SIEMENS

SIEMENS RDF310.2/MM Flush-mounted Room Thermostat Product Specifications Guide

SIEMENS RDF310.2/MM Flush-mounted Room Thermostat

Flush-mounted Room Thermostat

  • for 2-pipe fan coil units

SPECIFICATION

  • Output for on/off valve or 3-wire on/off valve actuator
  • 3-speed fan control: Automatic or manual
  • Manual heating/cooling changeover or continuous Cooling only / Heating only
  • Operating modes: Comfort, Protection
  • Adjustable commissioning and control parameters
  • Optional display of room temperature or setpoint
  • Minimum and maximum setpoint limitation
  • Display temperature in increments of 0.5 °C
  • Operating voltage AC 230 V
  • Mounting on recessed square conduit box, fixing centres 60.3 mm
  • User and parameter settings can be retained or restored with power loss

Use

For controlling the room temperature in individual rooms and zones that are

  • heated or cooled with 2-pipe fan coil units

The thermostat controls

  • a 3-speed fan
  • an on/off valve actuator in a 2-pipe system

Suitable for use in systems with

  • continuous heating or cooling mode
  • manual heating/cooling changeover

Functions

  • Manual changeover between heating and cooling mode
  • Maintenance of room temperature with integrated internal temperature sensor
  • Selection of operating mode with the operating mode button on the thermostat
  • 3-speed fan control (automatic or manual)
  • Output for 2-position (on/off) valve or 3-wire (on/off) valve actuator

Applications

  • V1 Heating/cooling valve actuator
  • M1 3-speed fan
  • N1 Thermostat

Operation

Temperature control

  • The thermostat acquires the room temperature via its built-in sensor and maintains the setpoint by delivering 2-position valve control commands.
  • The switching differential is 1 K in heating mode and 1 K in cooling mode (adjustable via parameters P08 and P09).

Display

  • The display shows the acquired room temperature or the setpoint of the current operating mode. This can be selected via parameter P18. The factory setting is a display of the current room temperature.
  • The heating symbol or the cooling symbol displays to indicate the output status of the relays connected to the fan coil. This means that the symbol does not display when the thermostat operates in the neutral zone. If the thermostat is under manual heating or cooling changeover, the heating symbol or the cooling symbol displays permanently to indicate the control sequence. i.e. heating or cooling. This means that the symbol displays when the thermostat operates in the neutral zone.
  • If required, room temperature and setpoint can also be displayed in °F in place of °C by changing parameter P17

Operating modes

The following operating modes are available

  • Comfort Mode
    • In Comfort mode, the thermostat maintains the setpoint, which can be adjusted via the + and – buttons. The fan can be set to automatic or manual fan speed: Low, medium or high.
      Tip!
      The setpoint setting range can be limited to a minimum (P05) and maximum (P06). This helps prevent the waste of energy, and saving costs.
  • Protection Mode
    • When the thermostat is in Protection mode , the relevant setpoints of heating or cooling are maintained. These setpoints can be adjusted via control parameters P03 and P04. Factory setting of both setpoints is OFF, indicating the thermostat is not activated when in Protection mode
  • Avoiding damage due to moisture
    • To avoid damage due to moisture in very warm and humid climatic zones resulting from lack of air circulation in Comfort mode, the fan can be kept running all the time (e.g. in apartments or shops during unoccupied periods), when setting parameter P21 “ON in dead zone”. In this case, the fan keeps running at minimum fan speed 1 in the neutral zone.

Control sequences

Water-based fan coil application

Used in conjunction with a valve, either for heating/cooling with changeover, or heating only, cooling only

ON

The valve receives the OPEN command via control output Y11 when

  1. the acquired room temperature lies by half the switching differential below the setpoint (heating mode) or above the setpoint (cooling mode), and
  2. control output Y11 was not energized for more than the “Minimum output off time” (factory setting 1 minute)

OFF

The valve receives the CLOSE command via control output Y11 when

  1. the acquired room temperature lies by half the switching differential above the setpoint (heating mode) or below the setpoint (cooling mode), and
  2. control output Y11 was energized for more than the “Minimum output on time”; (factory setting 1 minute)

Note:

Control output Y12 delivers a control command which is inverted to the control command at output Y11 and which can be used for normally open valves

Heating/cooling mode

  • When you press the heating/cooling changeover button , the thermostat changes from heating to cooling, or vice versa.
  • If the thermostat is set to ”Cooling only” or ”Heating only” via P22, the manual changeover function on the button is not available (the factory setting of parameter P22 is ”manual changeover”). Instead, “NOP” flashes on the display, indicating continuous cooling or heating is set respectively

Minimum output on/off time Y11 and Y12

The minimum output on/off time of Y11 and Y12 is fixed at 1 minute. It means that any readjustment of the setpoint or of Heating/Cooling Mode changeover lasts for 1 minute before Y11 and Y12 react

Fan operation

  • The fan operates either in automatic mode or at the selected speed when using manual mode. In automatic mode, the fan speed depends on the setpoint and the current room temperature. When the room temperature reaches the setpoint, the control valve is closed and the fan either remains in fan speed 1 or switches off (parameter P21, factory setting: fan speed 1 in dead zone).
  • In “Temperature-dependent” fan control the fan switches off (please see diagram below). The individual switching differentials of the fan speed 1 (Q1 only) can be adjusted via control parameters P08 – P09. The individual switching differentials of the fan speed 2 and 3 (Q2 and Q3) are fixed at 1K.

Ventilation always on

If desired, fan control can be set to ”Temperature-independent”, which means that ventilation is always on, even within the dead zone, using at least fan speed 1. This can be selected individually for Comfort mode via parameter P21; also refer to “Avoiding damage due to moisture” on page 3).

Dwelling time

In automatic mode, a dwelling time of 2 minutes (factory setting) is active. The fan maintains that speed for at least 2 minutes before it switches to the next speed. This dwelling time can be adjusted from 1…5 minutes via parameter P14.

Fan start

Whenever the fan starts from a standstill, it starts with speed 3 for 1 second in order to guarantee a safe fan motor starts (to overcome inertia and friction).

Error handling

The temperature out of range

When the room temperature is out of the measuring range, which means above 49 °C or below 0 °C, the display shows the limiting temperature in flashing figures, e.g. “0 °C” or “49 °C”.
If the current setpoint is not OFF (see parameter P03) and the thermostat is in heating mode, when the temperature is below 0 °C, output Y11 is energized. In all other cases, output Y11 is de-energized until the temperature returns to the measuring range, and then the thermostat resumes Comfort mode.

Control parameters

To optimize the control performance, you can use local HMI to adjust a number of control parameters. Proceed as follows to change the control parameter

Parameter settings

  1. Set the thermostat to Protection mode.
  2. Press and hold the + and – buttons simultaneously for 3 seconds. Release them and, within 2 seconds, press and hold the + button again for 3 seconds. Then, P03 displays.
  3. Select the required parameter by pressing the + and – buttons
  4. Press the + and – buttons simultaneously. Te current value of the selected parameter displays on the screen. Press the + or – button to change the value.
  5. You can either press the + and – buttons simultaneously to confirm the change or wait for 5 seconds to have the change saved automatically.
  6. Repeat steps 3 through 5 to change more parameters.
  7. 10 seconds after the last display or setting, all changes are saved and the thermostat returns to Protection mode

Parameter reset

Reload the factory setting of the control parameters as follows:

  1. Set the thermostat to Protection mode .
  2. Press the + and – buttons simultaneously for 3 seconds. Release them and, within 2 seconds, press the button twice.
    Then 888 displays during the reloading process.

Control parameters

Para- meter Meaning Setting range Factory setting
P03 Setpoint of heating in Protection Mode                     (WheatStb) OFF, 5 °C…WcoolStb 8 °C
P04 Setpoint of cooling in Protection Mode                     (WcoolStb) OFF, WheatStb …40 °C OFF
P05 Minimum setpoint limitation in Comfort Mode          (WminNorm) 5 °C…WmaxNorm 5 °C
P06 Maximum setpoint limitation in Comfort Mode         (WmaxNormf) WminNorm…40 °C 35 °C
P07 Sensor calibration -3…3 K 0 K
P08 Switching differential heating mode SDH 0.5…4 K 1 K
P09 Switching differential cooling mode SDC 0.5…4 K 1 K
P14 Dwelling time of auto fan speeds 1…5 min 2 min
P17 Selection of °C or °F °C or °F °C
P18 Display of temperature or setpoint OFF: Setpoint

ON: Room (or return air) temperature

ON
P21 Fan control in Comfort mode OFF in dead zone ON in dead zone ON

P22

Heating/cooling mode

0: Heating only

1: Cooling only

3: Manual H/C changeover

3: Manual

Equipment combinations

ON/OFF actuators

Type of unit Product no. Data sheet
Electromotoric ON/OFF actuator SFA21… 4863
Electromotoric ON/OFF valve and actuator (only available in AP, UAE,

SA and IN)

 

MVI…/MXI…

A6V11251892

Zone valve actuators (only available in AP, UAE, SA and IN) SUA… 4832
Thermal actuator (for radiator valve)   STA23… 4884
Thermal actuator

(for small valves 2.5 mm)

STP23… 4884

Ordering

When ordering, please indicate the product name, product number and SSN number: (e.g. room thermostat, RDF310.2/MM, S55770-T187)
Valve actuators should be ordered separately

Mechanical design

The thermostat consists of two parts:

  • Front panel which accommodates the electronics, the operating elements and the built-in room temperature sensor
  • Mounting base with the power electronics

The mounting base carries on the rear side the screw terminals. It fits on a square conduit box with fixing centres 60.3mm. The front panel engages in the mounting base and snaps on.

Setting and operating elements

Legend

  1. Display of the room temperature, setpoints and control parameters
  2. The symbol used when displaying the current room temperature
  3. Protection mode / fan mode status
    • Protection mode
    • AUTO Auto fan active
    • Fan speed low, medium, high
  4. output is energized (auto mode) / manual cooling mode (manual mode)
  5. output is energized (auto mode) / manual heating mode (manual mode)
  6. Comfort mode
  7. Buttons for adjusting the setpoints and control parameters
  8. Button for changing fan operation and Protection mode ( )
  9. Manual heating/cooling changeover

Mounting and installation

The thermostat can be mounted on a recessed square conduit box with fixing centres of 60.3 mm. The mounting location on a wall should not be in niches or bookshelves, not behind curtains, above or near heat sources and wind outlet or inlet, and not exposed to direct solar radiation. Mounting height is about 1.5 m above the floor

Wiring

Please also refer to the Mounting Instructions M3066… enclosed with the thermostat.
Wiring, protection and earthing must be installed in compliance with local regulations

Warning!
No internal line protection for supply lines to external consumers (Q1, Q2, Q3, Y11, Y12)
Risk of fire and injury due to short-circuits!

  • Adapt the line diameters as per local regulations to the rated value of the installed overcurrent protection device.
  • The AC 230 V mains supply line must have an external circuit breaker with a rated current of no more than 10 A.
  • Only valves rated for AC 230 V may be used.
  • Disconnect from supply before opening the cover

Commissioning

After applying power, the thermostat makes a reset during which all LCD segments flash, indicating that the reset has been correctly made. This takes about 3 seconds. Then, the thermostat is ready for commissioning by qualified HVAC staff. The control parameters of the thermostat can be set to ensure optimum performance of the entire system (please also refer to “Parameter settings”).

Heating/cooling mode

Set the heating/cooling mode via parameter P22 depending on the application. Factory setting is “Manual heat/cool changeover”. Set P22 accordingly in ”Cooling only” or “Heating only” mode

Calibrating the sensor

When the room temperature displays on the thermostat does not match the room temperature effectively measured, you can recalibrate the temperature sensor via parameter P07

Setpoint and range limitation

For comfort and energy saving reasons, it is suggested to review the setpoints and setpoint ranges (parameters P03…P06), if necessary, to change them accordingly.

Disposal

The device is considered electrical and electronic equipment for disposal in terms of the applicable European Directive and may not be disposed of as domestic garbage.

  • Dispose of the device through channels provided for this purpose.
  • Comply with all local and currently applicable laws and regulations

Technical data

Connection terminals

  • L, N Operating voltage AC 230 V
  • Q1 Control output “Fan speed 1 AC 230 V
  • Q2 Control output “Fan speed 2 AC 230 V
  • Q3 Control output “Fan speed 3 AC 230 V
  • Y11 Control output “Valve” AC 230 V (N.O.)
  • Y12 Control output “Valve” AC 230 V (N.C.)

Connection diagrams

  • N1 RDF310.2/MM
  • V1 On/off valve AC 230 V
  • M1 3-speed fan

  • N1 RDF310.2/MM
  • V2 Electromotoric actuator, e.g. SUA21/1
  • M1 3-speed fan

  • N1 RDF310.2/MM
  • V3 3-wire on/off (SPDT) zone valve
  • M1 3-speed fan

Dimensions

© Siemens Switzerland Ltd, 2010 – 2019
Technical specifications and availability are subject to change without notice.
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a
CH-6300 Zug
Tel. +41 58 724 2424
www.swww.siemens.iemens.ccom/buildinom/buildingtechngtechnologologiieses
Siemens Smart Infrastructure
Flush-mounted Room Thermostat

REFERENCE:

DOWNLOAD MANUALS:

SIEMENS RDF310.2MM Flush-mounted Room Thermostat Product Specifications Guide

SIEMENS RDF310.2/MM Flush-mounted Room Thermostat Product Specifications Guide

wpx_thermostats

Recent Posts

Johnson Controls T7000e LCD Digital Thermostat Installation Guide

Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide

1 year ago

Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’S GUIDE

Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE

1 year ago

Hetta HS01RF WIRELESS THERMOSTAT KIT USER MANUAL

Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…

1 year ago

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat USER MANUAL

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…

1 year ago

Honeywell RLV450 PROGRAMMABLE THERMOSTAT USER GUIDE

Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…

1 year ago

Honeywell RLV431 Programmable Thermostat User Guide

Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…

1 year ago