For heating applications
Room temperature control in a heating system:
Typical applications:
For the control of the following pieces of equipment:
The functional descriptions for the thermostat can be referred to the basic documentation P3174
The thermostat supports the heating applications:
Application Examples
Product no. | Stock no. | Operating voltage | Control outputs | Suitable for | ||
3-pos | ON/OFF | DC 0..10 V | ||||
RDD810/NF 2) | S55770-T406 | AC 230 V | — | 2 1) | — | Square conduit box 2) |
RDD810 3) | S55770-T443 | AC 230 V | — | 2 1) | — | Round or square conduit box |
Ordering
Equipment combinations
Type of unit | Product no. | Data sheet | |
Cable temperature sensor or changeover sensor cable length 2.5 m NTC (3 kW at 25 °C) | | QAH11.1 d) | 1840 |
Room temperature sensor NTC (3 kW at 25 °C) | QAA32 | 1747 | |
Cable temperature sensor, cable length 4 m NTC (3 kW at 25 °C) | QAP1030/UFH | 1854 | |
Electromotoric ON/OFF actuator | SFA21… | 4863 | |
Electromotoric ON/OFF valve and actuator a) | MVI…/MXI… | A6V11251892 | |
Zone valve actuators a) | SUA… | 4832 | |
Thermal actuator b) | STP..21.. | A6V12986007 | |
Thermal actuator c) | STA..21.. | A6V12986007 | |
Damper actuator | GDB.. | 4634 | |
Damper actuator | GSD.. | 4603 | |
Damper actuator | GQD.. | 4604 | |
Rotary damper actuator | GXD.. | 4622 |
Note:
Refer to data sheets of the actuators for the maximum number of parallel operation
Accessories
Designation | Product no. / SSN | Data sheet | |
Single mounting frame, Ivory White*) | | ARG800.1 / S55770-T370 | — |
*) See the dimensions of mounting frame on page 18.
Mechanical design
The thermostats consist of the following parts:
The rear of the mounting base contains the screw terminals. Slide the front panel in the mounting base and snap on
Status symbols: | |||
| Key lock | | Heating active |
| Alarm / Service reminder | ||
Selection symbols: | |||
Indoor temperature | | Comfort mode | |
| Protection mode | | Economy mode |
Operational icons: | |
+ ̶ | Increment, decrement OR selection |
Selection OR move to next items | |
| Temperature OR parameter values, and etc. |
| Parameter number OR password, and etc. |
| Setpoint mode (temperature only) |
| Operating mode |
| Setting mode |
Engineering notes
See the “Reference documentation”, page 14, for information on how to select and dimension connecting cables for supply voltage and field devices
Mount the room thermostat on a conduit box. Do not mount on a wall in niches or between bookshelves, behind curtains, above or near heat sources, or exposed to direct solar radiation. Mount about 1.5 m above the floor.
Wiring See the User Manual for the installation instructions enclosed with the thermostat.
Before power up
No DIP switch setting is required for RDD810… thermostats
Wizard function
After power up, the wizard function guides users to configure the basic parameters for normal operation according to the table below. Touch
LCD display | Parameter | Range | Factory setting |
User operating mode profile | 1: comfort > protection 2: comfort > economy > protection | 1 | |
Selection of ° C or °F | 0: °C 1: °F | 0 | |
Standard display | 0: Room temperature 1: Setpoint | 0 | |
Display info line (2nd line of LCD display) | 0: — (No display) 3: Time of day (12h) via bus 4: Time of day (24h) via bus | 0 | |
|
Functionality of X1 | 0: — No function 1: Ext / Return Temp (AI) 3: Window open detect (DI) 6: Fault input (DI) 7: Monitor input (Digital) 8: Monitor input (Temp) 10: Presence detection (DI) |
3 |
Functionality of X2 | 1 | ||
Operating action of X1 | Normal Open (NO) Normal Close (NC) | Normal Open (NO) | |
Operating action of X2 | |||
| – | End of wizard | – |
If more details are required about parameters, refer to basic documentation P3174.
Reset
To reload factory setting for all parameters, set parameter P71 to ON. Restart the thermostat after reset, all LCD segments flash, indicating that the reset is correct. 3 seconds later, the thermostat is ready for commissioning by qualified HVAC staff
Applications
RDD810… thermostats are for heating applications. Configure or changing parameter settings during commissioning using one of the following tools: − Local HMI
Setting parameters using the local HMI
Service level parameters
Parameter | Name | Factory setting | Range | Resolution |
Service level | ||||
P02 | User operating mode profile (mode button) | 1 = Comf – Protection | 1 = Comf – Protection
2 = Comf – Econ – Protection | |
P04 | Selection of °C or °F | 0 = °C (Degrees Celsius) | 0 = °C (Degrees Celsius)
1 = °F (Degrees Fahrenheit) | |
P05 | Sensor calibration (intern, extern) | 0 K | -5 K…+5 K | 0.5 K |
P06 | Standard temperature display | 0 = Room Temperature | 0 = Room Temperature
1 = Setpoint | |
P07 | Display info line
(2nd line of LCD) | 0 | 0 = — (No display)
1 = °C and °F | |
P08 | Comfort setpoint | 21 °C | 5…40 °C | 0.5 K |
P09 | Minimum setpoint in Comfort mode | 5 °C | 5…40 °C | 0.5 K |
P10 | Maximum setpoint in Comfort mode | 35 °C | 5…40 °C | 0.5 K |
P11 | Economy heating setpoint | 15 °C | OFF, 5…30 °C | 0.5 K |
P14 | Keylock function | 0 | 0 = Unlock
1 = Locked
2 = Setpoint | |
P16 | Buzzer function | ON = Enabled | ON = Enabled
OFF = Disabled |
Note: Parameter display depends on the selected application and function.
Expert-level parameters with diagnostics and test
Parameter | Name | Factory setting | Range | Resolution |
Expert level | ||||
P30 | P-band / Switching differential in heating mode | 2 K | 0.5…6 K | 0.5 K |
P38 | Functionality of X1 | 3 = Window open detection (DI) | 0 = — (no function)
1 = Room temp ext / Return temp (AI) 3 = Window open detection (DI) 6 = Fault input (DI) 10 = Presence detection (DI) | |
P39 | Operating action of X1 if digital input | 0 = Normally open / Open | 0 = Normally open / Open 1 = Normally closed / Close | |
P40 | Functionality of X2 | 1 = Room temp ext / Return temp (AI) | 0 = — (no function) 1 = Room temp ext / Return temp (AI) 3 = Window open detection (DI) 6 = Fault input (DI) 10 = Presence detection (DI) | |
P41 | Operating action of X2 if digital input | 0 = Normally open / Open | 0 = Normally open / Open
1 = Normally closed / Close | |
P48 | Minimum output on time 2-position control output | 1 min. | 1…20 minutes | 1 min. |
P49 | Minimum output off time 2-position control output | 1 min. | 1…20 minutes | 1 min. |
P51 | Floor heat limit temperature | OFF | OFF, 10..50 °C | 1 K |
P65 | Protection heating setpoint | 8 °C | OFF, 5 … WcoolPro;
WCoolPro = 40 °C max | 0.5 K |
P69 | Temporary setpoint comfort (see also comfort basic setpoint) | OFF = Disabled | OFF = Disabled ON = Enable | |
P71 | Reload factory setting | OFF = Disabled | OFF = Disable
ON = Reload factory setting Reload starts only after exits parameter mode. | |
P77 | Presence Detector Mode | 1: Standard Presence Mode | 1: Standard Presence Mode
2: Hotel Presence Mode |
Parameter | Name | Factory setting | Range | Resolution |
Diagnostics and test | ||||
d011) | Application no | Diagnose | H | |
d02 | X1 status | Diagnose
(display values according to the selected function of X1: DI, AI, HC changeover, etc) | 0 = Not activated (for DI) 1 = activated (DI) 0…49 °C = cur. temp. value (for AI) | |
d03 | X2 status | Diagnose
(display values according to the selected function of X1: DI, AI, HC changeover, etc) | 0 = Not activated (for DI) 1 = activated (DI) 0…49 °C = cur. temp. value (for AI) | 0.5 K |
d07 | Host software version
Show Ux.xx |
d01 shows H meaning heating.
Control parameters
The thermostat’s control parameters can be set to ensure optimum performance of the entire system (refer to basic documentation P3174). The parameters can be adjusted using Local HMI For commissioning via local HMI, refer to user manual B3174… for setting the passwords.
Control sequence
Only heating sequence is available
Calibrate sensor
Recalibrate the temperature sensor if the room temperature displayed on the thermostat does not match the room temperature measured (after min. 1 hour of operation). To do this, change parameter P05
Setpoint and range limitation
We recommend to review heating setpoint and their range limitation via parameters P08…P11. If necessary, adjust them to achieve maximum comfort and save energy
Disposal
The device is considered electrical and electronic equipment for disposal in terms of the applicable European Directive and may not be disposed of as domestic garbage.
RDD810/NF for square conduit boxes only
RDD810 for round conduit boxes
ARG800.1 single mounting frame for RDD810/NF
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58 724 2424 www.siemens.com/buildingtechnologies
© Siemens Switzerland Ltd, 2019 Technical specifications and availability subject to change without notice.
DOWNLOAD MANUALS:
SIEMENS RDD810 Flush mount touch screen room thermostat Product Specifications Guide
SIEMENS RDD810 Flush Mount Touch Screen Room Thermostat Product Specifications Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…