Flush-mounted room thermostat with RS485 Modbus communications
Factory setting | |
RDF660MB | |
X1 | 3 = Window contact (DI) |
X2 | 1 = External temperature sensor (AI) |
RDF660MB/MM | |
B1 | 9 = H/C changeover (DI) |
S1 | 3 = Window contact (DI) |
Carefully read all wiring diagrams prior to installation to avoid damage to the device caused by incorrect wiring of high or low voltages.
Dismounting
Needs to be configured by your HVAC installer
Needs to be enabled via parameter P02
Change room temperature setpoint
Press + or – buttons to increase or decrease the current room temperature setpoint for Comfort mode. The thermostat changes to Comfort
The setting range is 5…35 °C, unless limited by parameters P09 and P10.
Adjust fan speed/fan mode
Press the
In Auto mode
In manual mode, the fan always runs at the speed that user selects:
Change thermostat operating mode
Press operating mode button
In Comfort mode
In Economy mode
(switch or Modbus command) such as keycard or presence detector.
In Protection mode
In Protection mode, press any button to activate the screen, then press the mode button to change to another operating mode.
Important: User can set Protection setpoints to OFF; the thermostat then is inactive, i.e. no protective heating or cooling function. Risk of frost!
Change from heating to cooling mode
Changeover between cooling
No changeover is possible if the thermostat is configured for cooling only or heating only (see parameter P01).
Meaning of cooling
Key lock
The key symbol
Reminder to clean filters and for external faults
Recalibrating the sensor
After installation for at least one hour, the displayed room temperature can be recalibrated via parameter P05.
Commissioning
User can adjust several different control parameters to adapt the thermostat to your system and optimize control performance. User can do this during operation either via the buttons on the thermostat or using a commissioning tool via Modbus.
Baud rate and parity
The Baud rate can be adjusted to 9600 bps, 19200 bps (factory setting), 38400 bps or 57600 bps. The Parity can be set to none, odd or even (factory setting). Your HVAC installer can set them through additional parameters.
Important: Once making any changes on the baud rate or parity, user must reset the power before the changes take effect.
Control parameters
Proceed as follows to change the most important control parameters
Parameter | Description | Factory setting | Setting range |
P01 | Control sequence | 2-pipe = 1 [selection: 0…3] 4-pipe = 4 [selection: 2, 4] | 0 = Heating only; 1 = Cooling only; 2 = H/C changeover manual 3 = H/C Changeover auto; 4 = Heating and cooling |
P02 | Mode selection by user via operating mode button | 3 | 3 = Comfort – Protection; 4 = Comfort – Economy – Protection |
P04 | Unit | 0 | 0 = °C (Celsius); 1 = °F (Fahrenheit) |
P05 | Measured value correction (for built-in/external sensor) | 0 | –5 K…5 K |
P06 | Standard display | 0 | 0 = Room temperature; 1 = Setpoint; 2 = Temperature value via bus |
P07 | Additional display information | 0 | 0 = No display; 1 = Room temperature °C or °F; 2 = Outside temperature (via bus) 3 = Time of day (12 h) via bus; 4 = Time of day (24 h) via bus |
P08 | Comfort basic setpoint | 21 °C | 5…40 °C |
P09 | Minimum Comfort setpoint | 5 °C | 5…40 °C |
P10 | Maximum Comfort setpoint | 35 °C | 5…40 °C |
P11 | Economy heating setpoint (WheatEco) | 15 °C | OFF, 5 °C…WcoolEco |
P12 | Economy cooling setpoint (WcoolEco) | 30 °C | OFF, WheatEco…40 °C |
P13 *** | Electrical heater in cooling mode | 1 | 0 = Disabled; 1 = Enabled |
P14 | Key lock | 0 | 0 = Unlock; 1 = Lock (all lock); 2 = Setpoint adjustable; 3 = Setpoint lock; 4 = Fan lock; 5 = Operating mode lock |
All temperature settings are in increments of 0.5 °C. *** Parameter P13 is only displayed for the application “2-pipe with electric heater”. |
Issued by
Siemens Switzerland Ltd
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
Tel. +41 58 724 2424
www.siemens.com/buildingtechnologies
© Siemens Switzerland Ltd, 2020
Technical specifications and availability are subject to change without notice.
DOWNLOAD MANUALS:
Siemens RDF660MB Flush mount room thermostat Operating Instruction
OTHER MANUALS:
Siemens RDF660MB Flush mount room thermostat Product Specifications Guide
Siemens RDF660MB Flush Mount Room Thermostat Operating Instruction
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…