SIEMENS

SIEMENS RDG100 Room Thermostat Product Specifications Guide

SIEMENS RDG100 Room Thermostat

Wall-mounted room thermostats with LCD

  • for fan coil unit applications
  • for universal applications
  • for use with compressors in DX-type equipment
  • RDG100..: Operating voltage AC 230 V, On/Off, 3-positon or PWM control outputs
  • RDG110: Operating voltage AC 230 V, On/Off relay (SPDT) outputs
  • RDG110U: Operating voltage AC/DC 24 V, On/Off relay (SPDT) outputs
  • RDG100../RDG110..: Output for 1-speed and 3-speed
  • RDG160T..: Operating voltage AC/DC 24 V, DC 0…10 V or On/Off control outputs
  • RDG160T..: Output for 1-speed, 3-speed or ECM fan DC 0…10 V
  • Operating modes: Comfort, Economy and Protection
  • Automatic or manual fan speed
  • 3 multifunctional inputs for keycard contact, external sensor, etc
  • Automatic or manual heating/cooling changeover
  • Adjustable commissioning and control parameters
  • Minimum and maximum setpoint limitation
  • Backlit display
  • Additional features of RDG100T, RDG160T..:
  • The infrared remote control receiver
  • Auto Timer mode with 8 programmable timers
  • The auto timer can be disabled via P02
  • Auto timer can be disabled via DIP switches (RDG160T..)
  • Selectable relay output functions (RDG160T..)
  • Power reserve clock for 48 h during power failure

Use

The RDG1.. room thermostats are designed for use with the following types of system:

Fan coil units via On/Off or modulating control outputs:

  • 2-pipe system
  • A 2-pipe system with electric heater
  • 2-pipe system and radiator/floor heating
  • 4-pipe system
  • A 4-pipe system with electric heater
  • 2-stage heating or cooling system

Chilled/heated ceilings (or radiators) via On/Off or modulating control outputs:

  • Chilled/heated ceiling
  • Chilled/heated ceiling with electric heater
  • Chilled/heated ceiling and radiator/floor heating
  • Chilled/heated ceiling, 2-stage cooling or heating

Heat pumps with dx-type equipment:

  • 1-stage compressor for heating or cooling
  • 1-stage compressor for heating or cooling with electric heater
  • 1-stage compressor for heating or cooling and radiator/floor heating
  • 1-stage compressor for heating and cooling
  • 1-stage compressor for heating and cooling with reversing valve
  • 2-stage compressor for heating or cooling

Functions

  • Maintenance of room temperature via built-in temperature sensor or external room temperature/return air temperature sensor
  • Automatic or manual changeover between heating and cooling mode
  • Selection of applications via DIP switches
  • Selection of operating mode via the operating mode button on the thermostat
  • 1-speed, 3-speed or DC 0…10 V fan control (automatic or manual)
  • Display of current room temperature or setpoint in °C and/or °F
  • Minimum and maximum setpoint limitation
  • Button lock (automatic or manual)
  • 1 digital input, freely selectable for:
    • Operating mode switchover contact (keycard)
    • Automatic heating/cooling changeover contact
    • Electric heater enable
    • Dewpoint sensor
    • Fault input
  • 2 multifunctional inputs, freely selectable for:
    • Operating mode switchover contact (keycard)
    • Automatic heating/cooling changeover sensor
    • External room temperature or return air temperature
    • Dewpoint sensor
    • Electric heater enable
    • Fault input
    • Supply air temperature sensor (RDG160T..)
  • Advanced fan control function, i.e. fan kick, fan start, selectable fan operation
    (enable, disable or depending on heating or cooling mode)
  • Purge function together with 2-port valve in a 2-pipe changeover system
  • Reminder to clean filters
  • Floor heating temperature limit
  • Minimum and maximum supply air temperature limitation (RDG160T..)
  • Reloading factory settings for commissioning and control parameters
  • 7-day time program: 8 programmable timers to switch over between Comfort and Economy mode (RDG100T, RDG160T..)
  • Infrared remote control (RDG100T, RDG160T..)
  • Selectable relay function (RDG160T..)
    • For switching OFF external equipment OFF during Protection mode
    • For switching ON external equipment (such as. pump) during H/C demand
    • Output heating/cooling sequence
  • Wizard function to select working temperature unit °C or °F (RDG160TU, RDG110U)
  • Power reserve clock for 48 h during power failure on RDG1..T

Applications

The room thermostats support the following applications, which can be configured via DIP switches at the rear of the unit. Depending on the thermostat type, On/Off or modulating control outputs are available.

Product no. Control outputs
RDG100.. On/Off, PWM, 3-position
RDG110/RDG110U On/Off (SPDT)
RDG160T/RDG160TU On/Off, DC 0…10 V

Product no. Control outputs Fan
RDG110/RDG110U On/Off (SPDT) Disabled, 3-speed, 1-speed
RDG160T/RDG160TU On/Off, DC 0…10 V Disabled, 3-speed, 1-speed, DC 0…10 V

Legend

  • YHC.. Heating/cooling valve actuator M1 1-speed or 3-speed fan
  • YH Heating valve actuator
  • YC Cooling valve actuator
  • B1 Return air temperature sensor or external room temperature sensor (optional)
  • YE Electric heater B2 Changeover sensor (optional)

Type summary

  1. Infrared remote control must be ordered as a separate item
  2. ECM fan output DC 0…10 V
  3. On/Off, PWM or 3-position (triac outputs)
  4. Relay output (SPDT)
  5. Can be disabled via P02 (or via DIP switches on RDG160T..)
  6. On/Off (relay output) or DC control signal

Equipment combinations

Description Product no. Data Sheet
Infrared remote control                             

IRA211

3059

Cable temperature sensor or changeover sensor, cable length 2.5 m (8 feet)

NTC (3 kO at 25 °C (77 °F))

 

QAH11.1

 

1840

Room temperature sensor NTC (3 kO at 25 °C (77 °F)) QAA32 1747
Cable temperature sensor, cable length 4 m (13 feet) NTC (3 kO at 25 °C (77 °F))

QAP1030/UFH

1854

Condensation monitor QXA2601/ QXA2602/ QXA2603/

QXA2604

 

3302

On/Off actuators
Electromotor On/Off valve and actuator(only available in AP, UAE, SA and IN)
MVI../MXI.. A6V11251892
Electromotor On/Off actuator SFA21.. 4863
Electromotor On/Off actuator SFP21.. 4863
Zone valve actuators (only available in AP, UAE, SA and IN) SUA.. 4830
On/Off and PWM actuators )
Thermal actuator (for radiator valves) AC 230 V, NO

STA23..

4884

Thermal actuator (for radiator valves) AC 24 V, NO STA73.. *) 4884 *)
Thermal actuator AC 230 V (for small valves 2.5 mm (0.1″)), NC STP23..*) 4884
Thermal actuator AC 24 V (for small valves 2.5 mm (0.1″)) NC STP73.. *) 4884 *)
3-position actuators
Electrical actuator, 3-position (for radiator valves)
SSA31.. 4893
Electrical actuator, 3-position (for 2- and 3-port valves/V..P45) SSC31.. 4895
Electrical actuator, 3-position

(for small valves 2.5 mm (0.1″))

SSP31.. 4864
Electrical actuator, 3-position (for small valves 5.5 mm (0.2″)) SSB31.. 4891
Electrical actuator, 3-position (for CombiValves VPI45) SSD31.. 4861
Electromotor actuator, 3-position (for valves 5.5 mm) SAS31.. 4581
DC 0…10 V actuators
Electrical actuator, DC 0…10 V (for radiator valves)
SSA61.. 4893
Electrical actuator, DC 0…10 V (for 2- and 3-port valves/V..P45) SSC61.. 4895
Electrical actuator, DC 0…10 V (for small valves 2.5 mm (0.1″)) SSP61.. 4864
Electrical actuator, DC 0…10 V (for small valves 5.5 mm (0.2″)) SSB61.. 4891
Electrical actuator, DC 0…10 V

(for CombiValves VPI45)

SSD61.. 4861
Electromotor actuator, DC 0…10 V (for valves 5.5 mm) SAS61.. 4581
Electrothermal actuator, AC 24 V, NC, DC 0…10 V, 2 m (6.6feet) (for radiator valves and small valves 2.5 mm (0.1″))

 

STA63

 

4884

Electrothermal actuator, AC 24 V, NO, DC 0…10 V, 2 m (6.6 feet) (for radiator valves and small valves 2.5 mm (0.1″))

 

STP63

 

4884

With PWM control, it is not possible to ensure exact parallel running of 2 or more thermal actuators. If several fan coil systems are controlled by the same room thermostat, preference should be given to motorized actuators with On/Off or 3-position control.
Note:
For more information about parallel operation and the maximum number of actuators that can be used, refer to the Data Sheets of the selected type of actuator and the following list:

  • Maximum number of actuators in parallel on the RDG100..:
    • 6 SS..31.. actuators (3-pos)
    • 4 ST..23.. if used with On/Off control signal
    • 10 SFA.., SUA.., MVI.., MXI.. On/Off actuators
    • Parallel operation of SAS31.. is not available
  • Maximum number of actuators in parallel on the RDG110..:
    • 10 On/Off actuators
  • Maximum number of actuators in parallel on the RDG160T..:
    • 10 SS..61.. actuators (DC)
    • 10 ST..23/63/73.. actuators (DC or On/Off)
    • 10 SFA.., SUA.., MVI.., MXI.. On/Off actuators
    • 10 SAS61.. actuators (DC)

Accessories

Description Product no. Data Sheet
Changeover mounting kit (50 pcs/package) ARG86.3 3009

Ordering

Product no. Stock no. Designation
RDG100 S55770-T158 Room thermostat
RDG100T S55770-T159 Room thermostat, with timer
RDG110 S55770-T160 Room thermostat with relay outputs (AC 230 V)
RDG110U S55770-T361 Room thermostat with relay outputs (AC 24 V), UL certified
RDG160T S55770-T343 Room thermostat with timer and DC (or On/Off) output for valve and fan (AC 24 V)
RDG160TU S55770-T362 Room thermostat with timer and DC (or On/Off) output for valve and fan (AC 24 V), UL certified
  • Order the IRA211 infrared remote control separately.
  • Order valve actuators separately.
  • Order RDG110U and RDG160TU from Siemens Building Technologies USA.

Mechanical design

The room thermostat consists of two parts:

  • Plastic housing which accommodates the electronics, the operating elements and the room temperature sensor
  • Mounting plate with the screw terminals
    The housing engages in the mounting plate and is secured with 2 screws.

Operation and settings

  1. Operating mode selector/Esc
  2. Button to enter the time and to set the timers
  3. Fan mode selector/OK
  4. Rotary knob for setpoint and parameter adjustment

Display

# Symbol Description # Symbol Description

1

Heating mode

14

Automatic fan

2

Heating mode

auxiliary heater on (2nd stage)

15

Manual fan

3

Cooling mode

 

 

 

16

 

 

 

Fan speed

Fan speed 1

4

Comfort mode

Fan speed 2

5

Economy mode

Fan speed 3

6

Auto Timer mode

 

17

Degrees Celsius Degrees Fahrenheit

7 View and set Auto Timer program

8

Protection

18

Digits for room temperature and setpoint display

9

Escape

19

Button lock

10

Digits for time, room temperature, setpoint, etc.

20


Condensation in room (dewpoint sensor active)

11

Setting the time of day and the weekday

21


Weekday 1…7: 1 = Monday/7 = Sunday

 

12

 

 

Morning: 12-hour format Afternoon: 12-hour format

22
Fault

23


Temporary timer function (visible when

operating mode is temporarily extended due to prolonged presence or absence)

13

Confirmation of parameters

24

Indicates that room temperature is displayed

Mounting and installation

Do not mount on a wall in niches or bookshelves, behind curtains, above or near heat sources, or exposed to direct solar radiation. Mount about 1.5 m (5 feet) above the floor.

Mounting

  • The room thermostat must be mounted in a clean, dry indoor place and must not be exposed to drip or splash water.

Wiring: See Mounting Instructions (M3181, M3183, M3183.1 or M3183.2) enclosed with the thermostat.

  • Comply with local regulations to wire, protect and earth the thermostat.

Warning
No internal line protection for supply lines to external consumers (Q1, Q2, Q3, Yx or Yxx).
Risk of fire and injury due to short circuits!

  • Adapt the line diameters as per local regulations to the rated value of the installed overcurrent protection device.
  • The AC 230 V mains or AC 24 V supply line must have a circuit breaker with a rated current of no more than 10 A. For AC 24 V US installations, use Class 2 rated power supplies.
  • Properly size the cables to the thermostat, fan and valve actuators for AC 230 V mains voltage.
  • Use only valve actuators rated for AC 230 V on RDG100.., RDG110 and on RDG160T if AC 230V is connected to the “L” terminal.
  • Use only a 3-speed fan rated with AC 24 V on RDG160TU.
  • Isolate the cables of inputs X1-M/X2-M and D1-GND if the conduit box carries
    AC 230 V mains voltage.
  • On the RDG100.. and RDG110, inputs X1-M and X2-M carry mains potential.
    If the sensor’s cables are extended, they must be suited for mains voltage.
  • Inputs X1-M, X2-M or D1-GND of different units (e.g. summer/winter switch) may be connected in parallel with an external switch. Consider overall maximum contact sensing current for switch rating.
  • Selectable relay function (RDG160T..). Consider the overall maximum current though the relays.
  • Disconnect the power supply before removing the thermostat from the mounting plate!

Commissioning

  1. Select the application via the DIP switches at the rear of the thermostat before fitting the front housing to the mounting plate.
  2. Power up the thermostat after successfully connecting the line power. The thermostat starts to reset and all LCD segments flash, indicating that the reset was correct.

After the reset, which takes about 3 seconds, the thermostat is ready for commissioning by qualified HVAC staff. The control parameters of the thermostat can be set to ensure optimum performance of the entire system (see Basic Documentation P3181).

Temperature unit selection wizard (only for RDG110U and RDG160TU): The temperature unit selection wizard enables to select the preferable temperature unit display on thermostat between °C and °F.

  1. Rotate rotary knob to select the preferable temperature unit.
  2. Press the button (OK) to confirm the selection, and the thermostat goes to normal operating page.

Notes

  • Pressing button (Esc) does not confirm the temperature unit selection.
  • If the temperature unit is not selected, °C is used by default.

Control sequence

  • The control sequence may need to be set via parameter P01 depending on the application. The factory setting for the 2-pipe application is “Cooling only”; and
    “Heating and cooling” for the 4-pipe application.

Compressor-based application

  • When the thermostat is used in connection with a compressor, the minimum output on-time (parameter P48) and off-time (parameter P49) for Y11/Y21 (RDG110) must be adjusted to avoid damage to the compressor and shorten its life.

Calibrate sensor

  • Recalibrate the temperature sensor via parameter P05 if the room temperature displayed on the thermostat does not match the room temperature measured.

Adaptive temperature compensation for el. heating

  • If an electric heater is directly connected to output Y21, the load current of the electric heater should be indicated in parameter P46. (RDG110, Index D and higher only). Default setting: 1 A for loads up to 1 A.

Setpoint and setpoint range limitation

  • We recommend reviewing the setpoints and setpoint ranges (parameters P08…P12) and change them as needed to achieve maximum comfort and save energy.

Disposal: The device is considered electrical and electronic equipment for disposal in terms of the applicable European Directive and may not be disposed of as domestic garbage.

  • Dispose of the device through channels provided for this purpose.
  • Comply with all local and currently applicable laws and regulations.

Technical data

RDG100../RDG110


RDG110U


RDG160T

http://siemens.com/bt/download

Connection terminals

  • L, N: Operating voltage AC 230 V
  • G, G0: Operating voltage AC/DC 24 V
    Note: For DC 24 V: G0 = –; G = +
  • X1, X2: Multifunctional input for temperature sensor (e.g. QAH11.1) or potential-free switch Factory setting:
    • X1: external room temperature sensor
    • X2: sensor or switch for heating/cooling changeover

Change of setting: Parameters P38, P40

  • M: Measuring neutral for sensor and switch
  • D1, GND: Multifunctional input for the potential-free switch.
    Factory setting: Operating mode switchover

Connection diagrams

  • Change of setting: Parameter P42
  • Q1: Control output fan speed “low”
  • Q2: Control output fan speed “medium”
  • Q3: Control output fan speed “high”
  • Y1…Y4: Control output “Valve” AC 230 V (NO, for normally open valves), output for electric heater via an external relay
  • Y11, Y21: Control output “Valve” AC 230 V for RDG110 Control output “Valve” AC 24 V for RDG110U (NO, for normally open valves), output for compressor or electric heater
  • Y12, Y22: Control output “Valve” AC 230 V for RDG110Control output “Valve” AC 24 V for RDG110U (NC, for normally closed valves)
  • G, G0: Operating voltage AC/DC 24 V Note: For DC 24 V: G0 = –; G = +
  • L (-N): Power supply relay output Q1…3 AC 24…230 V for RDG160T
  • Y10, Y20: Control output for DC 0…10 V actuator Y50 Control output “Fan” DC 0…10 V
  • Q1…3: Control output fan, valve, el. heater or ex. equipment

  • C (-G0): Power supply relay output Q1…3 AC 24 V for RDG160TU

Connection diagrams

RDG100..

  • N1: Room thermostat RDG100..
  • M1: 1-speed or 3-speed fan
  • V: Valve actuators:
    On/Off, heating, cooling, radiator, heating/cooling, 1st or 2nd stage
  • S1, S2: Switch (keycard, window contact, etc.)
  • S3: Switch at SELV input (keycard, window contact)
  • B1, B2: The temperature sensor (return air temperature, external room temperature, changeover sensor, floor temperature limit, etc.)
  • Q: Relay outputs
  • Y1…Y4: Triac outputs
  • YH: Heating valve actuator
  • YC: Cooling valve actuator
  • YHC: Heating/cooling valve actuator
  • YR: Radiator valve actuator
  • YE: Electric heater with relay/contactor

RDG110

  • N1: Room thermostat RDG110
  • M1: 1-speed or 3-speed fan
  • V: Valve actuators: On/Off, heating, cooling, radiator, heating/cooling, 1st or 2nd stage
  • S1, S2: Switch (keycard, window contact, etc.)
  • S3: Switch at SELV input (keycard, window contact)
  • B1, B2: The temperature sensor (return air temperature, external room temperature, changeover sensor, floor temperature limit, etc.)
  • Q: Relay outputs
  • Y11…Y22: Relay outputs
  • YH: Heating valve actuator
  • YC: Cooling valve actuator
  • YHC: Heating/cooling valve actuator
  • YR: Radiator valve actuator
  • YE: Electric heater max. 5 A
  • YHC1/YHC2: 1st/2nd stage
  • C1/C2: Compressor 1st and 2nd stage
  • RV: Reversing valve

RDG110U

  • N1: Room thermostat RDG110U
  • M1: 1-speed or 3-speed fan
  • V: Valve actuators:
  • On/Off, heating, cooling, radiator, heating/cooling, 1st or 2nd stage
  • S1, S2: Switch (keycard, window contact, etc.)
  • S3: Switch at SELV input (keycard, window contact)
  • B1, B2: The temperature sensor (return air temperature, external room temperature, changeover sensor, floor temperature limit, etc.)
  • Q: Relay outputs
  • Y11…Y22: Relay outputs
  • YH: Heating valve actuator
  • YC: Cooling valve actuator
  • YHC: Heating/cooling valve actuator
  • YR: Radiator valve actuator
  • YE: Electric heater max. 5 A
  • YHC1/YHC2: 1st/2nd stage
  • RV: Reversing valve
  • C1, C2: Compressor 1st/2nd stage

warning: For US installations, use Class 2-rated power supplies. For other installations, use circuit breakers with rated current of no more than 10 A.

  • N1: Room thermostat RDG160T
  • S1…S3: Switch (keycard, window contact, presence detector, etc.)
  • B1, B2: The temperature sensor (return air temperature, external room temperature, changeover sensor, etc.)
  • YE: Electric heater max. 5 A
  • C1, C2: Compressor 1st/2nd stage
  • M1: 1-speed or 3-speed fan, DC 0…10 V fan
  • V1, V2: Valve actuators: On/Off, DC 0…10 V, heating, cooling, radiator, 1st or 2nd stage
  • YH: Heating valve actuator
  • YC: Cooling valve actuator
  • YHC: Heating/cooling valve actuator
  • YHC1/YHC2: 1st/2nd stage
  • YR: Radiator valve actuator

RDG160TU

  • N1: Room thermostat RDG160TU
  • S1…S3: Switch (keycard, window contact, presence detector, etc.)
  • B1, B2: The temperature sensor (return air temperature, external room temperature, changeover sensor, etc.)
  • YR: Radiator valve actuator
  • YE: Electric heater max. 5 A
  • M1: 1-speed or 3-speed fan, DC 0…10 V fan
  • V1, V2: Valve actuators: On/Off, DC 0…10 V, heating, cooling, radiator, 1st or 2nd stage
  • YH: Heating valve actuator
  • YC: Cooling valve actuator
  • YHC: Heating/cooling valve actuator
  • YHC1/YHC2: 1st/2nd stage

warning: For US installations, use Class 2 rated power supplies. For other installations, use circuit breakers with a rated current of no more than 10 A.

Dimensions

© Siemens Switzerland Ltd, 2016 – 2018
Technical specifications and availability are subject to change without notice.

Issued by

REFERENCE:

DOWNLOAD MANUALS:

Please select text to grab.

wpx_thermostats

Recent Posts

Johnson Controls T7000e LCD Digital Thermostat Installation Guide

Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide

1 year ago

Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’S GUIDE

Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE

1 year ago

Hetta HS01RF WIRELESS THERMOSTAT KIT USER MANUAL

Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…

1 year ago

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat USER MANUAL

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…

1 year ago

Honeywell RLV450 PROGRAMMABLE THERMOSTAT USER GUIDE

Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…

1 year ago

Honeywell RLV431 Programmable Thermostat User Guide

Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…

1 year ago