists, inform the competent person. |
Display view: Button lock act- ive To unlock, press OK for 3 seconds, it is not possible to change the settings or values | Button lock is active | 1. If you would like to change any of the values, follow the in- structions on the display. 2. Also read through the Button lock Activate (→ Page 13) function. |
Display view: Restricted opera- tion/ comfort protection, insuf- ficient heating up of the heating and the domestic hot water | Heat pump does not work | 1. Inform the competent person. 2. Select the setting for limp home mode until the competent person arrives. 3. To do this, read through the Implementing the setting when the heat pump fails (→ Page 17) function. |
Display view: Fault F. Fault: Heat generator 1, the specific fault code (e.g. F.33) and the specific heat generator appear behind F. in the display | Heat generator faults | 1. Carry out a Reset fault message (→ Page 17). 2. If the fault persists, inform the competent person. |
Maintenance messages
The maintenance message Service heat pump 1 is an example of a maintenance message that may appear for heat pumps 1 to 7. The maintenance message Service heat generator 1 is an example of a maintenance message that may appear for heat generators 1 to 7.
# | Message | Description | Maintenance work | Interval | |
1 | Service heat pump 1 | The heat pump requires main- tenance work. | Refer to the operating instruc- tions of the relevant heat pump for information on the mainten- ance work required | See the operating instructions for the heat pump | |
2 | Service heat generator 1 | The heat generator requires maintenance work. | Refer to the operating instruc- tions of the relevant heat gener- ator for information on the main- tenance work required | See the operating instructions for the heat generator | |
3 | Low water pres- sure | The water pressure is too low in the heating installation. | Refer to the operating instruc- tions for the relevant heat gen- erator for information on filling with water | See the operating instructions for the heat generator |
# | Message | Description | Maintenance work | Interval | |
4 | Service ventila- tion unit | The ventilation unit requires maintenance work. | Refer to the operating instruc- tions of the ventilation unit for information on the maintenance work required | See the operating instructions for the ventilation unit | |
5 | Service date Next service on | The competent person has entered a date on which main- tenance is due for the heating installation. | Inform the competent person if maintenance work is required | Date entered in the system con- trol |
Supplier
DOWNLOAD MANUALS:
Vaillant VRC 700-6 Programmable Thermostat Operating Instructions
Vaillant VRC 700/6 Programmable Thermostat Operating Instructions
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…