Tekmar

tekmar 554_C touchscreen Thermostat Product Specifications Guide

tekmar 554_C touchscreen Thermostat

INTRODUCTION

The tekmarNet Thermostat 554 is a communicating touchscreen thermostat designed to operate one heating stage, one cooling stage, and a fan. The heating stage can be either hydronic or forced air and the cooling stage is an air conditioner. There are two auxiliary sensor inputs available to measure room, floor, outdoor, coil or duct temperature. The optional floor sensor allows precise heating of radiant floors by controlling the floor temperature and maintaining the desired room air temperature. The large touchscreen allows you to easily adjust 7-day programmable schedules and room temperature to optimize comfort and energy savings. The 554 can connect to tekmarNet controls using two or four wires or it can operate as a stand-alone thermostat using three wires

Specifications

tekmarNet® Thermostat 554 One Stage Heat, One Stage Cool, One Fan
Literature 554_A, 554_C, 554_D, 554_J, 554_Q, 554_U
Control Microprocessor control. This is not a safety (limit) control.
Packaged weight 0.8 lb. (350 g)
Dimensions 5″ H x 3-1/4″ W x 15/16″ D (127 x 82 x 23 mm)
Enclosure White PVC plastic, NEMA type 1
Approvals Meets Class B: ICES & FCC Part 15
Ambient conditions Indoor use only, 32 to 122°F (0 to 50°C), RH ≤90% non-condensing
Power supply 24 V ± 10%, 60 Hz, 1.8 VA standby, NEC / CEC Class 2
Relays 24 V (ac), 2 A
Temperature sensor NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892
–Included None
–Optional tekmar type # 070, 071, 072, 073, 076, 077, 079, 082, 083, 084
Warranty Limited 3 Year (See 554_D for full warranty)

Feature

  • tekmarNet communication compatible
  • Touchscreen technology
  • Radiant floor heating
  • Programmable schedule
  • Network schedule master or member
  • Optimum start
  • Temporary hold
  • Air group master
  • Zone synchronization
  • 2 auxiliary sensor inputs
  • Room temperature limiting
  • Away scene key

Special requirements
An auxiliary sensor must be used to measure any auxiliary sensor temperatures.

Sample Application Drawing

Below is a sample application drawing for this product. This application may include other tekmar products that are required for installation. More sample applications can be found at www.tekmarControls.com.

NOTICE
The information contained herein is not intended to replace the full product installation and safety information available or the experience of a trained product installer. You are required to thoroughly read all installation instructions and product safety information before beginning the installation of this product

tekmar

  • tekmar Control Systems Ltd.,
  • A Watts Water Technologies Company. Head Office: 5100 Silver Star Road,
  • Vernon, B.C. Canada V1B 3K4, 250-545-7749,
  • Fax. 250-545-0650
  • Web Site: www.tekmarControls.com

REFERENCE

DOWNLOAD MANUAL

tekmar 554_C touchscreen Thermostat Product Specifications Guide

tekmar 554_C touchscreen Thermostat Product Specifications Guide

wpx_thermostats

Recent Posts

Amex Casino United Kingdom

Amex Casino United Kingdom Instead of free spins, you do well and have winnings that…

1 week ago

Best Online Casino For Roulette

Best Online Casino For Roulette Time and Again is an HTML5 title, best online casino…

1 week ago

Fastest Payout Online Casinos

Fastest Payout Online Casinos Bally Wulff is known for their amazing classic slots and Back…

1 week ago

Bison Casino No Deposit Bonus Codes For Free Spins 2026

Bison Casino No Deposit Bonus Codes For Free Spins 2026 One reels 1 and 5…

1 week ago

Casinos With Fast Payouts

Casinos With Fast Payouts Sky Queen is a medium to high volatility slot offering an…

1 week ago

European Roulette Guide Uk

European Roulette Guide Uk There is a 30x wagering requirement in place on the deposit…

1 week ago