FUNCTION
PART NUMBERS | OPERATING VOLTAGES | APPLICATIONS | VALVE TYPE | EXT.SENSOR | WIFI CONTROL THROUGH APP |
TX1000 OF220-V2 1CEW | 85-240VAC | 2-PIPE/ SINGLE STAGE | ON-OFF VALVE / COMPRESSOR | ||
TX1000 OF220-V2EW | 85-240VAC | 2-PIPE | ON-OFF VALVE | ||
TX1000 OF024-V21CW | 24VAC | 2-PIPE | ON-OFF VALVE / COMPRESSOR |
ABBREVIATION
CASING/COVER COLOR | |
BLACK | B |
WHITE | W |
BACKLIGHT COLOR | |
Sky Blue backlight + Black letters(TN LCD) | SB |
Black backlight + White letters (VA LCD) | BW |
ON-OFF VALVE /COMPRESSOR CONTROL
The thermostat acquires the room temperature via its integrated sensor and maintains the set-point by simple on-off output
POWER ON OR OFF
Pressing the POWER button
INCREASE / DECREASE
In the ON state, press
HEAT/COOL/VENT
Pressing the MODE button
FAN OPERATION
The fan can be selected as manual or automatic 3-speed operation. In manual mode, the fan will be switched to the selected speed via control output Gh, Gm, Gl (by pressing the FAN button
TEMPERATURE DISPLAY
Both the room temperature and the set point are displayed
COMFORT MODE
In the comfort mode, the set point can be changed by pressing
KEY LOCK
The default status of “Key lock” is all keys available and it can be changed in ISU mode. Key lock function includes the following settings: All keys are available (Default) Mode button is locked out. The fan and Mode buttons are locked out. All buttons are locked.
ENERGY SAVING MODE
By pressing the MODE button
FREEZE PROTECTION MODE
Freeze protection can be disabled (default) or enabled via ISU mode. If freeze protection is enabled ( it is not available in the cooling only application) and the thermostat is in OFF mode while the room temperature is below 6 °C, the thermostat will open the heating device before the temperature rises to 8 °C
TIME SETTING
In ON/OFF states, press
TO SELECT MANUAL AND PROGRAMMABLE
In the thermostat ON status, Press
ADJUSTING OF WEEKLY PROGRAMMABLE
After selecting programmable mode, press
Setting sequence when enter program setting
Workdays 1st period time adjusting -> temperature adjusting -> 2nd period time adjusting -> temperature adjusting……6th period time adjusting -> temperature adjusting -> holidays 1st period time adjusting -> temperature adjusting -> 2nd period time adjusting -> temperature adjusting
SETUP FUNCTION SETTINGS AND OPTIONS
ISU CODE | DESCRIPTION | POSSIBLE OPTIONS | |
1 |
S YS TEM TYPE | 0 HE AT ON LY 1 COOL ON LY 2 T WO PIPES 1H1C MANUAL(DE F AULT) | |
2 | TEMPERATURE UNIT | F : C : | ° F ° C(DE F AULT) |
3 |
F AN CONTROL TYPE | AO : CO : BO : | AUTO ON LY CON S TANT ON LY B OTH(DE F AULT) |
4 |
KEY PAD LOCK OUT | 0 : 1 : 2 : 3 : | ALL KE YS ARE AVAILABLE (DE F AULT) MODE BUT TON IS LOCKED OUT F AN AND MODE BUT TON ARE LOCKED OUT ALL BUT TONS ARE LOCKED |
5 |
REM OTE SET BA CK ENABLE METHOD | NO : NC : BU : | HOTEL C ARD NO HOTEL C ARD NC BUT TON (DE F AULT) |
6 | FREEZE PROTECTION | OF : ON : | DIS ABLED(DE F AULT) ENABLED |
7 | DISPLAY TEMP. ADJUSTMENT | -9˚C~+9˚C~(-9˚F~+9˚F)DEFAULT IS 0˚C/0˚F | |
8 | REMOTE SETBACK HEATING SET-POINT | RANGE 10-21°C DEFAULT 18 ° C(RANGE 50-70°F DEFAULT 64°F) | |
9 | REMOTE SETBACK COOLING SET-POINT | RANGE 22-32°C DEFAULT 26 ° C(RANGE 72-90°F DEFAULT 79°F) |
10 | RESERVED FOR ADDITIONAL ISU SETTINGS | |
11 | RESERVED FOR ADDITIONAL ISU SETTINGS | |
12 | RESERVED FOR ADDITIONAL ISU SETTINGS | |
13 |
SENSOR SELECTION | IN : INTERNAL SENSOR, OU: EXTERNAL SENSOR, IF CHOOSING EXTERNAL SENSOR, THE ROOM CARD FUNCTION WILL NOT BE AVAILABLE, DEFAULT IS IN |
14 | BEE SOUND SETTING | ON: ON, OF: OFF, DEFAULT IS OF |
15 |
PROGRAM SETTING | 0: 5 WORKING DAYS AND 2 DAYS HOLIDAY A WEEK, 1: 6 WORKING DAYS AND 1 DAY HOLIDAY A WEEK, 2: 7 WORKING DAYS A WEEK, 3: CLOSE PROGRAM SCHEDULE ,DEFAULT IS 0 |
16 |
COMPRESSOR OFF TIME DELAY SETTING | RANGE 0-4 MINUTES, IF SETTING VALUE IS 0, WITHOUT DELAY, THIS IS FOR SIMPLE ON-OFF VALVE CONTROL, COMPRESSOR FUNCTION IS NOT AVAILABLE IF SETTING VALUE IS 1-4,THIS IS FOR COMPRESSOR FUNCTION, WHEN SETTING IS 1, WITH 1 MINUTE OFF DELAY FOR COMPRESSOR CONTROL. |
17 |
FAN STOP/RUN SETTINGS | LO: FAN WILL BE SWITCHED TO LOW SPEED WHEN ROOM TEMP. REACHES TO SET-POINT&VALVE TURNS OFF OF: FAN WILL BE SWITCHED OFF WHEN ROOM TEMP. REACHES TO SET-POINT& VALVE TURNS OFF, DEFAULT IS OF |
18 |
ON / OFF BACK-LIGHT SETTING | OF: OFF, THE BACK-LIGHT WILL BE OFF AFTER 30 SECONDS IF NONE KEY PRESS ON: ON, THE BACK-LIGHT WILL BE ON ALWAYS EVEN NONE KEY PRESS, DEFAULT IS OF |
19 |
ON / OFF MEMORY SETTING | OF: OFF USER SETTING WILL NOT BE KEPT WHEN POWER OFF (WHILE ELECTRIFIED, THE THERMOSTAT WILL BE OFF) SU: ON, USER SETTING WILL BE KEPT WHEN POWER OFF (WHILE ELECTRIFIED, THE THERMOSTAT WILL BE ON), DEFAULT IS OF |
20 |
BACK-LIGHT SETTINGS | 10-60 SECONDS(DEFAULT 30 SEC.,USER CAN ADJUST BACK-LIGHT TIME ACCORDING TO ACTUAL DEMANDS) |
21 | RESERVED FOR ADDITIONAL ISU SETTINGS | |
22 | RESERVED FOR ADDITIONAL ISU SETTINGS | |
23 | RESERVED FOR ADDITIONAL ISU SETTINGS | |
24 | RESERVED FOR ADDITIONAL ISU SETTINGS | |
25 | RESERVED FOR ADDITIONAL ISU SETTINGS | |
26 |
RESET TO DEFAULTS | THIS FUNCTION IS RESETTING ALL ISU SETTINGS TO FACTORY DEFAULTS, OPERATION: PRESS “ ” 0>1>2>3>4, THEN PRESS “ ” 4>3>2 AND PRESS “ ” TO CONFIRM DEFAULT: 0 |
Before using your Wi-Fi thermostat for the first time you must configure the wifi signal and setting through your smartphone or tablet. This will allow communications between your connected devices
STEP 1 DOWNLOAD YOUR APP
For IOS devices, search true way controls in Apple Store and download. Alternatively, scan the relevant QR code here (fig 1-2) For Android devices, search trueway controls in Google Play and download. Alternatively, scan the relevant QR code here (fig 1-3)
STEP 2 REGISTER YOUR ACCOUNT
Open the app Trueway controls, and you will get a piece of notification F Click “Allow” and “Continue” to go into the page of registration. For registering for the first time on the signup page input the email ID /Password and reconfirm the password then continue for getting a verification code. Already registered users can sign
STEP 3 ADDING THE DEVICE AND CONNECT YOUR WIFI SIGNAL
After the verification appears for adding a new device, Tap the button to add a new device. You will get a request for allow a true way to access the device location click “Allow” to continue and select the desired product. The next step is to assign the network of the current location. Access our Network and enter the password and thus the app assigns to Wifi network
STEP 4 SETTING UP AND CONNECTING THE THERMOSTAT
After the wifi network is assigned to your app proceed to reset the Thermostat which is installed in the wall. When the Thermostat is in an OFF state, please press button “M” and “ ” arrows for 3 seconds to enter the network status query. After 3 seconds selection mode appears and press “M” for selection of “AP’and “SA” mode. For easy access “SA” mode is advisable. Select “SA” mode and press the fan button for confirmation. Once the wifi module is confirmed “SA” mode stops flashing and only the wifi icon will continue flashing. “CL” mode will be displayed after wifi is connected to the cloud. Confirm the sequence by tick box and continue. refer
The app starts to scan for finding the device Fig 4-2. Once the connection is made device will be discovered and displayed on the page, the device found in and complete the setup by assigning the preferred room eg : living room, bedroom, office room, common area, etc.
STEP 5 ASSIGNING PLACE & ROOM
Once you found the device you can assign the place. Different places can create as per your choice Like Offices, homes, Gyms, and garages, or create custom names as per your requirement. On Each place, you can arrange according to the name of the room like living room, bedroom, master bedroom, or custom name of room. Any number of rooms can add and assign thermostats of the same network
After setting up you will launch on the home screen. Our home screen is designed with a user-friendly Interface. Start with the power button which is placed top right side of screen by clicking the Power button. The power icon will be displayed largely in the center of the screen and the thermostat turn to the ON position. Room temperature is displayed on the center of dial and set temperature is below the dial. Also provide a plus and minus button to adjust the set temperature. Fan button.lock/unlock buttons are arranged visibly.
Power ON/OFF button
Select the power button on the top right.Large display power button in red color will pop up in the center. By clicking the power button ON the button will be changed to green color.
Fan Controls
When you select fan icon on the dashboard, an interactive fan button will pop up and a realistic fan blade with motion will be displayed. All three speeds are indicated on the dial and on the center a moving fan will rotate as per your selection. User can found in anticlockwise Low, medium, High and auto Users can also view the fan status below the fan blade, Low, medium,high and auto will be written Between (+ )plus and (-)minus symbols.User can tab in the dial and in the Plus/minus button for changing the Fan position function.
Lock/Unlock
The lock and Unlock button can access from the home screen with lock in red coloring and unlock in greening
How to set the temperature in our smart app
There is two ways of setting the desired temperature for our comfort. The first one is by taking the red indicator In the dial, moving clockwise to increase and moving anti-clockwise to decrease the temperature, alternatively
pressing the +plus or –minus button below the dial.The set temperature is displayed between +plus and –minus The large numeric in the middle of the dial is the current room temperature with degree or Fahrenheit as per choice Our smart app is designed with two types of settings one is the App setting and other one is device setting. App settings consist of Manage places, temperature scale, Ambience selection, Language selection Connected to network, Privacy policy, help & support, and finally logout
In the device setting following operations and selections can be easily made according to user requirements
Mode selection- user can tab for three types of modes
Mode is displayed in the home screen below room temperature in home screen
Scheduling Program 7 days 6 period
The user can schedule their program of operation throughout the week in 6-period of intervals. In Add New Taskbar user can set the temperature/Switch off by giving the task name, and selection Day, and Time by saving. Weekend device turn-off setting can be done in scheduled programming
Shared users
The user can share the device with friends and family members by inputting a registered email ID and Can create a group. Select “Shared users” in the device setting. The sharing page will open Fig 12-1 Add the email ID of members who wants to share .you can share multiple users for accessing the thermostat.
VAV/FCU
Air-conditioning types VAV(Variable Air volume) and FCU (Fan coil unit) can be selected on the device setting. If you select VAV all the fan keys in the app will be muted as VAV does not have Fan controls in the system. Whereas for FCU all key will be operational
TERMINAL POWER BOX
*wiring is subject to change without notice based on addons
NOTE:
INSTALLATION AND COMMISSIONING
IF… | THEN… |
Heating system does not turn on | Set the mode to Heat by pressing the Mode button. Wait five minutes for the heating system to respond. |
Cooling system does not turn on | Set the mode to Cool by pressing the Mode button. Wait five minutes for the cooling system to respond. |
The fan does n’t work | Ao : Auto Onlyconsectetuer Co : Constant Only bo : Both(Default) adipiscing elit, |
The Mode button does not work | Check whether the Fan mode is set to Auto Check whether the heating or cooling system works well. Check whether the keypad is loc ked out (ISU mode item 4) |
The Fan button does not work | Check whether the system is working in energy saving mode. Check whether the thermostat is off. Check whether the key pad is locked out (ISU mode item 4) |
The Up or Down button does not work | Check whether the system is working in energy saving mode. Check whether the thermostat is off. Check whether the keypad is locked out (ISU mode item 4) |
DOWNLOAD MANUALS:
TRUEWAY TX1000 Touch Screen Thermostat OPERATION INSTRUCTION
TRUEWAY TX1000 Touch Screen Thermostat OPERATION INSTRUCTION
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…