Siemens RDF870KN Touch Screen Room Controller Thermostat Product Specifications Guide

Siemens RDF870KN Touch Screen Room Controller Thermostat

PM2.5 control, CO2 control, or both, and ventilation applications
RDF870KN (KNX) and RDF870MB (Modbus) controllers:

  • AC 230 V operating voltage, large, backlit display
  • Display and setpoint adjustment for PM2.5 and CO2 control
  • Display of room temperature, outside temperature, VOC (volatile organic compound) and r.h. (relative humidity)
  • Supports 1-/3-/4-speed On/Off fan or DC fan output
  • Two multifunctional inputs for external passive and DC 0…10 V sensors
  • Operating modes: Comfort, Economy and Protection
  • KNX S-Mode for RDF870KN
  • KNX commissioning via ETS or local control parameters
  • KNX integration into Design via group (ETS) or individual addressing
  • KNX integration into the third-party system via group addressing (ETS)
  • RS485 Modbus RTU slave mode for RDF870MB
  • Modbus commissioning via a third-party tool, e.g. Modbus scan, Modbus poll, etc.

RDF870MB can be configured as a room unit via DIP switches and it provides the following additional functions:

  • Setpoint adjustment and display for room temperature, VOC, RH and display of outside temperature
  • Four external outputs via bus and controlled by a master controller

Mounting on recessed square 86 mm box or round 60 mm with 60 mm fixing centers and minimum 40 mm depth

Use

Ventilation control in purifier systems:
Typical applications:

  • Residential apartments
  • Commercial buildings
  • Schools/Universities
  • Hospitals/Healthcare centers
    Local and remote configuration via one of the following:
  • Local HMI
  • DIP switch selection: room controller or room unit RDF870MB only
  • Third-party tool Modbus poll/Modbus scan RDF870MB only
  • ETS RDF870KN only

Functions
For room controllers

  • Maintain PM2.5 or CO2 level or both via controlling a fan of fresh air units or air purifiers
  • Display of room temperature via built-in temperature sensor or bus
  • Setpoint adjustment for PM2.5 and CO2 only
  • PM2.5 and CO2 values are received from external sensor or via bus.
  • CO2 control has higher priority than PM2.5 control if both controls are available.

For room unit

  • Display room temperature via built-in sensor in °C
  • Display outside temperature via bus or outside sensor input in °C
  • Display PM2.5 via bus or outside sensor input in μg/m3
  • Display CO2 via bus or outside sensor input in ppm
  • Display VOC via bus or outside sensor input in mg/m3 or %
  • Display relative humidity via bus or outside sensor input in % r.h.
  • Setpoint adjustments for all of the above

Common functionalities

  • Selection of operating modes
  • Minimum and maximum setpoint limitation
  • Fan speed adjustment: Auto, manual (up to 4 speeds)
  • Reload factory settings for commissioning, engineering mode and control parameters

Mechanical design

The room controller/room unit consists of the following parts:

  • Front panel with electronics, operating elements and built-in room temperature sensor
  • Mounting base with power electronics
  • The mounting frame is an additional part to complete the installation for RDF870…

Operation

Display

Status symbols

Selection symbols

Operational icons

Type summary

Product no. Stock no. Operating voltage Control outputs Suitable for
On/Off DC 0…10 V
RDF870KN S55770- T407 AC 230 V 4 1) 1 Square or round conduit box
RDF870MB S55770- T408 AC 230 V 4 1) 1 Square or round conduit box

Ordering

  • When ordering, indicate product number, SSN, and name. e.g. RDF870KN (S55770-T407) room controller
  • Order sensors separately.

Equipment combinations
Sensors

Type of units Product number Data sheet*)
Room sensor for detection of PM2.5

3-color LED service

indication

QSA2700 A6V11160938
Room sensor with LCD display for detection of PM2.5

2.4-inch color LCD screen

for PM2.5 values, air quality index, and service

QSA2700D A6V11160938
Type of units Product number Data sheet*)
Duct air quality sensor CO2/Temperature / rel. humidity / VOC QPM1100, QPM2100, QPM2102 N1962
Duct air quality sensor CO2/Temperature / rel. humidity / VOC QPM2102D N1962
Duct air quality sensor CO2/Temperature / rel. humidity / VOC QPM2160, QPM2180 N1962
Duct air quality sensor CO2/Temperature / rel. humidity / VOC QPM2160D, QPM2162D N1962

Product Documentation

Related documents such as environmental declarations, CE declarations, etc., can also be downloaded at the following Internet address: http://siemens.com/bt/download.

Title Document ID:
Operating instruction A6V11439451
CE declaration A5W90010366 (RDF870KN) A5W90010367 (RDF870MB)
Environmental product declaration A6V11625786

Notes

CAUTION: National safety regulations
Failure to comply with national safety regulations may result in personal injury and property damage.

  • Observe national provisions and comply with the appropriate safety regulations.

Engineering
See the product documentation for information on engineering, selection and sizing connecting cables for supply voltage and field devices.

Mounting and installation
Mount the room controller on a conduit box. Do not mount on a wall in niches or between bookshelves, behind curtains, above or near heat sources, wind outlets or inlets, and do not expose to direct solar radiation. Mount about 1.5 m above the floor.

  • Do not apply excessive force to screws! Deformation of the mounting frame may result in improper connections and faulty operation.
  • Mount the room controller in a clean, dry indoor place without direct airflow from a heating/ cooling device, not exposed to drips or splash water.
  • Before removing the front cover, disconnect the power supply.

WARNING No internal line protection for supply lines to external consumers Risk of fire and injury due to short-circuits

  • Adapt the line diameters as per local regulations to the rated value of the installed fuse.

See Operating Instruction for the installation instructions enclosed with room controller.

  • Comply with local regulations to wire, protect and earth the room controller.
  • The device has no internal fuse for supply lines to fan and actuators. To avoid risk of fire and injury due to short circuits, the AC 230 V mains supply line must have a circuit breaker with a rated current of no more than 10 A.
  • The wiring cross-section used for the power supply (L, N) and 230 V outputs (Qxx – N) must be adapted to the preceding overload protection elements (max. 10 A) under all circumstances. Always comply with local regulations.
  • Properly size the cables to the room controller and valve actuators for AC 230 V mains voltage.
  • Cables of SELV inputs X1-M / X2-M: Use cables with min. 230 V insulation, as the conduit box carries AC 230 V mains voltage.
  • Inputs X1-M or X2-M of different units (e.g. temperature sensor) may be connected in parallel with an external switch. Consider overall maximum contact sensing current for switch rating.
  • KNX communication cables (input CE+ / CE-): Use cables with Min. 230 V insulation, as the conduit box carries AC 230 V mains voltage. (Only for RDF870KN)
  • When a KNX bus power supply is connected on the line with communicating room controller and Synco controllers, the internal KNX power supply of the Synco controllers must be switched off. (Only for RDF870KN)
  • Isolate the cables of Modbus communication input A+, B- and REF for 230 V. (Only for RDF870MB)
  • No cables are provided with a metal shield.
  • Disconnect from supply before opening the cover.

Commissioning

After powering up, all LCD segments light up for about three seconds before the room controller enter its normal states. Address and application can be downloaded via ETS by pressing and holding for more than five seconds to enter programming mode. (Only for RDF870KN) The room controller and room unit can be set via DIP switches. (Only for RDF870MB)

DIP switch configuration

DIP switch positions Application
1 2
ON OFF Room unit
OFF OFF Room controller

DIP switch setting applies to RDF870MB only. The current factory setting for PM2.5 control with 3-speed on/off fan application is as follows:

  • APP= 1: PM2.5 control only
  • DISP: Room temp= 1; PM2.5= 1
  • SEN1= 3: PM2.5 (AI) μg/m3 (0…10 V)
  • SEN2= 0: no function
  • FAN= 3: 3-speed fan

Software version (RDF870KN)
Two different software versions of RDF870KN are available:

  • RDF870KN with software version (U101): Related ETS5 file (RDF870KN_v1d0_ETS5.knxprod)
  • RDF870KN with software version (U103): Related ETS5 file (RDF870KN_v1d1_ETS5.knxprod)

The software version can be checked as follows:

  • The software version relates to the production date (DDMMYYYY) on the individual package label or printed on the rear of the product.
    E.g. “DDMMYYYY = 02062019” equals “02 June 2019”
    • If YYYY = 2018, 2019 or 2020, the RDF870KN software version is “U101”.
    • IF YYYY = 2021 onwards, the RDF870KN software version is “U103”.
  • Checked under parameter mode:
    • Enter password 9999 after accessing parameter mode. For parameter mode access, see Parameter mode user access.
    • When the first parameter appears, press and hold until “SW” is displayed. Then related software version is shown as “U101” or “U103”.

Note For further support, please raise a support request via the site: https://support.industry.siemens.com/cs.

Disposal
The device is considered an electronic device for disposal in accordance with European Guidelines and may not be disposed of as domestic garbage.

  • Dispose of the device through channels provided for this purpose.
  • Comply with all local and currently applicable laws and regulations.

Warranty

Technical data on specific applications are valid only together with Siemens products listed under “Equipment combinations”. Siemens rejects any and all warranties in the event that third-party products are used.

Technical data

Power supply
Operating voltage AC 230 V
Frequency 50/60 Hz.
Power consumption Max. 7.0 VA / 2.5 W

CAUTION On internal fuse.
External preliminary line protection with max. C 10 A circuit breaker is required in all cases.

Multifunctional input X1-M/X2-M
Temperature sensor input: Type
Temperature range Accuracy Calibration range
NTC 10k
0…50 °C (32…122 °F)
±0.5 K at 25 °C (77 °F)
-5 K…5 K, resolution 0.5 K
Digital Input: Logic states
Insulation against mains voltage (SELV) Cable length
Selectable NO/NC
≥3.75 kV, reinforced insulation
Up to 80 m (wire diameter of 1.5 mm2))
Analog input Signal type
Sensor range and limit Cable length
0…10 V, NTC 10k
Set by parameters
Up to 80 m (wire diameter of 1.5 mm2))
Function of inputs
PM2.5 sensor, CO2 sensor, VOC sensor, humidity sensor, alarm input
Selectable X1: SEN1 X2: SEN2
Output
3/4 speed fan Q1…Q4
Type On/Off
Voltage AC 230 V
Maximum current 5(2) A
ECM fan Y50
Type Modulating
Voltage DC 0…10 V
Maximum current 5.0 mA

CAUTION If fans must be connected in parallel, connect one fan directly, for additional fans, one relay for each speed.

KNX interface
KNX type Bus current KNX TP1-64, galvanic isolation. 5 mA
Modbus interface
Modbus type RS485
Transmit mode RTU
Connection Support up to 32
Baud rate 9600, 19200 (default), 38400
Modbus address 1-247, 1 (default)
Cable length Max.1200 meters
Identity Slave
Transmission format (start bit – data – parity 0 = 1-8-E-1 (default) / 1 = 1-8-O-1 / 2 = 1-8-
– stop) N-1 / 3 = 1-8-N-2
Wiring connections
Diameter Wire 1.5 mm2
Solid or stranded
Ambient Conditions and protection classification
Classification as per EN 60730

Function of automatic control devices Degree of contamination Overvoltage category

Type 1

2

III

Design type Device suited for use with equipment of safety class II.
Degree of protection of housing to EN 60529 Room automation station

With terminal cover

IP30. IP30.
Climatic ambient conditions

Transport (packaged for transport) as per EN 60721-3-2

Operation as per EN 60721-3-3.

Class 2K3 Class 3K5 1)
Mechanical ambient conditions

Transport as per EN 60721-3-2 Operation as per EN 60721-3-3

Class 2M2. Class 3M2.
Standards, directives and approvals
Electromagnetic compatibility For residential, commercial, and industrial environments
EU conformity (CE) A5W90010366 (RDF870KN) *)

A5W90010367 (RDF870MB) *)

Standards, directives and approvals
RCM conformity A5W90010386 (RDF870KN) *)

A5W90010387 (RDF870MB) *)

REACH Regulation (EC) No 1907/2006 Registration, Evaluation, Authorisation and Restriction of Chemicals (REACH)
RoHS Directive 2011/65/EU restriction of the use of certain hazardous substances in electronic equipment
Environmental compatibility The product environmental declaration (A6V11625786 *) contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal).
General
Weight without/with package 165 g / 265 g
Housing front color Ivory white
Housing flammability class according to UL94 V-0

The documents can be downloaded from http://siemens.com/bt/download.

Diagrams

Connection terminals

RDF870KN RDF870MB
X1 Multifunction input 1
M Input reference ground for X1, X2 and Y50
X2 Multifunction input 2
Y50 DC 0…10 V output
CE+, CE- KNX bus + and – terminals
REF Modbus reference ground
A+, B- Modbus + and – terminals
L, N AC 230 V operating voltage
Q1 Output, fan speed 1, AC 230 V
Q2 Output, fan speed 2, AC 230 V
Q3 Output, fan speed 3, AC 230 V
Q4 Output, fan speed 4, AC 230 V

Connection diagrams

L, N AC 230 V operating voltage
X1, X2 Multifunctional inputs 1 & 2 (sensor, alarm, etc.)
M Input reference ground for X1, X2 and Y50
CE+, CE- KNX bus + and – terminals
Q1, Q2, Q3, Q4 Four speeds fan output (relay output)
Y50 DC 0…10 V output
REF Modbus reference ground
A+, B- Modbus + and – terminals
M1 1-speed, 3-speed or 4-speed fan, DC 0…10 V fan

Application examples

CO2 application (single duct single fan)
Single duct single fan fresh air unit or purifier with a built-in PM2.5 filter

RDF870… unit can be set up as a CO2 controller with an external CO2 sensor connected to X1 to control the fan for a fresh air unit (i.e. single duct single fan fresh air unit with/without PM2.5 built-in filter).
The fan speeds are switched as per the actual CO2 level and the CO2 setpoint. The built-in PM2.5 filter already purifies the outside air before entering indoors.

PM2.5 application (single duct single fan)
Single duct single fan purifier with built-in PM2.5 filter

RDF870… unit can be set up as a PM2.5 controller with an external PM2.5 sensor connected to X1 to control the fan for a PM2.5 purifier unit (i.e. single duct single fan purifier with PM2.5 built-in filter).
The purifier is not connected to external but installed on the ceiling. The purifier circulates in-door through its built-in PM2.5 filter. The fan speeds are switched as per the actual PM2.5 level and the PM2.5 setpoint.

CO2 application (dual duct parallel connected fan)
Dual duct parallel connected fan fresh air unit or purifier with a built-in PM2.5 filter

RDF870… unit can be set up as a CO2 controller with an external CO2 sensor connected to X1 to control the fan operation of a fresh air unit (i.e. dual duct parallel connected fan fresh air unit with/without PM2.5 built-in filter).

  • The fan speeds are switched as per the actual CO2 value and the CO2 setpoint.
  • The built-in PM2.5 filter already purifies the outside air before entering indoors.
  • This fresh air unit operates in a similar way as per single duct type. With the dual duct type, air exchange performance is better.
    CAUTION If fans must be connected in parallel, connect one fan directly, for additional fans, one relay for each speed.

PM2.5 & CO2 room unit application (dual duct independent fan control together with a master controller)
Dual duct independent fan fresh air unit or purifier with built-in PM2.5 filter via by-pass damper

RDF870… unit can be set up as a controller combining PM2.5 and CO2 control with an external PM2.5 and CO2 sensors connected to X1 and X2 respectively to control the fan for a fresh air unit and purifier (i.e. dual duct independent fan fresh air unit with PM2.5 built-in filter via by-pass damper). The damper can be disabled (inlet open and by-pass close) or enabled (by-pass open) via an extra damper input from a master controller. When the by-pass damper is inactive, the outside air can enter the room via the inlet that is controlled by a master. The fan speeds are switched as per the actual CO2 level and the CO2 setpoint.

When the by-pass damper is active via control input from a master controller, the inlet is disabled by the master controller, and outside air is blocked. As a result, all the exhaust air (or partially) will be forced to flow via the bypass PM2.5 filter and return to the room– air circulates internally. The fan speeds are switched as per the actual PM2.5 level and the PM2.5 setpoint. If both fans have the same fan speed, airflow circulates internally. However, two fans also can be operated at different speeds to generate different air pressures internally.

Parameters

Parameter mode user access 

  1. Touch & hold icon > 5 s
  2. Enter first password via or.
  3. Enter the second password via or.
  4. After 6 seconds
  5. Edit parameters
  6. Exit parameter mode

Engineering parameters

Item Description Range Factory settings
MODA Modbus address setting 1…247 1
MODB Modbus baud rate setting 1: 9600 bps
2: 19200 bps
3: 38400 bps
2: 19200 bps
MODF Modbus data frame format 0: 1/8/E/1
1: 1/8/O/1
2: 1/8/N/1
3: 1/8/N/2
0: 1/8/E/1
APP Application selection 1: PM2.5 control only
2: PM2.5 + CO2 control 3: CO2 control only
4: Ventilation
1: PM2.5 control only
DISP Symbol display enable/disable 0: Disable display
1: Enable display
1)  Room temp= 1;
2)  Outside temp= 0; 3) PM2.5= 1;
4) VOC= 0; 5) CO2= 0; 6) RH= 0;
SEN1 1) External sensor1 type selection 0: No function
1: Temperature (AI) (NTC 10k) 2: Temperature (AI) (0…10 V) 3: PM2.5 (AI) μg/m3 (0…10 V)
4: CO2 (AI) ppm (0…10 V)
5: VOC (AI) % (0…10 V)
6: VOC (AI) mg/m³ (0…10 V)
7: R.h. (AI) % (0…10 V)
8: Alarm input (DI)
9: Dummy AI (0…10 V) (RU only) 10: Dummy DI (RU only)
3: PM2.5 (AI) μg/m3 (0…10 V)
DIL1 Control action if digital input 0: Normally open / Open
1: Normally closed / Closed
0: Normally open / Open
SEN2 1) External sensor2 type selection 0: No function
1: Temperature (AI) (NTC 10k) 2: Temperature (AI) (0…10 V) 3: PM2.5 (AI) μg/m3 (0…10 V)
4: CO2 (AI) ppm (0…10 V)
5: VOC (AI) % (0…10 V)
6: VOC (AI) mg/m³ (0…10 V)
7: R.h. (AI) % (0…10 V)
8: Alarm input (DI)
9: Dummy AI (0…10 V) (RU only) 10: Dummy DI (RU only)
0: No function
DIL2 Control action if digital input 0: Normally open / Open

1: Normally closed / Closed

0: Normally open / Open
PMH PM2.5 sensor high range Max. of low range…1000 500
PML PM2.5 sensor low range 0…Min. of high range 0
CO2H CO2 sensor high range Max. of low range…2000 2000
CO2L CO2 sensor low range 0…Min. of high range 0
UOCH VOC sensor high range Max. of low range…100 5
UOCL VOC sensor low range 0…Min. of high range 0
HUMH Humidity sensor high range Max. of low range…100 100
HUML Humidity sensor low range 0…Min. of high range 0
Item Description Range Factory settings
TEMH Temperature sensor high range Max. of low range…100 50
TEML Temperature sensor low range -50…Min. of high range 0
SPMH PM2.5 setpoint high range Max. of low range…500 100
SPML PM2.5 setpoint low range 0…Min. of high range 12
SPCH CO2 setpoint high range Max. of low range…2000 1500
SPCL CO2 setpoint low range 0…Min. of high range 500
FAN Fan type selection 1: 1-speed fan (ON/OFF)
3: 3-speed fan
4: 4-speed fan
5: ECM fan
3: 3-speed fan
ECMH ECM fan output limit high Max. of ECML…100 % 80 %
ECML ECM fan output limit low 0…Min. of ECMH 30 %
TC Filter time display setting 0: Disable

1: Enable

0: Disable
PMES 2) PM2.5 ECO mode setpoint 0…100 60
COES 2) CO2 ECO mode setpoint 500…1500 1000
BUZZ Buzzer function 0: Disable
1: Enable
1: Enable
UNIT Temperature unit 0: °C (degrees Celsius)
1: °F (degrees Fahrenheit)
0: °C (degrees Celsius)
LOCK Keylock function 0: Unlock
1: Locked
2: Setpoint only
3: Operating mode only
4: Setpoint and fan speed only
0: Unlock
OPSL Operating mode selection 0: ON/OFF
1: ON/ECO/OFF
2:ON/ECO/Protection/OFF (RU only)
3: ON/ECO/Protection (room unit only)
1: ON/ECO/OFF
CALT Internal temperature sensor calibration -5…5 K 0

RDF870KN available parameters and their order of appearance:

  • Room controller: APP > DISP > SEN > FAN > OPSL > TC > UNIT > LOCK > BUZZ > CALT > APP RDF870MB available parameters and their order of appearance:
  • Room controller: MODA > MODB > MODF >APP > DISP > SEN > FAN > OPSL > TC > UNIT > LOCK > BUZZ > CALT > MODA
  • Room unit: MODA > MODB > MODF > LOCK > BUZZ > CALT > MODA
  1. Room controller: 0…8; Room unit: 0…10
  2. The setpoint cannot be changed in ECO mode.

Restriction for sensor selection:

  1. If SEN1 and SEN2 are configured with the same selection type 1…8, they cannot be the same sensor types:
    • For type 1…8, sensor1 cannot be the same as sensor2.
    • For sensor types with the same function such as 1&2 or 5&6, if one sensor type is 1 or 5, the other one cannot be 2 or 6.
      Note: When APP = 2 (both PM2.5 and CO2 control) is selected, FAN = 1 or 3 only.

Firmware setpoint settings

Item Description Range Factory settings
TCSP Filter time setting 0…9999 8760
PM2.5 SP PM2.5 setpoint SPML…SPMH 60
CO2 SP CO2 setpoint SPCL…SPCH 1000
T SP Temperature setpoint T SP L…T SP H 24
T SP H Temperature setpoint range high Max. of low range…200 (°C) 50
T SP L Temperature setpoint range low -50…Min. of high range (°C) 5
VOC SP VOC setpoint %: 0…100 mg/m3: 0…5 0.6 mg/m3 or 6 %
HUM SP Humidity setpoint 0…100 % 50 %
P81 1) Device address (KNX only) 1…255 255
  • During power-up, there is a startup delay (TwaitDevice = tWaitMin + DeviceAdr * 200ms) before the processing signal is processed.
  • When P81=255 (default), the device does not process the signal according to the heartbeat and COV mechanism. But it can respond when another device is polling.
  • The local HMI does not support P81.
  • When the individual address is changed via ETS, P81 is updated automatically after the device downloads it from ETS.

Expert mode parameters

Item Description Range Factory settings
PMP PM2.5 control factor Xp 0…1000 50
PMI PM2.5 Control factor Tn 0…120 min 45 min
CO2P CO2 control factor Xp 0…2000 100
CO2I CO2 control factor Tn 0…120 min 45 min
PMDB PM2.5 control loop deadband 0…20 10
CODB CO2 control loop deadband 0…100 50
OPAF Operating mode settings after power failure/reset 0: Return to the previous operating mode/user setting

1: Off

0: Return to the previous operating mode/user setting
FANT Fan minimum on time 1…6 min 2 min
FSET Reload factory settings 0: OFF = Disable
1: ON = Reload start“–”“—”“—– ” is displayed while reloading
0: OFF = Disable
SW Software version
EPAS Engineer mode password 0000…4999 0000
XPAS Expert mode password 5000…9999 9999

Room controller workflow: EPAS > XPAS > PMP > PMI > PMDB > CO2P > CO2I > CODB > OPAF > FANT > FSET > SW > EPAS RDF870MB Room unit workflow: EPAS > XPAS > SW > EPAS

Other parameters (RDF870MB room unit only)

Item Description Range Factory settings
Output 1 (Q1) Output for external Modbus controller (master) 0: Off

1: On

0: Off
Output 2 (Q2) Output for external Modbus controller (master) 0: Off

1: On

0: Off
Output 3 (Q3) Output for external Modbus controller (master) 0: Off

1: On

0: Off
Output 4 (Q4) Output for external Modbus controller (master) 0: Off

1: On

0: Off

KNX S-Mode communication objects (RDF870KN)

Overview

Description of communication objects

Object no. Object name Function Type/length Flags
1 Fault information Alarm information 219.001

6 Byte

CT
Common alarm output. If an alarm occurs, the alarm number is transmitted.
2 Fault state Faulty/normal 1.005

1 bit

CT
Common alarm output. If an alarm occurs, the alarm flag is set.
3 Enable alarm info Enable/disable 1.003

1 bit

CWU
A supervisor alarm system can disable the broadcasting of alarms by the devices. This has no impact on the local display of alarms. After a timeout of 48 hours, the sending of faults is automatically enabled again.
4 Room operating mode user: Preselection Comfort Economy OFF 20.102

1 Byte

CWTU
Controls the room operating mode selection of the room controller/room unit via bus.
The command can also be submitted as three 1-bit communication objects (5…7). The last interaction wins-either from the local operating mode button or via bus.
Note: 8-bit and 1-bit objects available, selectable by using parameters in ETS

 

5

6

7

Operating mode user: Preselection

–  Comfort

–  Eco

–  Protection

ON OFF 1.001

1 bit

CW
Switch room operating mode to either Comfort, Economy or OFF.
The last interaction wins – either from local operating mode button or via bus.
Note: 8-bit and 1-bit object available, selectable by using parameters in ETS
8 Room operating mode: State Comfort Economy Off 20.102

1 Byte

CRT
Effective room operating mode used by the thermostat (considering timer, user selection, etc.) This state information is available via one 8-bit enumeration or three 1-bit communication objects (9…11).
Note: 8-bit and 1-bit object available, selectable by using parameters in ETS

9

10

11

Room operating mode:

–  State Comfort

–  State Eco

–  State Protection

ON OFF 1.001

1 bit

CT
The corresponding communication object sends “True”
Note: 8-bit and 1-bit object available, selectable by using parameters in ETS
12 Room temperature Temperature value 9.001

2 Bytes

CRT
Value of the room temperature.

Note: The room temperature value is decided by priority if all value types exist. (Built-in > Remote)

13 Remote: Indoor temperature Temperature value 9.001
2 Bytes
CWU
Remote indoor temperature sensor value
14 Outdoor temperature Temperature value 9.001
2 Bytes
CRT
Value of the outside temperature is received.
Object no. Object name Function Type/length Flags
Note: Outside temperature value is decided by the priority order if all value types exist. (X1/X2 > Remote)
15 Remote: Outdoor temperature Temperature value 9.001

2 Bytes

CWU
Remote outside temperature sensor value
16 PM2.5 setpoint user AQ Setpoint value 9.030

2 Bytes

CWTU
One AQ setpoint value from a HMI.

Same priority as local setpoint shift on the thermostat. The last intervention wins.

17 CO2 setpoint user AQ Setpoint value 9.008

2 Bytes

CWTU
One AQ setpoint value from an HMI.
Same priority as local setpoint shift on the thermostat. The last intervention wins.
18 PM2.5 current setpoint AQ Setpoint value 9.030

2 Bytes

CRT
Effective AQ setpoint, used for PM2.5 control.
19 CO2 current setpoint AQ Setpoint value 9.008

2 Bytes

CRT
Effective AQ setpoint, used for CO2 control.
20 X: Temperature Temperature value 9.001

2 Bytes

CRT
Indicate the values of the temperature sensors connected to the local inputs X1 / X2. Note: Available only when X1/X2 set as temperature.
21 X: Digital input ON OFF 1.001

1 bit

CRT
Indicate the status of the digital inputs (adjusted by parameters SEN / DIL) including considering of operating action.

Note: Available only when X1/X2 set as Filter alarm input

22 Room humidity Humidity value 9.007

2 Bytes

CRT
Indicate the value of the room humidity value
Note: Room humidity value, the priority order is X1/X2 > Remote
23 Remote: Humidity Humidity value 9.007

2 Bytes

CWU
Remote humidity sensor value
24 Room CO2 Room AQ value 9.008

2 Bytes

CRT
Indicate the value of the room CO2 value

Note: Room CO2 value, priority order is X1/X2 > Remote

25 Room PM2.5 Room AQ value 9.030

2 Bytes

CRT
Indicate the value of room PM2.5 value

Note: Room PM2.5 value, priority order is X1/X2 > Remote

26 Room VOC[mg/m3] Room AQ value 9.030

2 Bytes

CRT
Object no. Object name Function Type/length Flags
Indicate the value of the room VOC value

Note: Room VOC value, the priority order is X1/X2 > Remote

27 Room VOC[%] Room AQ value 5.004

2 Bytes

CRT
Indicate the value of the room VOC value

Note: Room VOC value, priority order is X1/X2 > Remote

28 Remote: PM2.5 AQ value 9.030

2 Bytes

CWU
Remote PM2.5 value
29 Remote: CO2 CO2 value 9.008

2 Bytes

CWU
Remote CO2 value
30 Remote: VOC[mg/m3] AQ value 9.030

2 Bytes

CWU
Remote VOC value
31 Remote: VOC[%] AQ value 5.004

2 Bytes

CWU
Remote VOC value
32 Fan command user 0…100% 5.001

8 bit

CWU
The fan can be set to a specified speed by a KNX control unit when manual fan operation is enabled.
Note:
1) Fan speed “0” is not supported by the thermostat and the fan speed will remain unchanged.
33 Enable fan command value Enable Disable 1.003

1 bit

CWU
Set fan mode to Auto (disable) or Manual (enable) by a KNX control unit. If Manual, the value received on Fan command value (32) will be used to command the fan speed.
Default: Enable
The last interaction wins – either from the local fan mode button or via bus.
34 Fan operation Auto Manual 1.011

1 bit

CRT
Indicates the fan operation mode: Auto (0) or Manual (1).
35

36

37

38

Fan speed 1 output Fan speed 2 output Fan speed 3 output Fan speed 4 output ON OFF 1.011

1 bit

CRT
Indicate the state of the relay outputs
39 ECM fan output 0…100% 5.001

8 bit

CRT
Indicates the current fan speed as a value 0…100%
Note: Available only when ECM fan type has been selected.

Modbus communication objects (RDF870MB)

Description of communication objects

Read Write
Object no. Object Register Address (Decimal) Object length (bytes) Read only (RO) or Read/Write (RW) Function code

0x03–Read Single Holding Register 0x04–Read RO Register

0x06–Write Single Holding Register

Multi Register Group Identification Special process Default Value Data Value Range
1 Modbus address 40001 1 RW 0x03 0x06 1 1 1…247
2 Modbus baudrate 40002 1 RW 0x03 0x06 1 2 1: 9600bps

2: 19200bps

3: 38400bps

3 Modbus format 40003 1 RW 0x03 0x06 1 0 0: 1/8/E/1

1: 1/8/O/1

2: 1/8/N/1

3: 1/8/N/2

4 Application 40004 1 RW 0x03 0x06 1 1 1: PM2.5 control only 2: PM2.5 + CO2 control 3: CO2 control only

4: Ventilation

5 Room temperature symbol enable 40005 1 RW 0x03 0x06 1 1 0: Disable display

1: Enable display

6 Outdoor temperature symbol enable 40006 1 RW 0x03 0x06 1 0 0: Disable display

1: Enable display

7 PM2.5 symbol enable 40007 1 RW 0x03 0x06 1 1 0: Disable display

1: Enable display

8 VOC symbol enable 40008 1 RW 0x03 0x06 1 0 0: Disable display

1: Enable display

9 CO2 symbol enable 40009 1 RW 0x03 0x06 1 0 0: Disable display

1: Enable display

10 Humidity symbol enable 40010 1 RW 0x03 0x06 1 0 0: Disable display

1: Enable display

11 Reserved 1 40011 1 RW 0x03 0x06 1 0 0…ffff
12 1) External sensor 1 type selection 40012 1 RW 0x03 0x06 1 3 0: (no function)

1: Temperature (AI) (NTC 10k) 2: Temperature (AI) (0…10 V) 3: PM2.5 (AI) (0…10 V)

4: CO2 (AI) (0…10 V)

5: VOC (AI) % (0…10 V)

6: VOC (AI) mg/m³ (0…10 V)

7: rH (AI) (0…10 V)

8: Alarm input (DI)

9: Dummy AI (0…10 V) (Room unit only)

10: Dummy DI (Room unit only)

13 2) External sensor 1 DI action 40013 1 RW 0x03 0x06 1 0 0: Normally open / Open 1: Normally closed / Close
Read Write
Object no. Object Register Address (Decimal) Object length (bytes) Read only (RO) or Read/Write (RW) Function code

0x03–Read Single Holding Register 0x04–Read RO Register

0x06–Write Single Holding Register

Multi Register Group Identification Special process Default Value Data Value Range
14 1) External sensor 2 type selection 40014 1 RW 0x03 0x06 1 0 0: (no function)

1: Temperature (AI) (NTC 10k)
2: Temperature (AI) (0…10 V)
3: PM2.5 (AI) (0…10 V)
4: CO2 (AI) (0…10 V)

5: VOC (AI) % (0…10 V)

6: VOC (AI) mg/m³ (0…10 V)

7: rH (AI) (0…10 V)

8: Alarm input (DI)

9: Dummy AI (0…10 V) (Room unit only)

10: Dummy DI (Room unit only)

15 3) External sensor 2 DI action 40015 1 RW 0x03 0x06 1 0 0: Normally open / Open 1: Normally closed / Close
16 4) Temperature range high 40016 1 RW 0x03 0x06 1 x100 50 Max. of low range…100
17 4) Temperature range low 40017 1 RW 0x03 0x06 1 x100 0 -50…Min. of high range
18 4) PM2.5 range high 40018 1 RW 0x03 0x06 1 500 Max. of low range…1000
19 4) PM2.5 range low 40019 1 RW 0x03 0x06 1 0 0…Min. of high range
20 4) CO2 range high 40020 1 RW 0x03 0x06 1 2000 Max. of low range…2000
21 4) CO2 range low 40021 1 RW 0x03 0x06 1 0 0…Min. of high range
22 4) VOC range high 40022 1 RW 0x03 0x06 1 x10 5) 5mg or

50 %

Max. of low range…100
23 4) VOC range low 40023 1 RW 0x03 0x06 1 0 0…Min. of high range
24 4) Humidity range high 40024 1 RW 0x03 0x06 1 100 Max. of low range…100
25 4) Humidity range low 40025 1 RW 0x03 0x06 1 0 0…Min. of high range
26 Reserved 2 40026 1 RW 0x03 0x06 1 0 0…ffff
27 PM2.5 setpoint high range 40027 1 RW 0x03 0x06 1 100 Max. of low range…500
28 PM2.5 setpoint low range 40028 1 RW 0x03 0x06 1 12 0…Min. of high range
29 CO2 setpoint high range 40029 1 RW 0x03 0x06 1 1500 Max. of low range…2000
30 CO2 setpoint low range 40030 1 RW 0x03 0x06 1 500 0…Min. of high range
31 Fan type 40031 1 RW 0x03 0x06 1 3 1: On/Off fan

3: 3-speed fan

4: 4-speed fan

5: ECM fan

32 ECM fan output limit LOW 40032 1 RW 0x03 0x06 1 30 0…Min. of high range
33 ECM fan output limit HIGH 40033 1 RW 0x03 0x06 1 80 Max. of low range…100%
34 Filter time display setting 40034 1 RW 0x03 0x06 1 0 0: disable

1: enable

Read Write
Object no. Object Register Address (Decimal) Object length (bytes) Read-only (RO) or Read/Write (RW) Function code

0x03–Read Single Holding Register 0x04–Read RO Register

0x06–Write Single Holding Register

Multi Register Group Identification Special process Default Value Data Value Range
35 6) PM2.5 ECO setpoint 40035 1 RW 0x03 0x06 1 60 0…100
36 6) CO2 ECO setpoint 40036 1 RW 0x03 0x06 1 1000 500…1500
37 Reserved 3 40037 1 RW 0x03 0x06 1 0 0…ffff
38 Buzzer 40038 1 RW 0x03 0x06 1 1 0: Disable

1: Enable

39 Temperature unit 40039 1 RW 0x03 0x06 1 0 0: °C (degrees Celsius)

1: °F (degrees Fahrenheit)

40 7) Keylock 40040 1 RW 0x03 0x06 1 0 0: Unlock

1: Locked

2: Setpoint only

3: Operating mode only

4: Setpoint and fan speed only

41 Operation mode 40041 1 RW 0x03 0x06 1 1 0: ON/OFF

1: ON/ECO/OFF

2: ON/ECO/Protection/OFF (Room unit only)

3: ON/ECO/Protection (Room unit only)

42 Calibration internal T sensor 40042 1 RW 0x03 0x06 1 x100 0 -5…+5 in K
43 Reserved 4 40043 1 RW 0x03 0x06 1 0 0…ffff
44 PM2.5 factor Xp 40044 1 RW 0x03 0x06 1 50 0…1000
45 PM2.5 factor Tn 40045 1 RW 0x03 0x06 1 45 0…120 mins
46 PM2.5 deadband 40046 1 RW 0x03 0x06 1 10 0…20
47 CO2 factor Xp 40047 1 RW 0x03 0x06 1 100 0…2000
48 CO2 factor Tn 40048 1 RW 0x03 0x06 1 45 0…120 mins
49 CO2 deadband 40049 1 RW 0x03 0x06 1 50 0…100
50 Reserved 5 40050 1 RW 0x03 0x06 1 0 0…ffff
51 Operation mode power failure 40051 1 RW 0x03 0x06 1 0 0: Return to the previous operating mode / User setting

1: Off

52 Fan minimum on time 40052 1 RW 0x03 0x06 1 2 1…6
53 Reload factory setting 40053 1 RW 0x03 0x06 1 0 0=OFF: Disable

1=ON: Reload factory setting

54 Engineer mode password 40054 1 RW 0x03 0x06 1 0000 0000…4999
55 Expert mode password 40055 1 RW 0x03 0x06 1 9999 5000…9999
56 Reserved 6 40056 1 RW 0x03 0x06 1 0 0…ffff
57 Software version 30001 1 RO 0x04 4 0000…9999
58 Filter time counter setpoint 40100 1 RW 0x03 0x06 2 8760 0…9999
Read Write
Object no.

Object

Register Address (Decimal) Object length (bytes) Read only (RO) or Read/Write (RW) Function code

0x03–Read Single Holding Register 0x04–Read RO Register

0x06–Write Single Holding Register

Multi Register Group Identification Special process Default Value Data Value Range
59 PM2.5 setpoint 40101 1 RW 0x03 0x06 2 60 SPML…SPMH
60 CO2 setpoint 40102 1 RW 0x03 0x06 2 1000 SPCL…SPCH
61 Local DO1 40103 1 RW 0x03 0x06 2 0 0: Off:

1: On

62 Local DO2 40104 1 RW 0x03 0x06 2 0 0: Off:

1: On

63 Local DO3 40105 1 RW 0x03 0x06 2 0 0: Off:

1: On

64 Local DO4 40106 1 RW 0x03 0x06 2 0 0: Off:

1: On

65 Room temperature source 40107 1 RW 0x03 0x06 2 1 0: Built-in temperature; 1: Remote
66 Current working mode 40108 1 RW 0x03 0x06 2 1 0: OFF;

1: ON;

2: ECO;

3: Protection (Room unit only)

67 Model name 30002 1 RO 0x04 4 0: Modbus model; 1: KNX model
68 Model type 30003 1 RO 0x04 4 0: Room controller; 1: Room unit
69 Room temperature present value 30004 1 RO 0x04 4
70 Outdoor temperature present value 30005 1 RO 0x04 4
71 PM2.5 present value 30006 1 RO 0x04 4
72 CO2 present value 30007 1 RO 0x04 4
73 VOC present value 30008 1 RO 0x04 4
74 Humidity present value 30009 1 RO 0x04 4
75 Alarm present value 30010 1 RO 0x04 4 0: No alarm;

1: Have an alarm

76 Room temperature 30011 1 RO 0x04 4 x100 0 0…50 °C
77 Outdoor temperature 30012 1 RO 0x04 4 x100 0 -50…200 °C
78 8) PM2.5_External 30013 1 RO 0x04 4 0 0…1000
79 8) CO2_External 30014 1 RO 0x04 4 0 0…2000
80 8) VOC_External 30015 1 RO 0x04 4 0 0…10 mg/m3;

0…100 %

81 8) Humidity_External 30016 1 RO 0x04 4 0 0…100 %
82 8) Alarm_External 30017 1 RO 0x04 4 0: OPEN;

1: CLOSE;

2: Invalid

83 Dummy_DI_X1 30018 1 RO 0x04 4 0: OPEN;

1: CLOSE;

Read Write
Object no.

Object

Register Address (Decimal) Object length (bytes) Read-only (RO) or Read/Write (RW) Function code

0x03–Read Single Holding Register 0x04–Read RO Register

0x06–Write Single Holding Register

Multi Register Group Identification Special process Default Value Data Value Range
2: Invalid
84 Dummy_DI_X2 30019 1 RO 0x04 4 0: OPEN;

1: CLOSE;

2: Invalid

85 Dummy_AI_X1 30020 1 RO 0x04 4 x1000 0…10 V value
86 Dummy_AI_X2 30021 1 RO 0x04 4 x1000 0…10 V value
87 8) Room temperature_Remote 40109 1 RW 0x03 0x06 2 x100 0 -50…200 °C; Use 32767 as non- valid value
88 8) Outdoor temperature_Remote 40110 1 RW 0x03 0x06 2 x100 0 -50…200 °C; Use 32767 as non- valid value
89 8) PM2.5_Remote 40111 1 RW 0x03 0x06 2 0 0…1000; Use 32767 as a non-valid value
90 8) CO2_Remote 40112 1 RW 0x03 0x06 2 0 0…2000; Use 32767 as a non-valid value
91 8) VOC_Remote 40113 1 RW 0x03 0x06 2 0 x10 for 0.0…10.0 mg/m3 plus 128, it means use 128…228 stand for 0.0…10.0 mg/m3;

0…100 %; Use 0…100 to stand for 0…100 %;

Use 127 as non-valid value

92 8) Humidity_Remote 40114 1 RW 0x03 0x06 2 0 0…100 %;

Use 127 as non-valid value

93 Fan1 speed 40115 1 RW 0x03 0x06 2 0 0…1 for 1 speed fan; 0…3 for 3 speed fan; 0…4 for 4 speed fan; 0…100 for ECM fan
94 Fan 1 status 40116 1 RW 0x03 0x06 2 0 0: Auto;

1: Manual

95 Fan 2 speed 40117 1 RW 0x03 0x06 2 0 0…1 for 1 speed fan; 0…3 for 3 speed fan; 0…4 for 4 speed fan; 0…100 for ECM fan
96 Fan 2 status 40118 1 RW 0x03 0x06 2 0 0: Auto;

1: Manual

97 Alarm value display 40119 1 RW 0x03 0x06 2 0 0: Disable

If alarm value ≥1, user can define

the error code display in RU.

98 Alarm information 30022 1 RO 0x04 4 0 0: No alarm;

Any bit set to 1 means there is alarm or error defined as below: Bit0: KNX bus error;

Bit1: KNX ADR error; Bit2: AL1;

Read Write
Object no. Object Register Address (Decimal) Object length (bytes) Read only (RO) or Read/Write (RW) Function code

0x03–Read Single Holding Register 0x04–Read RO Register

0x06–Write Single Holding Register

Multi Register Group Identification Special process Default Value Data Value Range
Bit3: AL2;

Bit4: Clean filter;

Bit5: Built-in sensor error; Bit6: EEPROM error; Bit7: X1/X2 error

99 PM2.5 sensor status 30023 1 RO 0x04 4 0 0: Normal status;

1: Module error;

2: Communication error

100 External PM2.5 sensor module error 30024 1 RO 0x04 4 0 0: No error;

1: Error

101 External PM2.5 sensor communication error 30025 1 RO 0x04 4 0 0: No error;

1: Error

102 Reserved 30026 4 0 0…ffff
103 Clean filter reminder 30027 1 RO 0x04 4 0 0: No reminder;

1: Reminder

104 Internal sensor error 30028 1 RO 0x04 4 0 0: No error;

1: Error

105 EEPROM error 30029 1 RO 0x04 4 0 0: No error;

1: Error

106 Filter counter value 30030 1 RO 0x04 4 0 0…9999
107 Room temperature setpoint 40200 1 RW 0x03 0x06 3 x100 24 Temp SP L…Temp SP H
108 VOC setpoint 40201 1 RW 0x03 0x06 3 0.6 x10 for 0.0…5.0 mg/m3; 0…100 for %
109 Humidity setpoint 40202 1 RW 0x03 0x06 3 50 0…100 %
110 Temp SP H 40203 1 RW 0x03 0x06 3 x100 50 Max. of low range…200
111 Temp SP L 40204 1 RW 0x03 0x06 3 x100 5 -50…Min. of high range
112 Idle page display 40205 1 RW 0x03 0x06 3 3 0: — (no function or no any configured function available) 1: Room temperature value 2: Outside temperature value 3: PM2.5 value

4: CO2 value

5: VOC value

6: Relative humidity value

113 Function selection for room temperature 40206 1 RW 0x03 0x06 3 2 0: Disable

1: Enable without setpoint 2: Enable with setpoint

114 Function selection for outside temperature 40207 1 RW 0x03 0x06 3 1 0: Disable

1: Enable

115 Function selection for PM2.5 40208 1 RW 0x03 0x06 3 0 0: Disable

1: Enable without setpoint

Read Write
Object no. Object Register Address (Decimal) Object length (bytes) Read-only (RO) or Read/Write (RW) Function code 0x03–Read Single Holding Register 0x04–Read RO Register 0x06–Write Single Holding Register Multi Register Group Identification Special process Default Value Data Value Range
2: Enable with setpoint
116 Function selection for VOC 40209 1 RW 0x03 0x06 3 0 0: Disable

1: Enable without setpoint 2: Enable with setpoint

117 Function selection for CO2 40210 1 RW 0x03 0x06 3 0 0: Disable

1: Enable without setpoint 2: Enable with setpoint

118 Function selection for humidity 40211 1 RW 0x03 0x06 3 0 0: Disable

1: Enable without setpoint 2: Enable with setpoint

119 Function selection for FAN 40212 1 RW 0x03 0x06 3 1 0: Disable

1: 1 Fan

2: 2 Fan

120 Heating / Cooling / Ventilation status display 40213 1 RW 0x03 0x06 3 0 0: Disable

1: Heating only

2: Cooling only

3: Ventilation

4: Aux heating

  1. If SEN1 and SEN2 are configured with the same selection type 1…8, they cannot be the same sensor types:
    • For type 1…8, sensor1 cannot be the same as sensor2.
    • For sensor types with the same function such as 1&2 or 5&6, if one sensor type is 1 or 5, the other one cannot be 2 or 6.
  2. Displays only when SEN1 is set to DI
  3. Displays only when SEN2 is set to DI
  4. Depends on settings of SEN1 and SEN2
  5. Only for unit μg/m3
  6. The setpoint cannot be changed in ECO mode.
  7. When the value is 0, the lock icon is not displayed. When other values are selected, the icon is displayed.
  8. The difference between external and remote:
    • Object name with external indicates the status, values of the connected sensors via inputs X1, X2, M.
    • Object name with remote indicates the values received from master controller.
    • If the values from master controller, external sensors and built-in sensor exist simultaneously, display priority of value on device is master controller > external sensors > built-in sensor.

Dimensions (mm)

Issued by
Siemens Switzerland Ltd
Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug
+41 58 724 2424
www.siemens.com/buildingtechnologies

© Siemens Switzerland Ltd, 2019 Technical specifications and availability are subject to change without notice.

Reference:

DOWNLOAD MANUALS:

Siemens RDF870KN Touch Screen Room Controller Thermostat Product Specifications Guide

Siemens RDF870KN Touch Screen Room Controller Thermostat Product Specifications Guide

wpx_thermostats

Recent Posts

Johnson Controls T7000e LCD Digital Thermostat Installation Guide

Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide

1 year ago

Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’S GUIDE

Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE

1 year ago

Hetta HS01RF WIRELESS THERMOSTAT KIT USER MANUAL

Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…

1 year ago

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat USER MANUAL

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…

1 year ago

Honeywell RLV450 PROGRAMMABLE THERMOSTAT USER GUIDE

Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…

1 year ago

Honeywell RLV431 Programmable Thermostat User Guide

Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…

1 year ago