The WiFi Thermostat 561 provides precise temperature control of a one-stage heating system. When connected to the Internet, the mobile app and website allows you to control the thermostat remotely. The thermostat and mobile app include an away feature that overrides the schedule to lower the temperature and increase energy savings. The thermostat is designed to support radiant floor heating and optional floor sensors can be installed to enhance comfort and protect floor coverings.
It is your responsibility to ensure that this thermostat is safely installed according to all applicable codes and standards. tekmar is not responsible for damages resulting from improper installation and/or maintenance.
Do not attempt to service the thermostat. There are no user serviceable parts inside the thermostat. Attempting to do so voids warranty.
Tools Required
Materials Required
18 AWG LVT Solid Wire (Low Voltage Connections)
Installation Location
Consider the following:
While holding the base section in one hand, pull the lower half of the display front towards you to pivot it away from the base.
Warning: To prevent the risk of personal injury and/or death, make sure power is not applied to the thermostat until it is fully installed and ready for final testing. All work must be done with power to the circuit being worked on turned off.
Please be aware local codes may require this thermostat to be installed or connected by an electrician.
The WiFi Thermostat 561 operates a radiant floor heating system. The thermostat uses the built-in air temperature sensor.
Legend
Electrical
The WiFi Thermostat 561 operates a radiant floor heating system based upon the floor temperature sensor. The built-in air sensor is disabled.
Legend
Electrical
The WiFi Thermostat 561 operates a radiant floor heating system. The thermostat uses both air and floor temperature sensors. The air temperature sensor can be either built-in and/or external.
Legend
Electrical
The WiFi Thermostat 561 operates a baseboard/radiator using an air temperature sensor. The air temperature sensor can be either built-in and/or external.
Legend
Electrical
Heating Operation
The Heat On symbol is shown on the display when the thermostat is heating. Heating for freeze protection is provided whenever the air or floor temperature falls below 40°F (4.5°C), regardless of operating mode.
Regular Heating
W1 relay is on when the air temperature falls 1.5°F (1°C) below the Heat To setting. When the temperature reaches the Heat To setting, the relay turns off. The W2 relay turns on based on settings selected in the Setup menu. W2 turns off when the air temperature is 0.5°F (0.25°C) below the Heat To setting.
Radiant Floor Heating
When Radiant Floor Heating is selected in the setup menu, the W1 relay operates using Pulse Width Modulation. This improves comfort for radiant systems with high mass floors.
Floor Sensor for Radiant Floor Heating
If a floor sensor is connected, floor minimum and maximum settings are available.
For a combination of air and floor temperature control, leave the internal air sensor on in the setup menu. A floor minimum can be used to prevent a fast drop in temperature caused by receding solar exposure. This operation is recommended for areas heated by afternoon sun through large windows. When the sun sets, it can take a long time for the floors to get warm again. This may cause the room to cool off too much in the early evening. A floor minimum setting can help with this condition by maintaining a floor minimum temperature. Keep in mind the floor minimum temperature will override the air temperature, and if set too high, may overheat the room.
A floor maximum is recommended for rooms with hardwood floors. Setting floor minimum and maximum temperatures is a way of enhancing the comfort of the living space while protecting floor coverings.
Warm Weather Shut Down (WWSD)
The heating system can automatically shut off based upon the outdoor temperature and the WWSD setting. This provides a convenient way to shut off radiant floor heating.
After 60 seconds of inactivity, the thermostat home screen displays only the time and the temperature.
Use the Away setting to save energy when the building is unoccupied.
The away setting is shared to:
Display | |||
Setting | Range | Default | |
TEMPERATURE UNITS Select °F or °C. | °F or °C | °F | |
ENERGY USE View the number of hours the heating system has operated either daily or monthly. |
0 to 24 (daily) 0 to 744 (monthly) |
0 hours | |
BRIGHTNESS ACTIVE Select the brightness when touching the screen. | 30 to 100% | 100% | |
BRIGHTNESS INACTIVE Select the brightness when not in use. | Off, 30 to 100% | 50% | |
BACKGROUND Select the background color. | White, Blue, Black, Latte, Espresso | Blue | |
LANGUAGE Select the language. | English, Español, Français | English | |
SCREEN CLEAN Locks screen for 10 seconds to allow cleaning. | N/A | N/A |
When connected to the Internet, the time can be set automatically. The time and date can be manually set by highlighting a field and then using the or buttons. Choose from the time options listed below.
Setting | Range | Default |
TIME FORMAT Select the time format. | 12 or 24 hour | 12 hour |
TIME SOURCE If Internet is available, the time source can be either automatically or manually set. | Automatic, Manual | Auto |
TIME ZONE Select the local time zone. | Hawaii, Alaska, Pacific, Mountain, Central, Eastern, Atlantic, Newfoundland | Eastern |
DAYLIGHT SAVING TIME Select the brightness when not in use. | Off, On | On |
Notice Incorrectly setting the time and date manually may prevent the thermostat from communicating to the mobile app. Automatic time source is recommended when using an Internet connection.
Notice Before using the WiFi features of this product, you must accept the Terms of Use, as amended from time to time and available at tekmarConnect.com/terms. If you do not accept these terms, this product can still be used without WiFi features.
This product requires WiFi WPA security. WEP is not supported. The thermostat includes a step by step tutorial to setup the WiFi connection.
Setup
Setup – Toolbox
Setting | Range | Default |
ERROR Displays any error messages. | N/A | N/A |
ACCESS LEVEL Select between user and installer access levels. User access level restricts access in the Setup Menu. | User, Installer | Installer |
STATUS The current status of warm weather shut down, cold weather shut down and each of the relays. | WWSD, W1 | N/A |
SOFTWARE VERSION Display the software version. | J1249A | N/A |
LOAD DEFAULTS All settings are returned to factory defaults. | Yes, No | No |
CALIBRATE TOUCHSCREEN Recalibrate the screen after loading factory defaults. | N/A | N/A |
Setup – Temp
Setting | Range | Default |
Screen Page 1 | ||
FLOOR MIN – WAKE Select the floor temperature while in the wake schedule. Applies when there is both a floor and an air sensor. | Off, 40 to 95°F Off, 4.5 to 35.0°C | Off |
FLOOR MIN – LEAVE Select the floor temperature while in the leave schedule. Applies when there is both a floor and an air sensor. | Off, 40 to 95°F Off, 4.5 to 35.0°C | Off |
FLOOR MIN – RETURN Select the floor temperature while in the return schedule. Applies when there is both a floor and an air sensor. | Off, 40 to 95°F Off, 4.5 to 35.0°C | Off |
FLOOR MIN – SLEEP Select the floor temperature while in the sleep schedule. Applies when there is both a floor and an air sensor. | Off, 40 to 95°F Off, 4.5 to 35.0°C | Off |
FLOOR MIN – AWAY Select the floor temperature while in away. Applies when there is both a floor and an air sensor. | Off, 40 to 95°F Off, 4.5 to 35.0°C | Off |
FLOOR MAX Select the maximum floor temperature. This protects the floor covering from over heating. Applies when there is a floor sensor. | Off, 40 to 95°F Off, 4.5 to 35.0°C | Off |
Screen Page 2 | ||
HEAT TO AWAY Select the heating temperature when away. | Off, 40 to 95°F Off, 4.5 to 35.0°C | 62°F (16.5°C) |
HEAT TO MIN LIMIT Select the minimum heating temperature limit. | Off, 40 to 95°F Off, 4.5 to 35.0°C | Off |
HEAT TO MAX LIMIT Select the maximum heating temperature limit. | Off, 40 to 95°F Off, 4.5 to 35.0°C | Off |
WARM WEATHER SHUT DOWN Select the outdoor temperature at which the heating is shut off. | Off, 40 to 95°F Off, 4.5 to 35.0°C | Off |
Setup – Sensors
Setting | Range | Default |
SENSOR 1 Select the type of sensor connected to S1 and Com wiring terminals. | Off, Room, Floor | Off |
SENSOR 2 Select the type of sensor connected to S2 and Com wiring terminals. | Off, Room, Floor, Outdoor |
Off |
INTERNAL ROOM SENSOR Select if the internal room temperature sensor is on or off. Only available when Sensor 1 or 2 is set to read a room or floor sensor. | Off, On |
On |
ROOM OFFSET Select if the internal room temperature sensor is on or off. Only available when Sensor 1 or 2 is set to read a room or floor sensor. | Off, -5 to +5°F -3.0 to 3.0°C |
Off |
Setup – Alerts
Setting | Range | Default |
ROOM HOT WARNING Sends an email notification if the room exceeds this temperature. | Off, 40 to 100°F Off, 4.5 to 38.0°C | Off |
ROOM COLD WARNING Sends an email notification if the room falls below this temperature. | Off, 40 to 100°F Off, 4.5 to 38.0°C | Off |
Setup – Relays
Setting | Range | Default |
RADIANT FLOOR HEATING Select if the first stage W1 heats a radiant floor. | No, Yes | No |
To view and adjust the WiFi Thermostat using a mobile phone or tablet, download the tekmar Connect mobile app from the Apple® iTunes® Store or from the Google Play® Store.
Alternatively, go to tekmarConnect.com for web browser access.
Add Thermostat to App
Using the App
When an error occurs an email notification will be sent to the registered tekmar Connect mobile or web app account owner.
Description |
MEMORY ERROR The thermostat memory settings are corrupted. To clear, load the factory defaults in the Toolbox menu. The thermostat will not operate any heating equipment while this error message is present. |
INTERNAL ROOM SENSOR FAULT Due to an open or short circuit, the thermostat is unable to read the internal room temperature sensor. If sensor 1 or 2 is set to room the thermostat continues to operate, otherwise operation stops. The error cannot be field repaired. Contact your tekmar sales representative for warranty or repair procedures. |
SENSOR 1 FAULT Due to an open or short circuit, the thermostat is unable to read the sensor wired to S1 and Com. The thermostat stops normal operation if sensor 1 is the only active room or floor sensor or if a floor maximum temperature has been set. Check the auxiliary sensor wire for short circuits according to the sensor installation manual. It may be necessary to replace the auxiliary sensor. Once the error has been corrected, the error message automatically clears. |
SENSOR 2 FAULT Due to an open or short circuit, the thermostat is unable to read the sensor wired to S2 and Com. The thermostat stops normal operation if sensor 2 is the only active room or floor sensor or if a floor maximum temperature has been set. Check the auxiliary sensor wire for short circuits according to the sensor installation manual. It may be necessary to replace the auxiliary sensor. Once the error has been corrected, the error message automatically clears. |
ROOM HOT WARNING The room temperature is above the Room Hot Warning setting in the Alerts menu. The warning will automatically clear once the room temperature falls below the setting. |
ROOM COLD WARNING The room temperature is below the Room Hot Warning setting in the Alerts menu. The warning will automatically clear once the room temperature falls below the setting. |
WiFi Thermostat 561 One Stage Heat | |
Literature | 561_C, 561_D, 561_J, 561_U |
Control | Microprocessor control. This is not a safety (limit) control. |
Packaged weight | 0.6 lb. (270 g) |
Dimensions | 4-5/8″ H x 3″ W x 15/16″ D (118 x 76 x 24 mm) |
Enclosure | White PVC plastic, NEMA Type 1 |
Approvals | Meets Class B: ICES & FCC Part 15 |
Ambient conditions | Indoor use only, 32 to 122°F (0 to 50°C), RH ≤90% non-condensing |
Power supply | 15 to 30 V (ac/dc), 2 VA standby, Class 2 |
Relays | 30 V (ac/dc), 2 A, Class 2 circuits |
Sensor | NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892 |
– Included | None |
– Optional | tekmar type # 070, 072, 073, 076, 077, 079, 084 |
Communications | WiFi 802.11n, 2.4 GHz, WPA2 encryption |
Mobile app | Apple iOS, Android |
Limited Warranty The liability of tekmar under this warranty is limited. The Purchaser, by taking receipt of any tekmar product (“Product”), acknowledges the terms of the Limited Warranty in effect at the time of such Product sale and acknowledges that it has read and understands same.
The tekmar Limited Warranty to the Purchaser on the Products sold hereunder is a manufacturer’s pass-through warranty which the Purchaser is authorized to pass through to its customers. Under the Limited Warranty, each tekmar Product is warranted against defects in workmanship and materials if the Product is installed and used in compliance with tekmar’s instructions, ordinary wear and tear excepted. The pass-through warranty period is for a period of twenty-four (24) months from the production date if the Product is not installed during that period, or twelve (12) months from the documented date of installation if installed within twenty-four (24) months from the production date.
The liability of tekmar under the Limited Warranty shall be limited to, at tekmar’s sole discretion: the cost of parts and labor provided by tekmar to repair defects in materials and / or workmanship of the defective product; or to the exchange of the defective product for a warranty replacement product; or to the granting of credit limited to the original cost of the defective product, and such repair, exchange or credit shall be the sole remedy available from tekmar, and, without limiting the foregoing in any way, tekmar is not responsible, in contract, tort or strict product liability, for any other losses, costs, expenses, inconveniences, or damages, whether direct, indirect, special, secondary, incidental or consequential, arising from ownership or use of the product, or from defects in workmanship or materials, including any liability for fundamental breach of contract.
The pass-through Limited Warranty applies only to those defective Products returned to tekmar during the warranty period. This Limited Warranty does not cover the cost of the parts or labor to remove or transport the defective Product, or to reinstall the repaired or replacement Product, all such costs and expenses being subject to Purchaser’s agreement and warranty with its customers.
Any representations or warranties about the Products made by Purchaser to its customers which are different from or in excess of the tekmar Limited Warranty are the Purchaser’s sole responsibility and obligation. Purchaser shall indemnify and hold tekmar harmless from and against any and all claims, liabilities and damages of any kind or nature which arise out of or are related to any such representations or warranties by Purchaser to its customers.
The pass-through Limited Warranty does not apply if the returned Product has been damaged by negligence by persons other than tekmar, accident, fire, Act of God, abuse or misuse; or has been damaged by modifications, alterations or attachments made subsequent to purchase which have not been authorized by tekmar; or if the Product was not installed in compliance with tekmar’s instructions and / or the local codes and ordinances; or if due to defective installation of the Product; or if the Product was not used in compliance with tekmar’s instructions.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO CONTRACTUALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, DURABILITY OR DESCRIPTION OF THE PRODUCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NON-VIOLATION OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY LEGISLATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY CONTRACTUALLY EXCLUDED IS LIM-ITED SUCH THAT IT SHALL NOT EXTEND BEYOND TWENTY-FOUR (24) MONTHS FROM THE PRODUCTION DATE, TO THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY THE GOVERNING LAW.
Product Warranty Return Procedure All Products that are believed to have defects in workmanship or materials must be returned, together with a written description of the defect, to the tekmar Representative assigned to the territory in which such Product is located. If tekmar receives an inquiry from someone other than a tekmar Representative, including an inquiry from Purchaser (if not a tekmar Representative) or Purchaser’s customers, regarding a potential warranty claim, tekmar’s sole obligation shall be to provide the address and other contact information regarding the appropriate Representative.
WARNING: This product contains chemicals known to the State of California to cause cancer and birth defects or other reproductive harm. For more information: Watts.com/prop65
All specifi cations are subject to change without notice
Tel: (250) 545-7749
Fax: (250) 984-0815
tekmarControls.com
Download manual:
tekmar 561_D WiFi Thermostat Installational Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…