Flush-mounted Room Thermostat
For controlling the room temperature in individual rooms and zones that are
The thermostat controls
Suitable for use in systems with
Temperature control
Display
Operating modes
The following operating modes are available
Water-based fan coil application
Used in conjunction with a valve, either for heating/cooling with changeover, or heating only, cooling only
ON
The valve receives the OPEN command via control output Y11 when
OFF
The valve receives the CLOSE command via control output Y11 when
Note:
Control output Y12 delivers a control command which is inverted to the control command at output Y11 and which can be used for normally open valves
Heating/cooling mode
Minimum output on/off time Y11 and Y12
The minimum output on/off time of Y11 and Y12 is fixed at 1 minute. It means that any readjustment of the setpoint or of Heating/Cooling Mode changeover lasts for 1 minute before Y11 and Y12 react
Ventilation always on
If desired, fan control can be set to ”Temperature-independent”, which means that ventilation is always on, even within the dead zone, using at least fan speed 1. This can be selected individually for Comfort mode via parameter P21; also refer to “Avoiding damage due to moisture” on page 3).
Dwelling time
In automatic mode, a dwelling time of 2 minutes (factory setting) is active. The fan maintains that speed for at least 2 minutes before it switches to the next speed. This dwelling time can be adjusted from 1…5 minutes via parameter P14.
Fan start
Whenever the fan starts from a standstill, it starts with speed 3 for 1 second in order to guarantee a safe fan motor starts (to overcome inertia and friction).
The temperature out of range
When the room temperature is out of the measuring range, which means above 49 °C or below 0 °C, the display shows the limiting temperature in flashing figures, e.g. “0 °C” or “49 °C”.
If the current setpoint is not OFF (see parameter P03) and the thermostat is in heating mode, when the temperature is below 0 °C, output Y11 is energized. In all other cases, output Y11 is de-energized until the temperature returns to the measuring range, and then the thermostat resumes Comfort mode.
To optimize the control performance, you can use local HMI to adjust a number of control parameters. Proceed as follows to change the control parameter
Parameter settings
Parameter reset
Reload the factory setting of the control parameters as follows:
Control parameters
Para- meter | Meaning | Setting range | Factory setting |
P03 | Setpoint of heating in Protection Mode (WheatStb) | OFF, 5 °C…WcoolStb | 8 °C |
P04 | Setpoint of cooling in Protection Mode (WcoolStb) | OFF, WheatStb …40 °C | OFF |
P05 | Minimum setpoint limitation in Comfort Mode (WminNorm) | 5 °C…WmaxNorm | 5 °C |
P06 | Maximum setpoint limitation in Comfort Mode (WmaxNormf) | WminNorm…40 °C | 35 °C |
P07 | Sensor calibration | -3…3 K | 0 K |
P08 | Switching differential heating mode SDH | 0.5…4 K | 1 K |
P09 | Switching differential cooling mode SDC | 0.5…4 K | 1 K |
P14 | Dwelling time of auto fan speeds | 1…5 min | 2 min |
P17 | Selection of °C or °F | °C or °F | °C |
P18 | Display of temperature or setpoint | OFF: Setpoint ON: Room (or return air) temperature | ON |
P21 | Fan control in Comfort mode | OFF in dead zone ON in dead zone | ON |
P22 | Heating/cooling mode | 0: Heating only 1: Cooling only 3: Manual H/C changeover | 3: Manual |
ON/OFF actuators
Type of unit | Product no. | Data sheet |
Electromotoric ON/OFF actuator | SFA21… | 4863 |
Electromotoric ON/OFF valve and actuator (only available in AP, UAE, SA and IN)
| MVI…/MXI… | A6V11251892 |
Zone valve actuators (only available in AP, UAE, SA and IN) | SUA… | 4832 |
Thermal actuator (for radiator valve) | STA23… | 4884 |
Thermal actuator (for small valves 2.5 mm) | STP23… | 4884 |
Ordering
When ordering, please indicate the product name, product number and SSN number: (e.g. room thermostat, RDF310.2/MM, S55770-T187)
Valve actuators should be ordered separately
Mechanical design
The thermostat consists of two parts:
The mounting base carries on the rear side the screw terminals. It fits on a square conduit box with fixing centres 60.3mm. The front panel engages in the mounting base and snaps on.
Setting and operating elements
Legend
The thermostat can be mounted on a recessed square conduit box with fixing centres of 60.3 mm. The mounting location on a wall should not be in niches or bookshelves, not behind curtains, above or near heat sources and wind outlet or inlet, and not exposed to direct solar radiation. Mounting height is about 1.5 m above the floor
Wiring
Please also refer to the Mounting Instructions M3066… enclosed with the thermostat.
Wiring, protection and earthing must be installed in compliance with local regulations
Warning!
No internal line protection for supply lines to external consumers (Q1, Q2, Q3, Y11, Y12)
Risk of fire and injury due to short-circuits!
Commissioning
After applying power, the thermostat makes a reset during which all LCD segments flash, indicating that the reset has been correctly made. This takes about 3 seconds. Then, the thermostat is ready for commissioning by qualified HVAC staff. The control parameters of the thermostat can be set to ensure optimum performance of the entire system (please also refer to “Parameter settings”).
Heating/cooling mode
Set the heating/cooling mode via parameter P22 depending on the application. Factory setting is “Manual heat/cool changeover”. Set P22 accordingly in ”Cooling only” or “Heating only” mode
Calibrating the sensor
When the room temperature displays on the thermostat does not match the room temperature effectively measured, you can recalibrate the temperature sensor via parameter P07
Setpoint and range limitation
For comfort and energy saving reasons, it is suggested to review the setpoints and setpoint ranges (parameters P03…P06), if necessary, to change them accordingly.
Disposal
The device is considered electrical and electronic equipment for disposal in terms of the applicable European Directive and may not be disposed of as domestic garbage.
© Siemens Switzerland Ltd, 2010 – 2019
Technical specifications and availability are subject to change without notice.
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a
CH-6300 Zug
Tel. +41 58 724 2424
www.swww.siemens.iemens.ccom/buildinom/buildingtechngtechnologologiieses
Siemens Smart Infrastructure
Flush-mounted Room Thermostat
DOWNLOAD MANUALS:
SIEMENS RDF310.2MM Flush-mounted Room Thermostat Product Specifications Guide
SIEMENS RDF310.2/MM Flush-mounted Room Thermostat Product Specifications Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…