Equipment description
The FEK control module only works in conjunction with the weather-compensated WPMi control unit. It enables the convenient entry and display of system parameters, e.g. outside temperature, relative humidity, and heating circuit parameters (e.g. heating times and required room temperature) for the heating system from the user’s living room. This allows the constant monitoring and optimization of the heating system, both in heating and cooling modes. In addition, hooking up a room temperature enables the correction of the weather-compensated WPMi control unit.
Equipment overview
With closed control flap and standard display
With the control flap open and with all indicator elements on display
important information
The control module must only be installed and maintained by qualified contractors.
The operation is split over three control levels. Control levels 1 and 2 are accessible to users and contractors alike. Control level 3 is only designed for qualified contractors:
Control level 1 (control flap closed)
This enables the adjustment of operating modes, such as standby mode, programmed operation, and constant day or setback mode (for this, see section 1.5.1).
Control level 2 (control flap open)
This enables parameters, such as room temperature, heating programs, etc. to be adjusted (for this, see section 1.5.5).
Control level 3 (for contractors only)
This level is protected by a code and should only be used by contractors. At this level, heat pump and system-specific details are determined (for this, see section 2.5).
Settings
All adjustments follow the same pattern: Opening the control flap toggles the FEK to control level 2. The display shows the parameter “room temp.”. Pressing
Terminating programming
You can terminate the programming process after entering and saving the required parameter changes by closing the control flap. However, if you want to make further changes, press one of the keys until the display shows BACK,
Adjustments (control level 1)
With the flap closed, the display shows the operating mode, time, and day, as well as the current room temperature and relative humidity.
Operating mode key
When connecting a FEK, only the operating modes for the pre-selected heating circuit are adopted by the WPMi. You can select the required operating mode by pressing this key several times with the flap closed. The selected operating mode is indicated by a symbol in the display. It becomes effective if the setting was not changed for five seconds.
Frost protection for the heating operation is active. The standby symbol flashes, when the heat pump manager is in standby mode, and the operating mode cannot be adjusted.
Application: During holidays.
Automatic mode
Heating according to the time switch program. Changeover between day temperature and setback temperature. With this operating mode, an additional symbol (sun or moon) indicates in the display, whether the heating circuit is currently in a day or in setback mode.
The heating circuit is held at a constant day temperature. Application: In low-energy houses without setback mode.
The heating circuit is held at a constant setback temperature. Application: During weekends away.
Away key
This key activates the eco mode (away). Press twice: The heating circuit switches to setback mode for one hour. The selected heating interruption is briefly displayed in hours. Press this key several times: the heating circuit switches for the respective number of hours to setback mode. If no key is then pressed for approx. three seconds, the display returns to the standard display, and the active heating interruption is displayed by the flashing moon symbol. You can scan the selected heating interruption by pressing the “Away” key once at any time. Pressing the operating mode key deactivates the “Away” period and the moon symbol will extinguish.
Help key
Pressing this key allows you to scan sensor temperatures of the heat pump or heat pump system, such as outside temperature, actual DHW temperature, actual return temperature, actual room temperature, and relative humidity. After you press this key, the first display is the outside temperature. Continuing to press displays, in sequence, the actual DHW temperature, the actual return temperature, the maximum and minimum room temperatures, and the maximum and minimum relative humidity. The standard display returns after five seconds. The MIN/MAX values for room temperature and relative humidity are constantly updated and stored. If you hold down the key for four seconds, the top of the display shows DELETE VALUES. All MIN/MAX values will then be deleted. Any fault in the heat pump causes an arrow above the help key and the attention symbol to flash. Pressing the help key displays that fault. Three seconds later, the fault display extinguishes, and the standard display returns again.
Room temperature
You can adjust the room temperature by +/- 5K with the rotary selector. This set value adjustment applies to the then current heating time, not to the setback time.
Overview of a system parameter (control level 2)
Selects the required parameter with the rotary selector. For adjustments to parameters, turn to page 6.
Adjustments at control level 2 for users and contractors
The heating curve, room temperature, and heating program parameters are not shown at the WPMi heat pump manager if the FEK is pre-selected for a specific heating circuit.
Room temperature
With the Room temp. parameters you can adjust the set room temperature for the day and setback mode. Changing these parameters results in a parallel offset of the heating curve.
Open the control flap
The Temperatures parameter enables you to scan the following sensor temperatures of the heat pump or heat pump system, comparing the actual with the set temperatures, the relative humidity, etc..
Note
No display, if the corresponding temperature sensor is not connected.
Open the control flap
Heating program
Under this parameter you have the option of setting up a heating program, i.e:
You can adjust three switching time pairs (I, II, III) for each of these options. This determines when and how often the heat pump system should heat in day mode. At all other times, the heat pump operates
in setback mode. You will already have selected the corresponding set values for day and setback mode under the Room temp. parameter.
Example:
Your heating system should operate daily from Monday to Friday at two different times, i.e. from 05:30 h until 08:30 h and from 14:00 h until 22:00 h. For the weekend, your heating system should provide heat from 08:30 h until 21:00 h.
Open the control flap
Heating curve
The Heating curve parameter allows you to select a heating curve for heating circuits 1 or 2. Selecting the correct heating curve is vitally important.
Note: Your contractor will have set up a building and system-specific optimum heating curve for the heating circuit. It relates to the heat pump return temperature for heating circuit 1 and to the mixer flow temperature for heating circuit 2. When adjusting the heating curve, the calculated set return or flow temperature, which is subject to the outside temperature and the set room temperature, will be shown at the top of the display.
Open the control flap
Heating curve diagram
One heating curve respectively can be adjusted for heating circuit 1 and heating circuit 2. At the factory, heating curve 0.6 is set up for heating circuit 1 and heating curve 0.2 for heating circuit 2. These heating curves relate to a set room temperature of 20 °C.
Adjustment of programmed changeover between day/setback mode
The figure shows a standard heating curve with a slope of 0.8, relative to a set room temperature for day mode of 20 °C. The lower curve represents the setback curve. For this, a set room temperature for setback mode of 15 °C is used, in other words, the heating curve is subjected to a parallel offset.
Matching a heating curve to actual conditions
Example: During spring and autumn, the return or flow temperature of a heating system is too low at an outside temperature between 5 and 15 °C, but is OK at outside temperatures of ≤ 0 °C. This problem can be remedied by a parallel offset and a simultaneous reduction of the heating curve. Prior to this adjustment, heating curve 1.0 was adjusted, relative to a set room temperature of 20 °C. The dotted line indicates the modified heating curve at 0.83 and a modified set room temperature at 23.2 °C.
Standard delivery
FEK Part no:22 01 93
Dimensions: 147 x 97 x 33 (mm)
General information
The FEK is vitally important for area cooling, e.g. underfloor heating systems, area heating, etc. Apart from the room temperature, it also determines the relative humidity to prevent condensation.
Installation
The correct function of the control module can only be assured if the following are observed:
Secure the bottom part on the wall and connect the BUS cable.
Supply voltage | 12 V DC ± 15 % |
Power consumption | ~ 25 mA |
EN 60529 EN 60730 | IP 40 |
Protection class II | |
Clock backup | > 10 hours |
Permiss. ambient temp. during operation | 0 to 50 °C |
Permiss. ambient temp. during storage | – 20 to 60 °C |
Room temperature sensor resistance Tolerance in Ohm Temperature tolerance | Test resistance NTC 5 kW ± 1 % at 25 °C ± 0.2 K at 25 °C |
FEK commissioning
Only approved contractors may commission this control module and instruct the owner in its use. Not only the adjustments at control level 2 but also the system-specific parameters must be determined as part of commissioning the FEK. These parameters are adjusted at control level 3, access to which is protected by code. To reach this point, press
Note: Not all adjustments take immediate effect. Some adjustments only become effective in certain situations or after a delay.
Code 1 0 0 0
Enter the correct four-digit code to change parameters at control level 3. The factory-set code is 1 0 0 0. After pressing
Pressing
Language
Press
Contrast
Press
SELECT REM CON
You can predetermine with parameter FE selection, to which heating circuit the remote control applies. As standard, HC1 is pre-selected. Accordingly, the parameters room temp., heating curve, and heating program for heating circuit 1 are not displayed at the WPMi.
This parameter enables the calibration of the actual room temperature.
Room influence for FEK
Standard setting 5; adjustable from —-via “0 to 20” dashes (—-) in the display: When the FEK control module is connected, the room temperature sensor only serves to capture and display the actual room temperature; it has no influence on the actual control. With any setting, you can adjust the set room temperature for the heating circuit at the FEK control module by ±5 K. This set value adjustment applies for the then-current heating time, not to the setback time.
At the same time, setting “0 to 20” serves to control the room temperature-dependent night setback. This means the heating circuit pump is switched OFF at the point of changeover from the heating into the setback phase. It remains OFF, until the actual room temperature first drops below the set room temperature. Afterward, the system regulates in weather-compensated mode. If you want the room temperature to be taken into account, set the room temperature sensor influence to > 0. The room sensor influence has the same effect as the outside temperature sensor has on the return temperature. Only this effect is 1 to 20 times greater than the set factor. Room temperature-dependent return temperature with weather compensation With this type of control, a controlled cascade is formed from weather-compensated and room temperature-dependent return temperature control. In other words, the weather-compensated return temperature control pre-selects the return temperature, which is corrected by the overlaid return temperature control in accordance with the following formula: ∆ϑR = (ϑRset − ϑRactual) * S * K
Because a substantial proportion of control
is already taken care of by the weather-compensated control, the room temperature sensor influence K can be set lower than with a pure room temperature control (K = 20). The figure on page 15 indicates the control method with the set factor K = 10 (room influence) and a heating curve S = 1.2.
Room temperature control with weather-compensation
This type of control offers two substantial benefits: Incorrectly set heating curves are corrected by the room temperature sensor influence K, whilst the smaller factor K provides more stable control.
However, observe the following for all control units with room temperature sensor influence:
LCD test
Pressing
FEK software
Display of the current software issue.
USA
Stiebel Eltron Inc.
17 West Street West Hatfield MA 01088
04 13-247-3380 Fax 0413-247-3369
E-Mail info@stiebel-eltron-usa.com
Internet www.stiebel-eltron-usa.com
DOWNLOAD MANUALS:
STIEBEL ELTRON FEK 220193 Room Thermostat Installational Instruction
STIEBEL ELTRON FEK 220193 Room Thermostat Installational Instruction
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…