Compatible With
Please read carefully before proceeding with the installation. Your failure to follow any attached instructions or operating parameters may lead to the product’s failure.
It is your responsibility to ensure that this thermostat is safely installed according to all applicable codes and standards. tekmar® is not responsible for damages resulting from improper installation and/or maintenance.
NOTICE
Do not attempt to service the thermostat. There are no user-serviceable parts inside the thermostat. Attempting to do so voids the warranty.
Preparation Tools Required
Materials Required
Thermostat Location
Consider the following:
Remove the old thermostat
If more than 2 wires are present, identify the R & C wires for use when connecting the Thermostat. Additional wires should be secured in a way that prevents them from touching the circuit board or terminals on the thermostat after the R & C wires are connected.
Mount thermostat base to wall
Remove the back plate from the thermostat.
Secure the thermostat back plate to a 2 x 4″ electrical box with machine screws or to drywall using wood screws with wall anchors.
If the wall has damage extending beyond the width of the Thermostat, place the wall plate trim behind the back plate.
Wiring the Thermostat
Connect the 2 wires from the old thermostat to the terminals on the back of the Thermostat. This connection is not polarity sensitive.
Attach the thermostat to back plate
Align the 2 notches at the top of the base plate with the holes on the top of the thermostat then rotate on the hinge point down to close.
Mounting the HVAC Interface Module
Locate the HVAC Interface Module so that it can connect to the other end of the existing wire from the thermostat. After removing the cover, secure the HVAC Interface Module to the wall, the HVAC equipment chassis or HVAC plenum using the holes at the top and bottom of the module. Wiring to the module enters from opening on the sides or the back. Refer to the diagrams on pages 6 to 11 for wiring details.
Replace the Cover
Push the HVAC Interface Module Cover towards the base. Top and bottom clips hold the cover in place.
This illustration shows various equipment connected to the HVAC Interface Module. Other equipment may be included in your application.
Conventional systems:
The HVAC Interface Module includes three relay power jumper connectors. These are used to provide power between terminals when necessary.
1-Stage Heat and 1-Stage Cooling with Fan
Up to 2-Stage Furnace and 2-Stage Air Conditioner
Up to 2-Stage Hydronic Boiler and 2-Stage Air Conditioner
Up to 2-Stage Heat Pump with Auxiliary Heat
The thermostat operates high cost electric resistance heat when the heat pump is unable to meet the building heating load.
Up to 2-Stage Heat Pump with 2-Stage Dual Fuel
The thermostat operates the heat pump when the outdoor air temperature is above the balance point setting and switches to the furnace when below.
Dehumidification using a DX Coil
The thermostat operates the cooling system and runs the system fan at low speed to dehumidify the air.
Humidifier
The thermostat operates a humidifier to increase relative humidity.
HRV/ERV Ventilator
The Heat Recovery Ventilator (HRV) or Energy Recovery Ventilator indoor air quality and recovers heat from exhaust air.
Essential Settings:
Outdoor Sensor
When the location of the thermostat is not ideal for accurate temperature and humidity measurement, an optional room sensor can be installed in a better location. The 086 mounts flush to a wall, blending in with the room decor.
Watts FloodSafe® Water Detector Shutoff
The Watts FloodSafe Water Detector Shutoff LFWDS prevents catastrophic water damage in the event of a water heater leak. The thermostat provides alert notification on the screen in the event that the FloodSafe Water Detector Shutoff LFWDS detects a water and shuts off the supply line to the water heater.
Restore power to the connected equipment. Once energized, the Thermostat will display the home screen.
Symbols
Away
Schedule
Display
Setting | Range | Default |
TEMPERATURE UNITS Select °F or °C . | °F or °C | °F |
ENERGY USE View the number of hours the heating or cooling has operated either daily or monthly . | 0 to 24 (daily) 0 to 744 (monthly) | 0 hours |
Setting | Range | Default |
BRIGHTNESS ACTIVE Select the brightness when touching the screen . | 30 to 100% | 100% |
BRIGHTNESS INACTIVE Select the brightness when not in use . | Off, 30 to 100% | 50% |
BACKGROUND Select the background color . | Light, Blue, Night, Latte, Espresso |
Blue |
LANGUAGE Select the language . | English, Español, Français | English |
SCREEN CLEAN Locks screen for 10 seconds to allow cleaning . | N/A | N/A |
INACTIVE TIME DISPLAY Select if the time is visible when the display is inactive . | Off or On | On |
INACTIVE HUMIDITY DISPLAY Select if the humidity is visible when the display is inactive . | Off or On | Off |
INACTIVE OUTDOOR DISPLAY Select if the outdoor temperature is visible when the display is inactive . Requires Outdoor Sensor 070 . | Off or On | Off |
Time
Setting | Range | Default |
TIME FORMAT Select the time format . | 12 or 24 hour | 12 hour |
DAYLIGHT SAVING TIME Select if Daylight Savings Time is used in location . | Off, On | On |
Fan
Setup
The Setup menu contains seven sub-menus that determine how the thermostat operates.
Setup – Toolbox
Setting | Range | Default |
ERROR Displays any error messages . | N/A | N/A |
ACCESS LEVEL Select between user and installer access levels . User access level restricts access in the Setup Menu . | User, Installer | Installer |
STATUS The current status of warm weather shut down, cold weather shut down and each of the relays . | Early Start, WWSD, CWSD, W1, W2, Y1, Y2, G, Acc1, Acc2 |
N/A |
SOFTWARE VERSION Display the software version . | N/A | N/A |
LOAD DEFAULTS All settings are returned to factory defaults . | Yes, No | No |
CALIBRATE TOUCHSCREEN Recalibrate the screen after loading factory defaults . | N/A | N/A |
Setup – Temp
Setting | Range | Default |
Screen Page 1 | ||
FLOOR MIN: Select the floor temperature minimum . Applies when there is both floor and an air sensors and when no schedule is set . | Off, 40 to 95°F Off, 4 .5 to 35 .0°C | Off |
HEAT TO AWAY Select the heating temperature when away . | Off, 40 to 95°F Off, 4 .5 to 35 .0°C | 62°F 16 .5°C |
HEAT TO MIN LIMIT Select the minimum heating temperature limit . | Off, 40 to 95°F Off, 4 .5 to 35 .0°C | Off |
HEAT TO MAX LIMIT Select the maximum heating temperature limit . | Off, 40 to 95°F Off, 4 .5 to 35 .0°C | Off |
COOL TO AWAY Select the cooling temperature when away . | Off, 40 to 100°F Off, 4 .5 to 38 .0°C | Off |
COOL TO MIN LIMIT Select the minimum cooling temperature limit . | Off, 40 to 100°F Off, 4 .5 to 38 .0°C | Off |
COOL TO MAX LIMIT Select the maximum cooling temperature limit . | Off, 40 to 100°F Off, 4 .5 to 38 .0°C | Off |
Screen Page 2 | ||
FLOOR MIN – WAKE Select the floor temperature while in the wake schedule . Applies when there is both a floor and an air sensor . | Off, 40 to 95°F Off, 4 .5 to 35 .0°C | Off |
FLOOR MIN – LEAVE Select the floor temperature while in the leave schedule . Applies when there is both a floor and an air sensor . | Off, 40 to 95°F Off, 4 .5 to 35 .0°C | Off |
FLOOR MIN – RETURN Select the floor temperature while in the return schedule . Applies when there is both a floor and an air sensor . | Off, 40 to 95°F Off, 4 .5 to 35 .0°C | Off |
FLOOR MIN – SLEEP Select the floor temperature while in the sleep schedule . Applies when there is both a floor and an air sensor . | Off, 40 to 95°F Off, 4 .5 to 35 .0°C | Off |
FLOOR MIN – AWAY Select the floor temperature while in away . Applies when there is both a floor and an air sensor . | Off, 40 to 95°F Off, 4 .5 to 35 .0°C | Off |
Screen Page 3 | ||
FLOOR MAX Select the maximum floor temperature . This protects the floor covering from over heating . Applies when there is a floor sensor . | Off, 40 to 95°F Off, 4 .5 to 35 .0°C | Off |
WARM WEATHER SHUT DOWN Select the outdoor temperature at which the heating is shut off . | Off, 40 to 100°F Off, 4 .5 to 38 .0°C | Off |
COLD WEATHER SHUT DOWN Select the outdoor temperature at which the cooling is shut off . | Off, 40 to 100°F Off, 4 .5 to 38 .0°C | Off |
HEAT PUMP BALANCE POINT Select the outdoor temperature at which the heat pump is shut off and the backup heat source is operated exclusively . | Off, 10 to 70°F Off, -12 .0 to 21 .0°C | Off |
Setup – Sensors
Setting | Range | Default |
SENSOR 1 Select the type of sensor connected to S1 and Com wiring terminals . | Off, Room, Floor | Off |
SENSOR 2 Select the type of sensor connected to S2 and Com wiring terminals . | Off, Room, Floor, Outdoor | Off |
SENSOR 3 Select the type of sensor connected to S3 and Com wiring terminals . | Off, Room, Floor, Humidity | Off |
INTERNAL ROOM SENSOR Select if the internal room temperature sensor is on or off . Only available when Sensor 1, 2 or 3 is set to read a room or floor sensor . | Off, On |
On |
INTERNAL HUMIDITY SENSOR Select if the internal humidity sensor is on or off . Only available when Sensor 3 is set to read an external humidity sensor . | Off, On |
On |
ROOM OFFSET Manual offset correction of the room temperature measurement. | Off, -5 to +5°F -3 .0 to 3 .0°C | Off |
FLOOR OFFSET Manual offset correction of the floor temperature measurement. | Off, -5 to +5°F -3 .0 to 3 .0°C | Off |
HUMIDITY OFFSET Manual offset correction of the relative humidity measurement. | Off, -10% to +10% | Off |
Setup – Alerts
Setting | Range | Default |
ROOM HOT WARNING Error on home screen if the room exceeds this temperature. | Off, 40 to 100°F Off, 4 .5 to 38 .0°C | Off |
ROOM COLD WARNING Error on home screen if the room falls below this temperature. | Off, 40 to 100°F Off, 4 .5 to 38 .0°C | Off |
LOW HUMIDITY WARNING Error on home screen if the humidity falls below this threshold. | Off, 5 to 95% | Off |
HIGH HUMIDITY WARNING Error on home screen if the humidity exceeds this threshold . | Off, 5 to 95% | Off |
AUXILIARY HEAT RUN TIME WARNING Error on home screen if the auxiliary heat W1 or W2 runs continuously for longer than this setting . This setting only applies for heat pump systems . |
Off, 1 to 24 hours |
Off |
AIR FILTER CHANGE WARNING Error on home screen to change the air filter when the fan exceeds this run time . | Off, 200 to 2000 hours | Off |
UV LAMP CHANGE WARNING Error on home screen to change the UV disinfectant lamp when it exceeds this run time . | Off, 10,000 to 50,000 hours | Off |
Setup – Relays (1 of 3)
Setting | Range | Default |
HEATING TYPE Select between conventional heating or heat pump . | Conventional, Heat Pump | Conventional |
EQUIPMENT Select the number of stages of the heating and cooling equipment . | Conventional 1 Heat/1 Cool, 1 Heat/2 Cool, 2 Heat/1 Cool, 2 Heat/2 Cool, |
1 Heat/ 1 Cool |
Heat Pump 1 HP, 1 HP/1 Aux, 1 HP/2 Aux, 2 HP, 2 HP/1 Aux, 2 HP/2 Aux |
1 HP/1 Aux | |
RADIANT FLOOR HEATING Select if the first stage W1 heats a radiant floor . | Yes or No | No |
HEAT 1 DIFFERENTIAL Select when the first stage heating turns on . Turn on point is the Heat To setting minus the differential . | 0 .9 to 2 .0°F 0 .5 to 1 .05°C | 1 .4°F 0 .75°C |
HEAT 2 DIFFERENTIAL Select when the second stage heating turns on . Turn on point is the Heat To setting minus the differential . This setting is available when there are at least 2 heating stages . | 1 .0 to 10 .0°F 0 .6 to 5 .6°C | 2 .0°F 1 .2°C |
HEAT 2 DELAY Select the time delay when the second stage heating turns on . The time delay starts counting after the first stage heating is turned on . This setting is available when there are at least 2 heating stages . |
0 to 180 minutes |
1 minute |
HEAT 3 DIFFERENTIAL Select when the third stage heating turns on . Turn on point is the Heat To setting minus the differential . This setting is available when a heat pump is selected and there are at least 3 heating stages . | 1 .0 to 10 .0°F 0 .6 to 5 .6°C | 2 .5°F 1 .4°C |
HEAT 3 DELAY Select the time delay when the third stage heating turns on . The time delay starts counting after the second stage heat- ing is turned on . This setting is available when a heat pump is selected and there are at least 3 heating stages . |
0 to 180 minutes |
1 minute |
HEAT 4 DIFFERENTIAL Select when the fourth stage heating turns on . Turn on point is the Heat To setting minus the differential . This setting is available when a heat pump is selected and there are 4 heating stages . | 1 .0 to 10 .0°F 0 .6 to 5 .6°C | 3 .0°F 1 .8°C |
Setup – Relays (2 of 3)
Setting | Range | Default |
HEAT 4 DELAY Select the time delay when the fourth stage heating turns on . The time delay starts counting after the third stage heating is turned on . This setting is available when a heat pump is selected and there are at least 4 heating stages . |
0 to 180 minutes |
1 minute |
COOL 1 DIFFERENTIAL Select when the first stage cooling turns on . Turn on point is the Cool To setting plus the differential . | 0 .9 to 2 .0°F 0 .5 to 1 .05°C | 1 .4°F 0 .75°C |
COOL 2 DIFFERENTIAL Select when the second stage cooling turns on . Turn on point is the Cool To setting plus the differential . This setting is available when there are two cooling stages . | 1 .0 to 10 .0°F 0 .6 to 5 .6°C | 2 .0°F 1 .2°C |
COOL 2 DELAY Select the time delay when the second stage cooling turns on . The delay time starts counting after the first stage cooling is turned on . This setting is available when there are two cooling stages . |
0 to 180 minutes |
1 minute |
Y MIN RUN TIME Select the minimum time the cooling compressor must run before shutting off . This helps prevent compressor failure . | 0:30 to 10:00 minutes | 2:00 minutes |
Y MIN OFF TIME Select the minimum time the cooling compressor must be off before turning back on . This helps prevent compressor failure . |
0:30 to 10:00 minutes |
5:00 minutes |
DUAL FUEL Select dual fuel on if the heat pump has 100% backup using a furnace or hydronic fan coil . The setting is available for heat pump systems with auxiliary heat . |
Off or On |
Off |
ACCESSORY RELAY 1 Select the type of equipment that the accessory relay 1 operates . | Off, Humidifier, Dehumidifier, Ventilation, HP Loop Valve |
Off |
ACCESSORY RELAY 2 Select the type of equipment that the accessory relay 2 operates . This setting is only available for conventional heating systems . | Off, Humidifier, Dehumidifier |
Off |
Setup – Relays (3 of 3)
Setting | Range | Default |
HEAT PUMP REVERSING VALVE Select O for heat pumps designed for normally heating operation . Select B for heat pumps designed for normally cooling operation . This setting is only available for heat pump systems . |
O (Orange), B (Blue) |
O |
FAN RELAY Select which relays require fan operation . Combinations with W1 are not available when Radiant Floor Heating is set to yes . | G only, With Y With Y and W1, With Y and W2, With Y, W1 and W2 |
G only |
FAN WITH HRV/ERV Select if the HVAC system fan should turn on together with the HRV or ERV ventilation fan . | Off or On | Off |
HUMIDIFIER TYPE Select the type of humidifier . This setting is available when Accessory 1 or 2 is set to Humidifier . | Evaporative, Steam, Stand Alone | Steam |
WINDOW PROTECTION Select if the relative humidity setpoint should automatically adjust with outdoor temperature to prevent frost on windows . This setting is available when Accessory 1 or 2 is set to Humidifier and a wired outdoor sensor is installed . |
Off or On |
Off |
WINDOW QUALITY The window quality determines the amount that the relative humidity setting is lowed during cold outdoor weather . Choose the highest number of panes installed and best quality as a starting point . If window condensation appears, lower the setting until condensation stops forming . This setting is available when Accessory 1 or 2 is set to Humidifier and a wired outdoor sensor is installed . | 1 Pane 2 Pane 3 Pane
Poor Average Better |
2 Pane Average |
DEHUMIDIFIER TYPE Select the type of dehumidifier . This setting is available when Accessory 1 or 2 is set to Dehumidifier . | DX Coil, Stand Alone | DX Coil |
HEAT-COOL TIME INTERLOCK When operating in Mode Auto, select the amount of time to wait between switching from heating to cooling and vice versa . |
0 to 180 minutes |
10 minutes |
Set the lowest relative humidity level. Range is 10 to 80%Default is 40% Available when Accessory 1 or 2 operates a humidifier.
Heating and Cooling Operation
Conventional Systems
A conventional heating system includes: furnaces, air conditioners, hydronic heating systems with baseboards, radiant floors, or fan coils and electric heating. The thermostat supports up to two heating stages, two cooling stages, a fan and two accessory relay
EQUIPMENT SETTING | 1H/1C | 1H/2C | 2H/1C | 2H/2C |
First stage heating | W1 | W1 | W1 | W1 |
Second stage heating | – | – | W2 | W2 |
First stage cooling | Y1 | Y1 | Y1 | Y1 |
Second stage cooling | – | Y2 | – | Y2 |
Fan | G | |||
Accessory 1 | Choice of: Humidifier, Dehumidifier, HRV/ERV | |||
Accessory 2 | Choice of: Humidifier, Dehumidifier |
Heat Pump Systems
A heat pump system may include additional heat sources as backup. The thermostat supports up to four heating stages, two cooling stages, a reversing valve, a fan and one accessory relay.
EQUIPMENT SETTING | 1HP | 1HP/1AUX | 1HP/2AUX | 2HP | 2HP/1AUX | 2HP/2AUX |
First stage heating | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 |
Second stage heating | – | W1 | W1 | Y2 | Y2 | Y2 |
Third stage heating | – | – | W2 | – | W1 | W1 |
Fourth stage heating | – | – | – | – | – | W2 |
First stage cooling | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 |
Second stage cooling | – | – | – | Y2 | Y2 | Y2 |
Fan | G | |||||
Accessory 1 | Choice of: Humidifier, Dehumidifier, HRV/ERV ventilator | |||||
Accessory 2 | Reversing valve O relay remains closed during cooling. Reversing valve B relay remains closed during heating. |
When radiant floor heating is installed, it is always the first stage of heating, followed by the heat pump, and lastly any backup heating. This allows the floor to remain warm in the heating season.
EQUIPMENT SETTING | 1HP | 1HP/1AUX | 1HP/2AUX | 2HP | 2HP/1AUX | 2HP/2AUX |
First stage heating | Y1 | W1 | W1 | Y1 | W1 | W1 |
Second stage heating | – | Y1 | Y1 | Y2 | Y1 | Y1 |
Third stage heating | – | – | W2 | – | Y2 | Y2 |
Fourth stage heating | – | – | – | – | – | W2 |
First stage cooling | Y1 | Y1 | Y1 | Y1 | Y1 | Y1 |
Second stage cooling | – | – | – | Y2 | Y2 | Y2 |
Fan | G | |||||
Accessory 1 | Choice of: Humidifier, Dehumidifier, HRV/ERV ventilator | |||||
Accessory 2 | Reversing valve O or B. O relay remains closed during heating operation. B relay remains closed during cooling operation.
|
Heating Differentials
Each heating stage has an adjustable differential and time delay setting to determine when the stage turns on. The heating stages Heat 4 to Heat 1 shut off are when they reach 1.5, 1.0, 0.5, and 0.0°F (0.75, 0.5, 0.25, and 0.0°C) of the Heat To setting respectively.
Radiant Floor Heating
Radiant floor heating is operated differently than other heating types due to the large time delays to heat and cool the slab. When Radiant Floor Heating is selected in the setup menu, the W1 relay oper-ates using Pulse Width Modulation. This improves comfort for radiant systems with high mass floors.
Room Sensor and Averaging
The room temperature can be measured using a combination of the built-in and auxiliary sensors.
Floor Sensor for Radiant Floor Heating
If a floor sensor is connected, floor minimum and maximum settings are available. For a combination of air and floor temperature control, leave the internal air sensor on in the setup menu. A floor minimum can be used to prevent a fast drop in temperature caused by receding solar exposure. This operation is recommended for areas heated by afternoon sun through large windows. When the sun sets, it can take a long time for the floors to get warm again. This may cause the room to cool off too much in the early evening. A floor minimum setting can help with this condition by maintaining a floor minimum temperature. Keep in mind the floor minimum temperature will override the air temperature, and if set too high, may overheat the room. A floor maximum is recommended for rooms with hardwood floors. Setting floor minimum and maximum temperatures is a way of enhancing the comfort of the living space while protecting
floor coverings. If there are more than one floor temperature sensors, the temperature is averaged.
Cooling Differentials
The first and second stage cooling have adjustable differentials and time delay setting to determine when the stage turns on, and shut off when the room temperature reaches 0.5 and 0.0°F (0.25 and 0.0°C) above the Cool To setting respectively.
Heat Pump Balance Point
An air source heat pump’s Coefficient of Performance (COP) declines with falling outdoor air tempera-ture. The Balance Point is the outdoor temperature at which it is more economical to shut off the heat pump (relays Y1 and Y2) and operate the backup heating equipment (relays W1 and W2). This feature requires an Outdoor Sensor 070.
Dual Fuel
Dual fuel systems include a heat pump together with a backup heat source such as a furnace or a hydronic fan coil. When Dual Fuel is set to on, the heat pump (relays Y1 and Y2) is shut off whenever the backup heating equipment (relays W1 and W2) is operating.
Warm Weather Shut Down (WWSD)
The heating system can automatically shut off based upon the outdoor temperature and the WWSD setting. This provides a convenient way to shut off the heating system. The WWSD requires an Outdoor Sensor 070.
Cold Weather Shut Down (CWSD)
The cooling system can automatically shut off based upon the outdoor temperature and CWSD setting. This prevents unwanted cooling during the winter. The CWSD requires an Outdoor Sensor
Relative Humidity Sensor
The thermostat includes an internal relative humidity (RH) sensor and has the option to connect to an external RH sensor. The installer has the option to disable the internal RH sensor when an external RH sensor is installed. When both the internal and external RH sensors are enabled, the RH reading is averaged.
Humidifier Operation
The thermostat controls the relative humidity (RH) by operating either the Accessory 1 or Accessory 2 relays. This is an installer configurable setting. When the RH is below the Humidify To setting by 3%, the Accessory 1 or 2 relay is closed to operate a humidifier. The humidifier is shut off when the RH reaches the Humidify To setting. The thermostat can operate 3 types of humidifiers:
The thermostat can operate 3 types of humidifiers:
Humidifier Window Protection
During cold weather, condensation will form on windows when the relative humidity (RH) is too high. The optional window protection feature automatically calculates the indoor dew point based upon the outdoor temperature and the quality of the windows installed. The humidifier is then operated to the highest possible RH that is below the Humidify To setting. This feature requires a wired outdoor sensor to be installed.
Dehumidifier Operation
The thermostat controls the relative humidity (RH) by operating either the Accessory 1 or Accessory 2 relay. This is an installer configurable setting. When the RH is above the Dehumidify To setting by 3%, the Accessory 1 or 2 relay is closed to operate the dehumidifier. The dehumidifier is shut off when the RH reaches the Dehumidify To setting.
The thermostat can operate 2 types of dehumidifiers:
HRV / ERV Ventilator Operation
Ventilation with fresh outdoor air is important for maintaining indoor air quality. The thermostat can operate a heat recovery ventilator (HRV) or energy recovery ventilator (ERV) on a timer by closing the Accessory 1 relay to operate the ventilator fan at low speed.
Heat Pump Loop Valve Operation
The thermostat supports water-to-air heat pump systems that absorb or reject heat to a hydronic building loop. Whenever the heat pump compressor Y1 or Y2 relay is turned on, the Accessory 1 relay closes to open a hydronic zone valve. This allows variable-speed pumps on the hydronic loop to operate at lower speeds when the heat pump is off, thereby saving electrical energy.
Description |
COMMUNICATION ERROR Communication between the display module and the HVAC Interface Module is interrupted . This error clears automatically once communication is re-established . This error can occur if the power supply voltage to the HVAC Interface Module is low . Check the voltage with a volt meter and that the transformer VA rating is enough to power all the equipment . |
MEMORY ERROR The thermostat memory settings are corrupted . To clear, load the factory defaults in the Toolbox menu . The thermostat will not operate any heating or cooling equipment while this error message is present . |
INTERNAL ROOM SENSOR FAULT Due to an open or short circuit, the thermostat is unable to read the internal room temperature sensor . If sensor 1, 2 or 3 is set to room the thermostat continues to operate, otherwise operation stops . The error cannot be field repaired . Contact your tekmar sales representative for warranty or repair procedures . |
INTERNAL HUMIDITY SENSOR FAULT Due to an open or short circuit, the thermostat is unable to read the internal humidity sensor . The thermostat stops controlling the humidifier or dehumidifier unless an external humidity sensor is installed on Sensor 3 . The error cannot be field repaired . Contact your tekmar sales representative for warranty or repair procedures . |
SENSOR 1 FAULT Due to an open or short circuit, the thermostat is unable to read the sensor wired to S1 and Com . The thermostat stops normal operation if sensor 1 is the only active room or floor sensor or if a floor maximum temperature has been set . Check the auxiliary sensor wire for short circuits according to the sensor installation manual . It may be necessary to replace the auxiliary sensor . Once the error has been corrected, the error message automatically clears . |
SENSOR 2 FAULT Due to an open or short circuit, the thermostat is unable to read the sensor wired to S2 and Com . The thermostat stops normal operation if sensor 2 is the only active room or floor sensor or if a floor maximum temperature has been set . Check the auxiliary sensor wire for short circuits according to the sensor installation manual . It may be necessary to replace the auxiliary sensor . Once the error has been corrected, the error message automatically clears . |
SENSOR 3 FAULT Due to an open or short circuit, the thermostat is unable to read the sensor wired to S3 and Com . The thermostat stops normal operation if sensor 3 is the only active room sensor or if a floor maximum temperature has been set . Check the auxiliary sensor wire for short circuits according to the sensor installation manual . It may be necessary to replace the auxiliary sensor . Once the error has been corrected, the error message automatically clears . |
Description |
WATER LEAK DETECTOR WARNING A water leak has been detected and the water line has been shut off . The warning will automatically clear once the water leak detector has been reset . |
ROOM HOT WARNING The room temperature is above the Room Hot Warning setting in the Alerts menu . The warning will automatically clear once the room temperature falls below the setting . |
ROOM COLD WARNING The room temperature is below the Room Cold Warning setting in the Alerts menu . The warning will automatically clear once the room temperature rises above the setting . |
LOW HUMIDITY WARNING The relative humidity is below the Low Humidity Warning setting in the Alerts menu . The warning will automatically clear once the relative humidity rises above the setting . |
HIGH HUMIDITY WARNING The relative humidity is above the High Humidity Warning setting in the Alerts menu . The warning will automatically clear once the relative humidity falls below the setting. |
AUXILIARY HEAT RUN TIME WARNING The auxiliary heat has been operating continuously longer than the Aux Heat Run Time Warning setting in the Alerts menu. The error clears when the auxiliary heat turns off . There may be problem with your heat pump . Contact your heating professional for service . |
CHANGE AIR FILTER WARNING The fan run time has exceeded the Change Air Filter setting in the Alerts menu and requires replacement . To clear the warning, press the Air Filter Replaced button . |
CHANGE UV LAMP WARNING The UV lamp run time has exceeded the UV Lamp setting in the Alerts menu and requires replacement. To clear the warning, press the UV Lamp Replaced button . |
Thermostat 565 | |
Literature | ES-T-565, IOM-T-565, UserManual-T-565, JobRecord-T-565 |
Packaged weight | 1.3 lb. (600 g) |
Dimensions | Display: 41/2″ H x 23/4″ W x 9⁄16″ D (114 x 70 x 14 mm) HVAC Interface Module: 77⁄16″ H x 47⁄16″ W x 11/4″ D (188 x 112 x 31 mm) |
Display | 3.5″ color touchscreen |
Enclosure | Display: White or Black PVC plastic, NEMA type 1 HVAC Interface Module: Blue PVC plastic, NEMA type 1 |
Approvals | Meets Class B: ICES & FCC Part 15 |
Ambient conditions | Display: Indoor use only, -4 to 122°F (-20 to 50°C), RH ≤90% non-condensing HVAC Interface Module: -40 to 122°F (-40 to 50°C), RH ≤90% non-condensing, outdoor use requires mounting in a NEMA 3 enclosure |
Environmental | Do not use in presence of ammonia (animal barns). |
Power supply | 21-30 V (ac), 6 VA, Class 2 |
Relays | 30 V (ac) 2 A, Class 2 Circuits |
Humidity sensor | 0 to 90% ±4% RH |
RH Output | 3.3 V (dc) humidity sensor power, 3.0 mA maximum |
Temperature sensor | NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892 |
Optional sensors | tekmar type # 070, 072, 073, 076, 077, 079, 084, 086, 087 |
Languages | English/Français/Español |
Warranty | 3-Year Limited Warranty |
Limited Warranty The liability of tekmar under this warranty is limited. The Purchaser, by taking receipt of any tekmar product (“Product”), acknowledges the terms of the Limited Warranty in effect at the time of such Product sale and acknowledges that it has read and understands same. The tekmar Limited Warranty to the Purchaser on the Products sold hereunder is a manufacturer’s pass-through warranty which the Purchaser is authorized to pass through to its customers. Under the Limited Warranty, each tekmar Product is warranted against defects in workmanship and materials if the Product is installed and used in compliance with tekmar’s instructions, ordinary wear and tear excepted. The pass-through warranty period is for a period of twenty-four (24) months from the production date if the Product is not installed during that period, or twelve (12) months from the documented date of installation if installed within twenty-four (24) months from the production date.
The liability of tekmar under the Limited Warranty shall be limited to, at tekmar’s sole discretion: the cost of parts and labor provided by tekmar to repair defects in materials and/or workmanship of the defective product; or to the exchange of the defective product for a warranty replacement product; or to the granting of credit limited to the original cost of the defective product, and such repair, exchange or credit shall be the sole remedy available from tekmar, and, without limiting the foregoing in any way, tekmar is not responsible, in contract, tort or strict product liability, for any other losses, costs, expenses, inconveniences, or damages, whether direct, indirect, special, secondary, incidental or consequential, arising from ownership or use of the product, or from defects in workmanship or materials, including any liability for fundamental breach of contract. The pass-through Limited Warranty applies only to those defective Products returned to tekmar during the warranty period. This Limited Warranty does not cover the cost of the parts or labor to remove or transport the defective Product, or to reinstall the repaired or replacement Product, all such costs and expenses being subject to Purchaser’s agreement and warranty with its customers. Any representations or warranties about the Products made by Purchaser to its customers which are different from or in excess of the tekmar Limited Warranty are the Purchaser’s sole responsibility and obligation. Purchaser shall indemnify and hold tekmar harmless from and against any and all claims, liabilities and damages of any kind or nature which arise out of or are related to any such representations or warranties by Purchaser to its customers.
The pass-through Limited Warranty does not apply if the returned Product has been damaged by negligence by persons other than tekmar, accident, fire, Act of God, abuse or misuse; or has been damaged by modifications, alterations or attachments made subsequent to purchase which have not been authorized by tekmar; or if the Product was not installed in compliance with tekmar’s instructions and/or the local codes and ordinances; or if due to defective installation of the Product; or if the Product was not used in compliance with tekmar’s instructions.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO CONTRACTUALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, DURABILITY OR DESCRIPTION OF THE PROD-UCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NON-VIOLATION OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY LEGISLATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT EXTEND BEYOND TWENTY-FOUR (24) MONTHS FROM THE PRODUCTION DATE, TO THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY THE GOVERNING LAW.
Product Warranty Return Procedure All Products that are believed to have defects in workmanship or materials must be returned, together with a written description of the defect, to the tekmar Representative assigned to the territory in which such Product is located. If tekmar receives an inquiry from someone other than a tekmar Representative, including an inquiry from Purchaser (if not a tekmar Representative) or Purchaser’s customers, regarding a potential warranty claim, tekmar’s sole obligation shall be to provide the address and other contact information regarding the appropriate Representative.
Need help? Go to our website or contact us.
tekmarControls.com
tekmar.customerservice@wattswater.com
1-800-438-3903 All specifications are subject to change without notice
Tel: 1-800-438-3903
Fax: (250) 984-0815 watts.com/tekmar
Download manuals:
tekmar 565 Programmable Thermostat Installational Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…