IMPORTANT SAFETY INFORMATION
REMOVING THE OLD THERMOSTAT
WARNING!: Electrical Shock Hazard
INSTALLING YOUR THERMOSTAT
ATTACH THE THERMOSTAT BASE TO THE WALL AND PULL THE COVER OFF THE BASE.
WARNING!: Electrical Shock Hazard
Turn off power at the main service panel by removing the fuse or switching the appropriate circuit breaker to the OFF position before removing the existing thermostat.
Wiring Diagrams
THERMOSTAT LCD DISPLAY
THERMOSTAT BUTTONS AND SWITCHES
CHECK THERMOSTAT OPERATION
If at any time during testing your system does not operate properly, contact a qualified service person.
Turn on the power to the system.
Heating System
Cooling System
CAUTION!: To prevent compressor and/or property damage, if the outdoor temperature is below 10ºC, DO NOT operate the cooling system.
FAN OPTION SWITCH
Fan Operation
Move the system switch to the OFF position. If your system does not have a “G” (Fan) terminal connection, skip to the Heating System.
This thermostat is configured from the factory to energize the fan on a call for heat. If your system is an electric heat or heat pump that REQUIRES the thermostat to turn on the fan on a call for heat, place the fan option switch in the ELEC position. If your system does not require the thermostat to energize the fan on a call for heat such as fossil fuel (gas, oil, etc.), forced air system as well as hydraulic heating systems, place the fan option switch in the GAS position.
BATTERY OPERATION
The thermostat will operate from 2 size “AA” alkaline batteries or 24VAC power. When operated from batteries, connection to the “C” (common) or (neutral) terminal is not required.
NOTE: When operated from batteries (No “C” terminal connection), the LCD display backlight options are limited to option 1 (disabled) or option 2 (30-second illumination after each button press).
If your thermostat was pre-installed, the batteries may be in place. If the battery icon on the display is flashing, it indicates that the batteries need to be replaced. When the thermostat is powered only by battery, the battery icon will flash for approximately 2 months before the batteries are expected to expire. Then the thermostat will cut power to the heating/cooling system.
Important: Replace the batteries when the low battery message flashes on the display. This will keep the thermostat operating properly. With two “AA” batteries installed, your thermostat will maintain time and continuously display the temperature during a loss of AC power.
THERMOSTAT OPERATION
Setting the thermostat
This thermostat is very easy to operate. Set the SYSTEM switch to either HEAT or COOL, then press the ▲ or ▼buttons until the temperature you want to maintain is shown on the right side of the display. If you want to turn the system off, just move the SYSTEM switch to the OFF position and the FAN switch to the AUTO position.
Set the current day and time
Filter timer
5 | PRGM | FL (00) | 00, 1 thru12 | Select filter time in months. Default = 00. A selection of “00” deactivates the filter feature. |
To exit the review menu press the ▲ or ▼ buttons one time. Or If no buttons are pressed within 15 seconds, the thermostat will exit the configuration menu. In review mode, press and hold the ▲ and ▼ 15 sec. to clean the filter warning. It will show a “dEF” blink. To reset the filter days – refer to configuration item 5 operation
Enter the Heating Program
NOTE: To set a scheduled program to OFF set your heat temperature to 7.0ºC and your Cooling to 32.0ºC
Enter the Cooling Program
Note: The time of day clock MUST be set to the correct day and time in order for the programmed times to be correct. Look at the factory preprogrammed times and temperatures shown in the Factory default program setting. If this program will suit your needs, simply press the RUN button to begin running the factory preset program. If you wish to change the preprogrammed time and temperature, follow these steps: Determine the time periods and temperatures for your program. You must program four periods for each day. However, you may use the same heating and cooling temperatures for consecutive time periods. You can choose the heating temperature, cooling temperature, and start time independently. (for example, you may select 5:00 am AND 21ºC as the weekday 1st-period heating start time and temperature and also choose 7:00 AM and 24ºC as the weekday 1st-period cooling start time and temperature.
Use the table below to plan your program time periods and the temperatures you want during each period. Fill in the completed table to have a record of your program.
EXAMPLE:
Heating/Cooling Schedule Plan (Factory default program setting)
Weekdays (5 day) | Saturday and Sunday | ||||
Mode | Period | Start Time | Temperature | Start Time | Temperature |
Heat | 1st | 6:00 AM | 21.0ºC | 6:00 AM | 21.0ºC |
2nd | 8:00 AM | 16.5ºC | 8:00 AM | 16.5ºC | |
3rd | 6:00 PM | 21.0ºC | 6:00 PM | 21.0ºC | |
4th | 10:00 PM | 16.5ºC | 10:00 PM | 16.5ºC | |
COOL | 1st | 6:00 AM | 24.0ºC | 6:00 AM | 24.0ºC |
2nd | 8:00 AM | 28.5ºC | 8:00 AM | 28.5ºC | |
3rd | 6:00 PM | 24.0ºC | 6:00 PM | 24.0ºC | |
4th | 10:00 PM | 25.5ºC | 10:00 PM | 25.5ºC |
Heating/Cooling Schedule Plan
Weekdays (5 day) | Saturday and Sunday | ||||
Mode | Period | Start Time | Temperature | Start Time | Temperature |
Heat | 1st | ||||
2nd | |||||
3rd | |||||
4th | |||||
COOL | 1st | ||||
2nd | |||||
3rd | |||||
4th |
NOTE: To set a scheduled program to OFF set your heat temperature to 7.0º C and your Cooling to 32.0º C
Check your programming
Follow these steps to check your thermostat programming one final time before beginning thermostat operation:
REVERT TO FACTORY DEFAULT PROGRAM SETTINGS
Press the RESET button. All user’s changed settings will revert to factory default settings (Including configuration settings).
Advanced Configuration Menu
The configuration menu allows you to set certain thermostat operating characteristics to your system or personal requirements. Move the SYSTEM switch to the OFF position, then press and hold the PRGM and RUN buttons for 3 seconds to enter the configuration menu. The display will show the first item in the configuration menu. Press the PRGM button to move to the next menu item, or press TIME to return to a previous menu item. To revert to factory default settings, press the RESET button (See Fig. 3). All users’ changed settings will revert to factory default settings, including program settings. Use the ▲or▼ buttons to select. To exit the configuration menu and return to normal operation, press the RUN button. If no buttons are pressed within 130 seconds, the thermostat will exit the configuration menu. The configuration menu chart summarizes the configuration options. An explanation of each option follows.
Step | Press Buttons | Displayed (Factory Defaults) | Press ▲ or▼ to select |
Description |
1 | PRGM+RUN 5 seconds | CC (FA) | FA or SL | Select (FA)st or (SL)ow cooling cycles Default = FA |
2 | PRGM | HC (FA) | FA or SL | Select F(ast) or (S)low Heating cycles. Default = FA |
3 | PRGM | h0 (0) | 0 or 1 | Select system heating type, 0 = Gas, oil, or electric heating. 1 = Heat pump heating. Default = 0 |
4 |
PRGM |
bL (2) |
1 – 3 | Select display backlight (1) = OFF, (2) = 30 seconds on any button push, (3) = ON. Default = 2. Option (3) can be activated only if the common wire is used. |
5 | PRGM | FL (00) | 00, 1 thru12 | Select filter time in months. Default = 00. A selection of “00” deactivates the filter feature. |
6 | PRGM | FC (C) | F or C | Select Temperature display to indicate °F or °C. Default = C |
7 | PRGM | CL (0) | +4 TO -4 | Select temperature calibration point up to 4° higher or 4° lower. Default = 0 |
8 |
PRGM |
CP (5) |
0 or 5 | Compressor Lockout delay. 0 = none 5 = 5 Minutes Default = 5 |
9 |
PRGM |
IC |
0 or 1 | Intelligent Recovery Option. “1” = Active “0” = Deactivated. Default = 0 |
RUN | Return to normal operation |
If a voltage spike or static discharge blanks out the display or causes erratic operation, you can reset the thermostat by pressing the reset button (see Figure 1). If the thermostat has power, has been reset, and still does not function correctly, contact your heating/cooling service person or place of purchase.
Symptom | Possible Cause | Corrective Action |
Heat, Cool or Fan Runs Constantly |
1. Fan switch set to FAN ON
2. Possible short in wiring
3. Possible short in thermostat
4. Possible short in Heat/Cool/Fan system | Check each wire connection to verify they are not shorted or touching together. No bare wire should stick out from under terminal screws. Try resetting the thermostat as described below. If the condition persists, the manufacturer of your system or service person can instruct you on how to test the Heat/Cool system for correct operation. If the system operates correctly, replace the thermostat. |
Furnace Cycles too fast or too slow | 1. The location of the thermostat and/or the size of the heating system may be influencing the cycle rate. | Item 2 in the Configuration Menu is the adjustment that controls the heating cycle rate. If an acceptable cycle rate is not achieved using the FA or SL adjustment, contact a local service person for additional suggestions. |
Cooling cycles too fast or too slow | 1. The location of the thermostat and/or the size of the heating system may be influencing the cycle rate. | Item 1 in the Configuration Menu is the adjustment that controls the cooling cycle rate. If an acceptable cycle rate is not achieved using the FA or SL adjustment, contact a local service person for additional suggestions. |
Thermostat Setting and Thermometer disagree |
1. Thermostat thermometer setting requires adjustment. | The thermostat temperature calibration can be adjusted +\- 3 degrees as listed in item 7 of the Configuration menu. No other adjustment is possible. |
Clock looses or gains time |
1. Loss of power to thermostat and low batteries | The thermostat will maintain its program in memory even with no power and no batteries, but the clock time will be incorrect when power is restored. See No Heat/No Cool/No Fan above for items to check in the system. |
Thermostat does not follow program | 1. AM or PM set incorrectly in program
2. AM or PM set incorrectly on the clock
3. Voltage spike or static discharge | Check current clock and program setting including the AM or PM designation for each time period. If a voltage spike or static discharge occurs, use the Reset
Operation listed above. |
Blank display and/or keypad not responding | 1. Loss of power and dead batteries.
2. Voltage spike or static discharge | Replace batteries and check heat/cool system for proper operation. If a voltage spike or static discharge occurs, use the Reset Operation listed above. |
These instructions assume the installer of this thermostat has
knowledge of Heating & Air conditioning systems, the terminology used in these systems, and of the HVAC industry requirements It is an offense in Australia for unqualified persons to make any changes to Air‐conditioning systems. Failure to observe this may void equipment and thermostat warranty, and property insurance and cause irreparable damage to the thermostat or equipment connected to it. Warranty 24 Months from date of purchase ‐ RTB
For technical support please contact Smart Temp Australia P/L
or an authorized sales/service agent.
Due to continual product improvement, these specifications are subject to change without notice.
www.smarttemp.com.au www.thermostat.com.au
DOWNLOAD MANUALS:
Smarttemp 42-160 PROGRAMMABLE THERMOSTAT Operation Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…