The RDE100.1DHW is used to control the room temperature in heating systems with independent control of DHW.
Typical applications:
For the control of the following plant components and of DHW:
RDE100.. comprises of both 2-position and TPI temperature controls, which can be configured by parameter P78 (Control Behavior). 2-position control algorithm is to switch on and off the heating system within a switching differential according to comparison between setpoint setting and the measured room temperature.
TPI (Time proportional Integral) control algorithm is to periodically switch on and off the heating system. The period time and pulse length of the control signal (PWM) are determined by the setpoint and the measured room temperature.
Heating mode
Can only be used when circulating pump or valve is controlled! This function protects the pump or valve against seizing during longer off periods. Perodic pump run is activated for 3 minutes every 24 hours at 12:00.
Parameter | Pump status |
P12 = 0 (Default) | Pump run off |
P12 = 1 | Pump run on |
Optimum start control
The purpose of optimum start control is to reach a temperature level 0.25 K below the Comfort setpoint when occupancy according to the time program starts in Auto timer mode. For that purpose, the heating circuit must be switched on at an earlier point in time. The extent of forward shift depends primarily on the outside temperature. The maximum forward shift on time can be adjusted by parameter P89. A Forward shift on maximum “0” means the function is disabled.
Parameter | Range | Factory setting |
Forward shift on max (P89) | 0, 0.5,…24 h | 0 |
Optimum stop control
Optimum stop control switches off the heating circuit at the earliest possible point in time so that the room temperature will lay 0.5 K below the Comfort setpoint when the time switch changes from Comfort mode to the Economy mode in Auto timer mode. The early shut down maximum time can be adjusted by parameter P90. Early shut down maximum “0” means the function is disabled.
Parameter | Range | Factory setting |
Early shutdown max (P90) | 0, 0.5,….6 h | 0 |
TPI slow
TPI control behavior for slow heating systems that require longer minimum On times and limited numbers of switching cycles per hour. Typical applications:
Minimum switching on / off time | > 4 minutes |
Average period time | Approximately 20 minutes |
TPI medium
TPI control behavior for general heating applications such as radiator systems, thermal actuators, …
Minimum switching on / off time | > 1 minute |
Average period time | Approximately 20-25 minutes |
TPI fast
TPI control behavior for fast heating systems that tolerate a high number of switching cycles. Typical applications: electric heaters, gas boilers, fast thermal actuators.
Minimum switching on / off time | > 1 minute |
Average period time | Approximately 10 minutes |
Product No. | Stock No. | Features |
RDE100.1DHW | S55770-T280 | Battery-powered DC 3 V |
Ordering
Product No. | Stock No. | Description |
RDE100.1DHW | S55770-T280 | DHW room thermostat |
Description | Product No. | Data Sheet *) | Use with the type of Temperature Control | |
Electromotoric actuator | | SFA21.. | 4863 | 2-Position & TPI slow |
Electrothermal actuator (for radiator valves) | | STA23.. | 4884 | 2-Position & All TPI |
Electrothermal actuator (for small valves 2.5 mm) | | STP23.. | 4884 | 2-Position & All TPI |
Electromotor actuator for zone valves VVI46.. | | SUA21.. | 4830 | 2-Position |
Damper actuator | | GDB.. | 4634 | 2-Position & TPI slow |
Damper actuator | | GSD.. | 4603 | 2-Position & TPI slow |
Damper actuator | | GQD.. | 4604 | 2-Position & TPI slow |
Rotary damper actuator | | GXD.. | 4622 | 2-Position & TPI slow |
*) The documents can be downloaded from http://siemens.com/bt/download.
The room thermostat consists of 2 parts:
The housing engages in the mounting plate and is secured with a screw.
Symbol /Description
Do not mount the thermostat in niches or bookshelves, not behind curtains, not above or near heat sources, and not exposed to direct solar radiation. Mount about 1.5 m above the floor.
Mounting
Wiring
See the Mounting Instructions M1429 enclosed with the thermostat.
No internal line protection for supply lines to external consumers.
Risk of fire and injury due to short-circuits!
Commissioning
After power is applied, the thermostat carries out a reset during which all LCD segments flash, indicating that the reset was made correctly. After the reset, the thermostat is ready for commissioning by qualified HVAC personnel. The control parameters of the thermostat can be set to ensure optimum performance of the entire system. Please refer to Operating Instructions CB1B1423, section “Do you want to change parameters?”.
Sensor calibration
If the temperature on the display does not agree with the room temperature effectively measured, the temperature sensor can be recalibrated. For that purpose, adjust parameter P04.
Setpoint lock
We recommend reviewing the setpoint lock (for public areas) in parameters P06 and P08 and changing them as needed. If the Economy setpoint is locked then the Comfort temperature setpoint can not be set lower than the locked Economy setpoint.
Touchpad scanning rate
Since the thermostat uses touch technology and to minimize battery power consumption, a parameter P21 (adjustable from 0.25 to 1.5 seconds) is implemented for the user to adjust. This function is only valid for the battery-powered version and the default value is 1 second.
This means that when, for a certain time, the user does not touch the touchpad, the unit operates in power saving mode and the touchpad is running at a scanning rate of 1 second. (From the calculation – assuming 4 operations per day on the thermostat, the estimated 1-second scanning rate results in a battery life of 1 year. If the user increases the scanning rate, the battery’s life is extended.)
Change of batteries
If the battery symbol
The RDE100.1DHW provides Comfort, Economy, Auto timer and Protection mode. The difference between Comfort and Economy mode is only the room temperature setpoint. The changeover between Comfort, Economy and Protection mode is made either automatically by the auto time switch or by pressing touch key mode.
Comfort mode
Economy mode
Protection mode
Holiday mode
Time switch
When Auto timer mode is enabled, the changeover between the operating modes (Comfort and Economy mode) will take place automatically. There are three options for time switch setting: individual day, 7 day or 5-2 day. You can select Comfort or Economy mode in every 15 minutes interval of the day. The 0:00 to 24:00 hour time bar will allow you to set the mode throughout the selected day(s).
Factory default for 7-day Time switch
Default value | Day/s | Comfort mode | Economy mode |
Mo (1) – Fr (5) | 6:00 – 8:00 hr 17:00 – 22:00 hr | 22:00 – 6:00 hr 8:00 – 17:00 hr | |
Sa (6) – Su (7) | 7:00 – 22:00 hr | 22:00 – 7:00 hr |
Please refer to Operating Instructions CB1B1423, section “Do you want to enter your own Time switch?”.
DHW
Press
Factory default for 7-day Time switch for DHW
Default value | Day/s | DHW control ON | DHW control OFF |
Mo (1) – Fr (5) | 6:00 – 8:00 hr 17:00 – 22:00 hr | 22:00 – 6:00 hr 8:00 – 17:00 hr | |
Sa (6) – Su (7) | 7:00 – 22:00 hr | 22:00 – 7:00 hr |
Please refer to Operating Instructions CB1B1423, section “Do you want to enter your own Time switch for DHW control?”.
Changing the parameters by the following steps:
Parameter list
Parameter no. | Description | Setting range (default) |
P01 | Time format | 1 = 24:00 hours (default) 2 = 12:00 AM/PM |
P02 | Selection of °C or °F | 1 = °C (default) 2 = °F |
P03 | Standard temperature display | 1 = room temperature (default) 2 = setpoint |
P04 | Temperature sensor calibration | -3…3 °C Step 0.5 °C (-6…6 °F, step 1 °F) Default: 0 °C |
P06 | Comfort setpoint lock | 0 = OFF (default) 1 = ON è locked according to setting in permanent temperature setpoint |
P08 | Economy setpoint lock | 0 = OFF (default) 1 = ON è locked according to setting in permanent temperature setpoint |
P09 | Buzzer | 0 = OFF 1 = ON (default) |
P10 | Show frost protection icon | 0 = OFF (default) 1 = ON |
P11 | Time switch type for auto timer and DHW | 0 = Individual Days (default) 1 = All 7 days 2 = 5/2 days |
P12 | Periodic pump run | 0 = OFF (default) 1 = ON |
P13 | DHW timer bar timeout | 0 = no DHW bar 1 = 1 minute (default) 2 = 2 minutes Adjustable range 0 to 15 minutes |
P21 | Button scanning rate for the capacitive buttons Note: a higher scanning rate means shorter battery life. | 0.2 = 0.25 s 0.5 = 0.5 s 1.0 = 1.0 s (default) 1.5 = 1.5 s |
P22 | Reload factory settings | 0 = OFF (default) 1 = reload |
P23 | Software version information | No adjustment possible |
P78 | Control behavior | 0 = On/Off, 1.0 K 1 = On/Off, 0.3 K 2 = TPI fast 3 = TPI medium 4 = TPI slow (default) |
P89 | Forward shift on max | 0, 0.5,…24 h Default: 0 h |
P90 | Early shutdown max | 0, 0.5,…6 h Default: 0 h |
The device is considered an electronic device for disposal in terms of the European Directive 2012/19/EU and may not be disposed of as domestic garbage.
WARNING | ||
Risk of explosion due to fire or short-circuit, even if the batteries are empty Risk of injuries from by flying parts
|
WARNING | ||
Electrolyte leakage Chemical burns • Only grasp damaged batteries using suitable protective gloves. • If electrolyte comes into contact with eyes, immediately rinse eyes with plenty of water. Consult a doctor. |
Observe the following:
*) The documents can be downloaded from http://siemens.com/bt/download.
Legend
Legend
Room thermostat with direct control of a heating circuit pump (precontrol by manual mixing valve) and independent control of DHW.
All dimensions in mm
Heating: Because of the unavoidable self heating effects of the electrical current, any loads of more than 3 Amperes connected to the unit can influence the control behavior and temperature accuracy in a negative way.
© Siemens Switzerland Ltd., 2017
Technical specifications and availability are subject to change without notice.
RDE100.1DHW Room thermostat with Auto Timer, independent DHW
DOWNLOAD MANUALS:
SIEMENS RDE100.1DHW Room Thermostat Product Specifications Guide
OTHER MANUALS:
SIEMENS RDE100.1DHW Room thermostat Operating Manual
SIEMENS RDE100.1DHW Room Thermostat Product Specifications Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…