Siemens RDF660MB Flush Mount Room Thermostat Operating Instruction

Siemens RDF660MB Flush Mount Room Thermostat

Mounting Instructions

Flush-mounted room thermostat with RS485 Modbus communications

Mounting location

Factory setting
RDF660MB
X1 3 = Window contact (DI)
X2 1 = External temperature sensor (AI)
RDF660MB/MM
B1 9 = H/C changeover (DI)
S1 3 = Window contact (DI)

Wiring diagrams

Dimensions (mm)

Mounting

Carefully read all wiring diagrams prior to installation to avoid damage to the device caused by incorrect wiring of high or low voltages.

Dismounting

Operating Instructions

Needs to be configured by your HVAC installer
Needs to be enabled via parameter P02

Change room temperature setpoint
Press + or – buttons to increase or decrease the current room temperature setpoint for Comfort mode. The thermostat changes to Comfort.
The setting range is 5…35 °C, unless limited by parameters P09 and P10.

Adjust fan speed/fan mode
Press thebutton to adjust the fan mode and fan speed.
In Auto mode,the thermostat automatically selects the fan speed based on setpoint and actual room temperature.
In manual mode, the fan always runs at the speed that user selects:

  • Low fan speed
  • Medium fan speed
  • High fan speed

Change thermostat operating mode
Press operating mode button to change the operating mode display.
In Comfort mode , the thermostat maintains the room temperature at the setpoint which can be readjusted using the + and – buttons.
In Economy mode , the room temperature is maintained at a lower or higher fixed setpoint (factory-set: 15 °C, 30 °C) to save energy. Adjust parameters P11 and P12 to change the preselected setpoints. The availability of Economy mode depends on parameter P02 or via an external signal
(switch or Modbus command) such as keycard or presence detector.
In Protection mode , the thermostat stops operating. However, it will operate if the room temperature is below 8 °C (heating application) against frost (P65) and the value is adjustable.
In Protection mode, press any button to activate the screen, then press the mode button to change to another operating mode.
Important: User can set Protection setpoints to OFF; the thermostat then is inactive, i.e. no protective heating or cooling function. Risk of frost!

Change from heating to cooling mode
Changeover between cooling and heating is either automatic using a heating/cooling changeover sensor or a remote changeover switch or via instruction from the central management station via Modbus, or manual by pressing operating mode button.
No changeover is possible if the thermostat is configured for cooling only or heating only (see parameter P01).
Meaning of cooling and heatingsymbols when displaying on LCD:

  • For automatic changeover or heating only/cooling only:
    Heating valve is open
    Cooling valve is open
  • For manual changeover only:
    Thermostat is in heating mode
    Thermostat is in cooling mode

Key lock
The key symbol indicates buttons are locked. Key lock can be configured via parameter P14.

Reminder to clean filters and for external faults 
This message reminds user to clean HVAC equipment filters.

Recalibrating the sensor 
After installation for at least one hour, the displayed room temperature can be recalibrated via parameter P05.

Commissioning 
User can adjust several different control parameters to adapt the thermostat to your system and optimize control performance. User can do this during operation either via the buttons on the thermostat or using a commissioning tool via Modbus.

Baud rate and parity
The Baud rate can be adjusted to 9600 bps, 19200 bps (factory setting), 38400 bps or 57600 bps. The Parity can be set to none, odd or even (factory setting). Your HVAC installer can set them through additional parameters.
Important: Once making any changes on the baud rate or parity, user must reset the power before the changes take effect.

Control parameters
Proceed as follows to change the most important control parameters

  1. Press the – and + buttons simultaneously for more than 6 seconds.
    Release, and within 2 seconds, press + again for more than 3 seconds. “P01” is displayed.
  2. Repeatedly press the + or – button to select the required parameter.
  3. Press + and – simultaneously once to enter EDIT mode. Then press + or – button to change the value of the selected parameter and press + and – simultaneously to save the change.
  4. Repeat steps 2 to 3 to display and change additional parameters.
  5. Press + or – until “End” is displayed, and then press + and –simultaneously to exit parameter entry mode.
Parameter Description Factory setting Setting range
P01 Control sequence 2-pipe = 1 [selection: 0…3] 4-pipe = 4 [selection: 2, 4] 0 = Heating only; 1 = Cooling only; 2 = H/C changeover manual 3 = H/C Changeover auto; 4 = Heating and cooling
P02 Mode selection by user via operating mode button 3 3 = Comfort – Protection; 4 = Comfort – Economy – Protection
P04 Unit 0 0 = °C (Celsius); 1 = °F (Fahrenheit)
P05 Measured value correction (for built-in/external sensor) 0 5 K…5 K
P06 Standard display 0 0 = Room temperature; 1 = Setpoint; 2 = Temperature value via bus
P07 Additional display information 0 0 = No display; 1 = Room temperature °C or °F; 2 = Outside temperature (via bus) 3 = Time of day (12 h) via bus; 4 = Time of day (24 h) via bus
P08 Comfort basic setpoint 21 °C 5…40 °C
P09 Minimum Comfort setpoint 5 °C 5…40 °C
P10 Maximum Comfort setpoint 35 °C 5…40 °C
P11 Economy heating setpoint (WheatEco) 15 °C OFF, 5 °C…WcoolEco
P12 Economy cooling setpoint (WcoolEco) 30 °C OFF, WheatEco…40 °C
P13 *** Electrical heater in cooling mode 1 0 = Disabled; 1 = Enabled
P14 Key lock 0 0 = Unlock; 1 = Lock (all lock); 2 = Setpoint adjustable; 3 = Setpoint lock; 4 = Fan lock; 5 = Operating mode lock
All temperature settings are in increments of 0.5 °C.                                      *** Parameter P13 is only displayed for the application “2-pipe with electric heater”.

Issued by
Siemens Switzerland Ltd
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
Tel. +41 58 724 2424
www.siemens.com/buildingtechnologies

© Siemens Switzerland Ltd, 2020
Technical specifications and availability are subject to change without notice.

REFERENCE:

DOWNLOAD MANUALS:

Siemens RDF660MB Flush mount room thermostat Operating Instruction

OTHER MANUALS:

Siemens RDF660MB Flush mount room thermostat Product Specifications Guide

Siemens RDF660MB Flush Mount Room Thermostat Operating Instruction

wpx_thermostats

Recent Posts

Johnson Controls T7000e LCD Digital Thermostat Installation Guide

Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide

1 year ago

Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’S GUIDE

Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE

1 year ago

Hetta HS01RF WIRELESS THERMOSTAT KIT USER MANUAL

Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…

1 year ago

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat USER MANUAL

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…

1 year ago

Honeywell RLV450 PROGRAMMABLE THERMOSTAT USER GUIDE

Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…

1 year ago

Honeywell RLV431 Programmable Thermostat User Guide

Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…

1 year ago