FUNCTION
ORDERING PART NUMBERS
PART NUMBERS | OPERATING VOLTAGES | APPLICATIONS | VALVE TYPE | ADDON FUNCTIONS |
TX892OF220-V2E | 85-240VAC | 2-PIPE | ON-OFF VALVE | EXTERNAL SENSOR |
TX892OF220-V2K | 85-240VAC | 2-PIPE | ON-OFF VALVE | HOTEL KEYCARD |
TX892OF024-V2 | 24VAC | 2-PIPE | ON-OFF VALVE | N/A |
ABBREVIATION
CASING/COVER COLOR | |
BLACK | B |
WHITE | W |
BACKLIGHT COLOR | |
Sky Blue backlight + Black letters (TN LCD) |
SB |
ON-OFF VALVE /COMPRESSOR CONTROL
The thermostat acquires the room temperature via its integrated sensor and maintains the set-point by simple on-off output
POWER ON OR OFF
Pressing the POWER button
INCREASE / DECREASE
In the ON state, press UP
HEAT/COOL/VENT
Pressing the MODE button M to select heat
TEMPERATURE DISPLAY
Either room temperature or set-point is displayed
Noted: When pressing UP
COMFORT MODE
In the comfort mode, the set point can be changed by pressing UP
FAN OPERATION
Fan can be selected as manual or automatic 3-speed operation. In manual mode, the fan will be switched to the selected speed via control output Gh,Gm,Gl (by pressing FAN button
KEY LOCK
The default status of “Key lock” is all keys available and it can be changed in ISU mode. Key lock function includes the following settings: All keys are available (Default) Mode button is locked out. Fan and Mode button are locked out. All buttons are locked.
ISU CODE | DESCRIPTION | POSSIBLE OPTIONS |
1 | SYSTEM TYPE | 0 HEAT ONLY 1COOL ONLY 2 TWO PIPES 1H1C MANUAL(DEFAULT) |
2 | TEMPERATURE UNIT | F : ° F C : ° C(DEFAULT) |
3 | FAN CONTROL TYPE | AO: AUTO ONLY CO: CONSTANT ONLY BO : BOTH(DEFAULT) |
4 | KEYPAD LOCKOUT | 0: ALL KEYS ARE AVAILABLE (DEFAULT) 1: THE MODE BUTTON IS LOCKED OUT, AFTER LOCKED OUT, WHEN YOU PRESS MODE KEY, IT WILL DISPLAY “LOC” 2: FAN AND MODE BUTTONS ARE LOCKED OUT, AFTER LOCKED OUT,WHEN YOU PRESS FAN OR MODE BUTTON, IT WILL DISPLAY” LOC” 3: ALL BUTTONS ARE LOCKED, AFTER LOCKED OUT WHEN YOU PRESS ANY KEYS, IT WILL DISPLAY” LOC” |
5 | DISPLAY TEMP. ADJUSTMENT | -9°C/ °F ~ + 9°C/°F |
6 | RESERVED FOR ADDITIONAL ISU SETTINGS. | |
7 | RESERVED FOR ADDITIONAL ISU SETTINGS. | |
8 | SENSOR SELECTION | IN : INTERNAL SENSOR, OU : EXTERNAL SENSOR, IF CHOOSING OU EXTERNAL SENSOR, THE ROOM CARD FUNCTION WILL NOT BE AVAILABLE (DEFAULT IN) |
9 | BACK-LIGHT TIME SETTING | 10-90 SECONDS(DEFAULT 30 SEC., USER CAN ADJUST BACK-LIGHT TIME ACCORDING TO ACTUAL DEMANDS) |
10 | RESERVED FOR ADDITIONAL ISU SETTINGS. | |
NO | TERMINALS | DESCRIPTION | NO | TERMINALS | DESCRIPTION | NO | TERMINALS | DESCRIPTION | ||
1 | L | LIVE IN | 1 | L | LIVE IN | 1 | R | 24V ACTIVE | ||
2 | FH | HIGH SPEED FAN | 2 | FH | HIGH SPEED FAN | 2 | LINE | 220V LINE FOR 220V FAN | ||
3 | FM | MEDIUM SPEED FAN | 3 | FM | MEDIUM SPEED FAN | 3 | FH | HIGH SPEED FAN | ||
4 | FL | LOW SPEED FAN | 4 | FL | LOW SPEED FAN | 4 | FM | MEDIUM SPEED FAN | ||
5 | NO | VALVE OPEN | 5 | NO | VALVE OPEN | 5 | FL | LOW SPEED FAN | ||
6 | NC | VALVE CLOSE | 6 | NC | VALVE CLOSE | 6 | C | 24V NEUTRAL | ||
7 | N | NEUTRAL IN | 7 | N | NEUTRAL IN | 7 | NO | VALVE OPEN | ||
8 | COM | COM FOR EXTERNAL SENSOR | 8 | COM | COM FOR KEY CARD | 8 | NC | VALVE CLOSE | ||
9 | AI | EXTERNAL SENSOR | 9 | DI | KEY CARD | 9 |
TERMINAL POWER BOX
*wiring is subject to change without notice based on addons
NOTE
INSTALLATION AND COMMISSIONING
Office:
DOWNLOAD MANUALS:
TRUEWAY TX892 Room Digital Thermostat User Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…