To control the room temperature in individual rooms and zones that are:
The thermostats control:
The thermostat consists of two parts:
Ordering
Type | Stock number | Designation |
RDF510 | S55770-T382 | Room thermostat (White) in single pack of 1 unit |
RDF510/BP | S55770-T383 | Room thermostat (White) in bulk pack of 20 units |
RDF510/BP.VS | S55770-T403 | Room thermostat (Silver) in bulk pack of 20 units |
RDF510/BP.VB | S55770-T404 | Room thermostat (Black) in bulk pack of 20 units |
RDF510/BP.VG | S55770-T405 | Room thermostat (Gold) in bulk pack of 20 units |
RDF530 | S55770-T384 | Room thermostat (White) in single pack of 1 unit |
RDF530/BP | S55770-T385 | Room thermostat (White) in bulk pack of 20 units |
RDF530/BP.VS | S55770-T423 | Room thermostat (Silver) in bulk pack of 20 units |
RDF530/BP.VB | S55770-T417 | Room thermostat (Black) in bulk pack of 20 units |
RDF530/BP.VG | S55770-T424 | Room thermostat (Gold) in bulk pack of 20 units |
Delivery
Order valve actuators separately.
On/Off actuators
Type of units | Product number | Data sheet*) | |
Electromotive ON/OFF valve and actuator (only available in AP, UAE, SA and IN) | | MVI…/MXI… | A6V11251892 |
Electromotive ON/OFF actuator | | SFA21… | N4863 |
Thermal actuator (for radiator valve) AC 230 V, NO | | STA23… | N4884 |
Thermal actuator AC 230 V (for small valves 2.5 mm), NC | | STP23… | N4884 |
Zone valve actuators (only available in AP, UAE, SA and IN) | | SUA… | N4832 |
Title | Document ID |
Mounting and operating instructions | A6V10889954 |
CE declarations | A6V101090515 |
Environmental declarations | A5W00085405A |
CAUTION: National safety regulations
Failure to comply with national safety regulations may result in personal injury and property damage
Mounting
Do not wall-mount in niches or bookshelves, behind curtains, above or near heat sources, wind outlets or inlets, and do not expose to direct solar radiation. Mount about 1.5 m above the floor.
WARNING: Wire, protect, and earth in compliance with local regulations.
Current loading is limited by a standard slow-blow 6.3 A fuse (replaceable). Risk of fire and injury due to short circuits!
Commissioning
Note
If the room thermostat uses the mains supply from a hotel Room Control Unit (RCU), less startup time (e.g. < 3 seconds) is more suitable for this type of hotel applications. Please add a special note to request for RDF510/RDF530 products with firmware revision D or above.
Sensor calibration
The thermostat has an internal sensor for accurate temperature display. If the temperature display is influenced by its installation location, calibrate the sensor via parameter P05 to adjust the readings.
Setpoint and range limitation
For comfort and energy-saving reasons, we suggest to review the setpoints and setpoint ranges (parameters P09, P10, P65 and P66) and change them as needed.
Manual heating/cooling changeover
If the thermostat is enabled for “H/C changeover manual” via parameter P01=2 (factory setting for RDF510), press the “H/C changeover” button to display the currently selected control sequence on the LCD. Press again to change the control sequence. The newly selected control sequence is displayed and executed after the thermostat returns to On mode.
If the thermostat is set to “Cooling only” or “Heating only” via parameter P01, the manual changeover function is not available. Press the “H/C Changeover” button to display only the current control sequence on the LCD.
On/Off control
On 2-pipe applications, the thermostat controls an On/Off valve in heating/cooling mode with manual changeover (P01 = 2, factory set).
RDF510 | |||
T[°C] | Room temperature | SDH | Switching differential “Heating” |
W | Room temperature setpoint | SDC | Switching differential “Cooling” |
YH | Control command “Valve” (heating) | YC | Control command “Valve” (cooling) |
On 4-pipe applications, the thermostat controls two On/Off valves in heating and cooling mode (P01=4, factory set), or heating/cooling mode (P01=2) by manual changeover.
RDF530 | |||
Heating mode | Cooling mode | ||
Heating and cooling mode | |||
T[°C] | Room temperature | SDH | Switching differential “Heating” |
W | Room temperature setpoint | SDC | Switching differential “cooling” |
YH | Control command “Valve” (heating) | YC | Control command “Valve” (cooling) |
Xdz | Deadzone |
On/Off control signal
The valve receives the On command via control output Y14 (Y1 and Y2 on RDF530) when:
The valve receives the Off command when:
Note
Fan operation
Heating mode
Cooling mode
Ventilation always on
If desired, fan control can be set to “Temperature-independent”, which means that ventilation is always on, even within the dead zone, using at least fan speed 1(P15 = 1, factory set).
See “Avoiding damage due to moisture” for more information.
Fan minimum On-time
In automatic mode, a dwelling time of 2 minutes (factory setting) is active. The fan maintains that speed for at least 2 minutes before it switches to the next speed. This dwelling time can be adjusted from 1…6 minutes via parameter P59.
Fan On-time is set to minimum 2 minutes before the fan is turned off. This prevents the fan from being frequently switched between the On and Off states. The maximum duration is 6 minutes.
Fan start
When the fan starts from standstill, it starts at speed 3 for 1 second to guarantee safe fan motor start (to overcome inertia and friction).
Temperature out of range
Factory setting of the heating/cooling setpoint in Protection mode is Off, i.e. overheating/frost protection is disabled.
In this case, when the room temperature is out of range, i.e. above 49 °C or below 0 °C, the temperature displays and flashes at “0 °C” or “49 °C”, and the thermostat continues to work.
Sensor error
When the internal sensor is not working properly, “Er1” is displayed.
Parameter settings
To optimize control performance, use the local HMI to adjust a number of control parameters. All control parameter settings are retained after power down.
Proceed as follows to change the control parameters:
Reload factory setting
Parameter | Description | Factory setting | Setting range |
P01 | Control sequence | RDF510 = 2 RDF530 = 4 | 0:= Heating only 1:= Cooling only 2:= H/C changeover manual 4:= Heating and cooling (RDF530) Note: RDF510: 0, 1, 2 RDF530: 2, 4 |
P05 | Sensor calibration | 0 K | -5…+5 K |
P06 | Standard temperature display | 0 | 0:= Room temperature 1:= Setpoint |
P09 | Minimum setpoint in Comfort mode | 5 ℃ | 5…40 ℃ |
P10 | Maximum setpoint in Comfort mode | 35 ℃ | 5…40 ℃ |
P14 | Keylock function | 0 | 0:= No lock 1:= Full lock 2:= Partial lock |
P15 | Fan control deadzone in Comfort mode | 1 | 0:= Fan off 1:= Fan speed 1 in heating or cooling mode |
P27 | Operating mode settings upon power down | 0 | 0:= Return to previous operating mode or user settings 1:= Protection mode 2:= Comfort mode |
P28 | Timer with delay Off | 0 | 0:= Users to set on-time duration 1 to 23:= Preset with a fixed on-time in hours |
P30 | Switching differential in heating mode | 1 K | 0.5 … 6 K |
P31 | Switching differential in cooling mode | 1 K | 0.5 … 6 K |
P33 | Deadzone in Comfort mode | 2 K | 0.5 … 5 K (RDF530) |
P59 | Fan minimum On-time (dwelling time) | 2 minutes | 1…6 minutes |
P65 | Protection heating setpoint | 8 ℃ | OFF, 5 ℃…Wcoolpro; Wcoolpro=40℃ max. |
P66 | Protection cooling setpoint | OFF | OFF, Wheatpro…40 ℃; Wheatpro=5 ℃ min. |
P71 | Reload factory setting | OFF | OFF:= Disable ON:= Reload start “—” is displayed for 3 seconds while reloading |
P91 1) | Fan symbol display and function controls – associated key button function is disabled | RDF510 = 1 RDF530 = 1 | 0: disable display 1: enable display |
P92 1) | H/C changeover symbol display and function controls – associated key button function is disabled | RDF510 = 1 RDF530 = 1 | 0: disable display 1: enable display |
Notes
Temperature control
The thermostat acquires the room temperature via its built-in sensor and maintains the setpoint by delivering 2-position valve control commands.
The switching differential is 1 K in heating mode and 1 K in cooling mode (adjustable via parameters P30 and P31).
Display
The display shows the current room temperature or the setpoint of the current operating mode (adjustable via parameter P06). Factory setting is to display the current room temperature.
The heating symbol
The triangle symbol indicates the relay output connected to the fan coil unit is energized.
Setpoint adjustment and limitations
The factory setting for the Comfort basic setpoint is 21 ℃. The Comfort setpoint can be adjusted via the +/- buttons. For comfort or energy saving purposes, the setpoint setting range is limited to minimum (P09) and maximum (P10).
P09<P10 (comfort concept)
If the minimum setpoint (P09) is set lower than the maximum setpoint (P10), both heating and cooling setpoints are adjustable between these two limits. The customer sets the desired setpoint and the thermostat controls the room temperature accordingly.
For 4-pipe applications, the selected Comfort setpoint is in the middle of the deadzone (P33). The unit stops to energize the heating/cooling outputs as soon as the room temperature reaches the deadzone.
P09≥P10 (energy saving concept)
If the minimum limit P09 is set higher that maximum limit P10, then:
As a result, the maximum heating setpoint and the minimum cooling setpoint can be limited, thus saving energy and lowering costs.
For 4-pipe applications:
The thermostat runs with the setpoint of the active sequence:
Switching from heating to cooling setpoint and vice-versa occurs when the room temperature reaches the adjusted limitation (P09 or P10) of the inactive sequence. e.g. the thermostat is in heating sequence and runs on the heating setpoint. When the room temperature reaches P09, the thermostat switches to cooling mode and runs on the cooling setpoint, provided the room temperature does not drop below P10.
Keylock
Keylock can be activated or deactivated via parameter P14 when the thermostat is in Comfort and Protection mode.
Either full lock (P14=1) or partial lock (P14=2) can be selected. All buttons are disabled if full lock is set. On partial lock, only setpoints can be adjusted.
Operating modes
The following operating modes are available:
Comfort mode
In Comfort mode, the thermostat maintains the setpoint, which can be adjusted via the + and – buttons. The fan can be set to automatic or manual fan speed: Low, medium or high.
To save energy, the setpoint setting range has a minimum (P09) and maximum limitation (P10).
Protection mode
When the thermostat is in Protection mode, the related setpoints of heating or cooling setpoints are maintained. They can be adjusted via control parameters P65 and P66. The factory setting for P66 is OFF, indicating the thermostat is not active in Protection (cooling) mode.
Timer with delay Off mode
In timer with delay Off mode, the timer starts counting down according to the hour selected (via parameter P28) after the thermostat is turned ON. When the timer expires, the thermostat automatically turns OFF.
Operating mode setting upon power down
If the thermostat is disconnected from AC 230 V power supply and then reconnected, the thermostat returns to the previous operating mode or user settings if P27=0, remains in Protection (Off) mode if P27=1, or remains in Comfort mode if P27=2.
Avoiding damage due to moisture
To avoid damage due to moisture in very warm and humid climates resulting from lack of air circulation in Comfort mode, the fan can be kept running at all times (e.g. in apartments or shops during unoccupied periods) when setting parameter P15 “ON in deadzone”. In this case, the fan continues to run at minimum fan speed 1 in the neutral zone.
The device is considered an electronic device for disposal in accordance with European Directive and may not be disposed of as domestic waste.
Technical data on specific applications are valid only together with Siemens products listed under “Equipment combinations”. Siemens rejects any and all warranties in the event that third-party products are used.
Power supply | |
Operating voltage | AC 230 V (+10%, -15%) |
Frequency | 50/60 Hz |
Power consumption | Max. 12 VA |
Internal fuse (replaceable) | |
Fuse type | SLOW-BLOW |
Size | dia. 5.2×20 mm |
Voltage rating | 250 V |
Current rating | 6.3 A |
Outputs | |
Valve output (RDF510) Y12 (N.C.)/Y14 (N.O.) Rating | AC 230 V 5 mA…4(2) A |
Valve output (RDF530) Y1 (N.O.) /Y2 (N.O.) Rating | AC 230 V 5 mA…4(2) A |
Fan output (3-speed fan) Q1, Q2, Q3 Rating | AC 230 V 5 mA…4(2) A |
Operational data | |
Switching differential – Heating mode – Cooling mode | 0.5…6 K (factory setting: 1 K) 0.5…6 K (factory setting: 1 K) |
Setpoint setting range (see note below)
| 5…40 °C OFF, 5…40 °C |
Built-in room temperature sensor
| 0…50 °C < ±0.5 K – 5.0…+5.0 K |
Resolution of settings and display
| 0.5 °C 0.5 °C |
Note: The standard range is 5…40 °C. Customization is available upon request (e.g. 0…50 °C).
Ambient conditions and protection classification | |
Safety class | II as per EN 60730-1 |
Pollution class | II as per EN 60730-1 |
Degree of protection of housing | IP30 as per EN 60529 |
Climatic ambient conditions
| – Class 1K3 – Class 2K3 – Class 3K5 1) |
Standards, directives and approvals | |
EU conformity (CE) | A6V101090515 |
Environmental compatibility | The product environmental declaration (A5W00085405A) contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal). |
All documentation can be downloaded from
https://www.downloads.siemens.com/download-center/.
General | |
Connection terminals | Solid wires or prepared stranded wires: 1×0.4-1.5 mm2 |
Weight | Mounting frame: 20 g RDF510 unit with mounting frame: 160 g RDF530 unit with mounting frame: 165 g |
Color of front housing | White, RAL 9003 Silver, Cool Grey 4C Gold, Gold 453C Black, Pantone black 7C |
Mounting screws
Connection terminals
RDF510 | RDF530 | |
| | |
L, N | AC 230 V power supply, mains and neutral | |
Q1 | Output, fan speed 1, AC 230 V | |
Q2 | Output, fan speed 2, AC 230 V | |
Q3 | Output, fan speed 3, AC 230 V | |
Y12 | Output “Valve”, AC 230 V (NC) | |
Y14 | Output “Valve”, AC 230 V (NO) | |
Y1 | Output “Valve”, AC 230 V (NO) | |
Y2 | Output “Valve” AC 230 V (NO) |
RDF530
RDF510 | ||
2-pipe fan coil unit ON / OFF (heating or cooling) |
| |
V1 | Heating/cooling valve actuator | |
M1 | 3-speed fan | |
N1 | RDF510 |
RDF530 | ||
4-pipe fan coil unit ON/OFF (heating and cooling) |
| |
V1 | Heating or heating/cooling valve actuator | |
V2 | Cooling valve actuator | |
M1 | 3-speed fan | |
N2 | RDF530 |
Dimensions in mm
View A View B
Above are the dimensions for the thermostat and its mounting plate.
© Siemens Switzerland Ltd, 2020
Technical specifications and availability subject to change without notice.
Issued by
DOWNLOAD MANUALS:
SIEMENS RDF510 Flush mount room thermostat Product Specifications Guide
SIEMENS RDF510 Flush mount room thermostat Product Specifications Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…