SIEMENS

Siemens RDF870KN Touch Screen Room Controller Thermostat Operating Instruction

Siemens RDF870KN Touch Screen Room Controller Thermostat

Introduction

Reference pages Terminals Description
RDF870KN RDF870MB

Application

L, N

 

Q1, Q2, Q3, Q4

L, N

 

Q1, Q2, Q3, Q4

AC 230 V operating voltage

Fan relay with max four speeds outputs

X1, X2

M

X1, X2

M

Multifunctional inputs 1 & 2

Input reference ground

Installation Y50 Y50 DC 0…10 V output

Parameters

CE+, CE-

A+, B- REF

KNX bus + and – terminals Modbus + and – terminals

Modbus reference ground

Symbols

Status symbols

Selection symbols

Operational icons

Commissioning

Download via ETS

Note: This operation applies to RDF870KN only.

  1. Screen idle
  2. Touch digits/screen
  3. Normal display
  4. Touch & hold the icon > 5 s to enter Programming mode
  5. Ready for downloading address & application

Commissioning: Local via DIP switches

  1. Set application via DIP switches
    • Refer to
  2. Configure basic control parameters
DIP switch positions

Application

1 2

ON

OFF

Room unit

OFF

OFF

Room controller

DIP switch setting applies to RDF870MB only.

Current factory setting for PM2.5 control with 3 speed on/off fan application:

  • APP= 1: PM2.5 control only
  • DISP: Room temp= 1; PM2.5= 1
  • SEN1= 3: PM2.5 (AI) μg/m3 (0…10 V)
  • SEN2= 0: no function
  • FAN= 3: 3 speed fan

OPERATIONS INSTRUCTIONS

Idle screen shows default PM2.5

  1. Screen idle
  2. Touch digits / screen
  3. Normal display / mode

Normal display for ventilation

  1. Screen idle
  2. Touch digits / screen
  3. Normal display / mode

If unit is OFF

  1. Screen idle
  2. Touch digits / screen
  3. Unit being turned ON
  4. Normal display / mode

Adjust setpoint

  1. Touch icon
  2. Press + or – to adjust:

Single fan: On/Off only

  1. Touch icon
  2. Press + or to adjust:
  3. Change fan mode:
    • ON > AUTO
    • See for fan type selection.

Fan speed selection

Adjust 3- or 4-speed fan:

  1. Touch icon
  2. Press + or to adjust:
    1. Auto
      1. Speed 1
      2. Speed 2
      3. Speed 3
      4. Speed 4
        • Depends on fan type selection

Adjust ECM fan:

  1. Touch icon
  2. Press + or to adjust:

Fan speed is adjusted by percentage

  • Touch + or – once to adjust speed by 5 %.
  • Press and hold + or –to quickly adjust speed.

(See Min./Max. settings in Engineering mode parameters)

Dual fan operations

(RDF870MB RU only)

  1. Touch icon
  2. Useor and press + or to adjust:

Change operating modes

  1. Touch icon
  2. Press + or to select:
    • ON: Comfort mode
    • ECO: Economy mode, a symbol will be shown
    • OFF: OFF

Adjust timer

(Fan filter alarm)

Change timer setpoint (TCSP) default value:

  1. Touch timer area once to enter time counter setting
  2. Press + or to adjust:

Reset timer:

  • Press and hold timer area more than 10 s to reset timer to 0.

View alarms

(RDF870KN)

  1. When alarm bell is displayed
  2. Touch icon once and press or to view all alarms

View alarms

(RDF870MB)

  1. When alarm bell is displayed
  2. Touch icon once and press or to view all alarms

View alarms

(RDF870MB room unit)

  1. When alarm bell is displayed
  2. Alarm AL originates in the controller when RDF870MB works as a room unit.
Priority Alarm/Service Display Error code * Type Product
1 Bus power supply BUS 5000 Fault RDF870KN
2 Device address error Adr 6001

 

 

 

RDF870KN
4 External fault input 1 AL1 9001 RDF870..
5 External fault input 2 AL2 9002 RDF870..
6 Clean filter reminder FIL 3911 RDF870..
7 Internal sensor error Er1 RDF870..
8 EEPROM error Er2 RDF870..
9 External error Er3 RDF870..
  • Error codes are for RDF870KN only.

Parameter mode user access

  1. Touch & hold icon > 5 s
  2. Enter first password via or
  3. Enter the second password via or
  4. After 6 seconds
    Note: Press the Setting icon to exit or re-enter the password if not correct
  5. Edit parameters.
  6. Exit parameter mode

Engineering parameters

Item Description Range Factory settings
MODA Modbus address

setting

1…247 1
MODB Modbus baud rate setting 1: 9600 bps
2: 19200 bps
3: 38400 bps
2: 19200 bps
MODF Modbus data frame format 0: 1/8/E/1
1: 1/8/O/1
2: 1/8/N/1
3: 1/8/N/2
0: 1/8/E/1
APP Application selection 1: PM2.5 control only
2: PM2.5 + CO2 control
3: CO2 control only
4: Ventilation
1: PM2.5 control only
DISP Symbol display enable/disable 0: Disable display 1: Enable display 1)  Room Temp= 1;

2) Outside Temp= 0;

3) PM2.5= 1;

4) VOC= 0;

5) CO2= 0;

6) RH= 0;

SEN11) External sensor1 type selection 0: No function
1: Temperature (AI) (NTC 10k)
2: Temperature (AI) (0…10 V)
3: PM2.5 (AI) μg/m3 (0…10 V)
4: CO2 (AI) ppm (0…10 V)
5: VOC (AI) % (0…10 V)
3: PM2.5 (AI)

μg/m3

(0…10 V)

6: VOC (AI) mg/m³ (0…10 V)
7: R.h. (AI) % (0…10 V)
8: Alarm input (DI)
9: Dummy AI (0…10 V) (RU only)
10: Dummy DI (RU only)
DIL1 Operating action if

digital input

0: Normally open / Open
1: Normally closed /
Closed
0: Normally open /

Open

SEN21) External sensor2 type selection 0: No function
1: Temperature (AI) (NTC 10k)
2: Temperature (AI) (0…10 V)
3: PM2.5 (AI) μg/m3 (0…10 V)
4: CO2 (AI) ppm (0…10 V)
5: VOC (AI) % (0…10 V)
6: VOC (AI) mg/m³ (0…10 V)
7: R.h. (AI) % (0…10 V)
8: Alarm input (DI)
9: Dummy AI (0…10 V) (RU only)
10: Dummy DI (RU only)
0: No function
DIL2 Operating action if

digital input

0: Normally open / Open

1: Normally closed / Closed

0: Normally open /

Open

PMH PM2.5 sensor high range Max. of low range…1000 500
PML PM2.5 sensor low

range

0…Min. of high range 0
CO2H CO2 sensor high

range

Max. of low range…2000 2000
CO2L CO2 sensor low range 0…Min. of high range 0
UOCH VOC sensor high

range

Max. of low range…100 5
UOCL VOC sensor low

range

0…Min. of high range 0
HUMH Humidity sensor high range Max. of low range…100 100
HUML Humidity sensor low range 0…Min. of high range 0
TEMH Temperature sensor high range Max. of low range…100 50
TEML Temperature sensor low range -50…Min. of high range 0
SPMH PM2.5 setpoint high range Max. of low range…500 100
SPML PM2.5 setpoint low range 0…Min. of high range 12
SPCH CO2 setpoint high

range

Max. of low range…2000 1500
SPCL CO2 setpoint low

range

0…Min. of high range 500
FAN Fan type selection 1: 1-speed fan (ON/OFF)
3: 3-speed fan
4: 4-speed fan
5: ECM fan
3: 3-speed fan
ECMH ECM fan output limit high Max. of ECML…100 % 80 %
ECML ECM fan output limit Low 0…Min. of ECMH 30 %
TC Filter time display 0: Disable 0: Disable
setting 1: Enable
PMES2) PM2.5 ECO mode

setpoint

0…100 60
COES2) CO2 ECO mode

setpoint

500…1500 1000
BUZZ Buzzer function 0: Disable
1: Enable
1: Enable
UNIT Temperature unit 0: °C (degrees Celsius)
1: °F (degrees Fahrenheit)
0: °C (degrees Celsius)
LOCK Keylock function 0: Unlock
1: Locked
2: Setpoint only
3: Operating mode only 4: Setpoint and fan speed only
0: Unlock
OPSL Operating mode

selection

0: ON/OFF
1: ON/ECO/OFF
2: ON/ECO/Protection/OFF (RU only)
3: ON/ECO/Protection (room unit only)
1: ON/ECO/OFF
CALT Internal temperature sensor calibration -5…5 K 0

RDF870KN available parameters and their order of appearance:

  • Room controller:
    • APP > DISP > SEN > FAN > OPSL > TC > UNIT > LOCK > BUZZ > CALT > APP

RDF870MB available parameters and their order of appearance:

  • Room controller:
    • MODA > MODB > MODF >APP > DISP > SEN > FAN > OPSL > TC > UNIT > LOCK > BUZZ > CALT > MODA
  • Room unit:
    • MODA > MODB > MODF > LOCK > BUZZ > CALT > MODA
  1. Room controller: 0…8; Room unit: 0…10
  2. The setpoint cannot be changed in ECO mode.

Restriction for sensor selection:

  1. If SEN1 and SEN2 are configured with the same selection type 1…8, they cannot be the same sensor types:
    • For type 1…8, sensor1 cannot be the same as sensor2.
    • For sensor types with the same function such as 1&2 or 5&6, if one sensor type is 1 or 5, the other one cannot be 2 or 6.

Firmware Setpoint Settings

Item Description Range Factory

settings

TCSP Filter time setting 0…9999 8760
PM2.5 SP PM2.5 setpoint SPML…SPMH 60
CO2 SP CO2 setpoint SPCL…SPCH 1000
T SP Temperature setpoint T SP L…T SP H 24
T SP H Temperature setpoint range high Max. of low range…200 (°C) 50
T SP L Temperature setpoint range low -50…Min. of high range (°C) 5
VOC SP VOC setpoint %: 0…100

mg/m3: 0…5

0.6 mg/m3 or

6 %

HUM SP Humidity setpoint 0…100 % 50 %
P81 1) Device address (KNX only) 1…255 255

1) P81 is only for ETS and local HMI does not support P81:

  • During power up, there is a startup delay (TwaitDevice = tWaitMin + DeviceAdr * 200ms) before the processing signal is processed.
  • When P81=255(default), the device does not process the signal according to the heartbeat and COV mechanism. But it can respond when another device is polling.
  • The local HMI does not support P81.
  • When the individual address is changed via ETS, P81 is updated automatically after the device downloads it from ETS.

Expert Mode Parameters

Item Description Range Factory

settings

PMP PM2.5 Control factor Xp 0…1000 50
PMI PM2.5 Control factor Tn 0…120 min 45 min
CO2P CO2 control factor Xp 0…2000 100
CO2I CO2 control factor Tn 0…120 min 45 min
PMDB PM2.5 control loop

deadband

0…20 10
CODB CO2 control loop deadband 0…100 50
OPAF Operating mode settings after power failure/reset 0: Return to the previous operating mode/user setting

1: Off

0: Return to previous operating mode/user

setting

FANT Fan minimum on time (dwell time) 1…6 min 2 min
FSET Reload factory settings 0: OFF = Disable

1: ON = Reload start

“–””—””—– ” is displayed

while reloading

0: OFF = Disable
SW Software version
EPAS Engineer mode password 0000…4999 0000
XPAS Expert mode password 5000…9999 9999

Room controller workflow:

  • EPAS > XPAS > PMP > PMI > PMDB > CO2P > CO2I > CODB > OPAF > FANT > FSET > SW > EPAS
  • RDF870MB Room unit workflow: EPAS > XPAS > SW > EPAS

Other Parameters (RDF870MB room unit only)

Item Description Range Factory settings
Output 1 (Q1) Output for external Modbus

controller (master)

0: Off

1: On

0: Off
Output 2 (Q2) Output for external Modbus

controller (master)

0: Off

1: On

0: Off
Output 3 (Q3) Output for external Modbus

controller (master)

0: Off

1: On

0: Off
Output 4 (Q4) Output for external Modbus

controller (master)

0: Off

1: On

0: Off

For complete parameter list, please refer to the document listed in the following table.

Ref. Document title Document number
[1] Datasheet A6V11439454

Download above document from http://siemens.com/bt/download by searching for the document number.

WIRING

RDF870…

  • 3/4 Speed Fan and ECM Fan

INFO

INSTALLATION INSTRUCTIONS

DIMENSION

Issued by

Open Source Software (OSS)

© Siemens Switzerland Ltd, 2019
Technical specifications and availability are subject to change without notice.

REFERENCE:

DOWNLOAD MANUALS:

Siemens RDF870KN Touch Screen Room Controller Thermostat Operating Instruction

Siemens RDF870KN Touch Screen Room Controller Thermostat Operating Instruction

wpx_thermostats

Recent Posts

Johnson Controls T7000e LCD Digital Thermostat Installation Guide

Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide

1 year ago

Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’S GUIDE

Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE

1 year ago

Hetta HS01RF WIRELESS THERMOSTAT KIT USER MANUAL

Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…

1 year ago

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat USER MANUAL

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…

1 year ago

Honeywell RLV450 PROGRAMMABLE THERMOSTAT USER GUIDE

Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…

1 year ago

Honeywell RLV431 Programmable Thermostat User Guide

Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…

1 year ago