Designed for radiator and floor heating applications with either line contacts or dry contacts, and for wall-hung boiler applications with dry contacts
Room temperature control in a heating system:
Typical applications in …
For the control of the following equipment and applications:
The thermostat consists of two parts:
The rear side of the mounting base contains screw terminals. Slide the front panel in the mounting base and snap on. The thermostat fits on a square conduit box with 60.3 mm fixed centers.
RDD310/MM User Interface
Ordering
Type | Stock Number | Designation |
RDD310/MM | S55770-T358 | Room thermostat |
Delivery
Valve actuators should be ordered separately
On/Off actuators
Type of units | Product number | Data Sheet | |
Electromotoric ON/OFF valve and actuator (only available in AP, UAE, SA and IN) | | MVI…/MXI… | A6V11251892 |
Electromotoric ON/OFF actuator | | SFA21… | N4863 |
Thermal actuator (for radiator valve) AC 230 V, NO | | STA23… | N4884 |
Thermal actuator (for radiator valves) AC 24 V, NO | | STA73… | N4884 |
Thermal actuator AC 230 V (for small valves 2.5 mm) , NC | | STP23… | N4884 |
Thermal actuator AC 24 V (for small valves 2.5 mm), NC | | STP73… | N4884 |
Zone valve actuators (only available in AP, UAE, SA and IN) | | SUA… | N4832 |
Damper actuator | | GDB… | N4634 |
Damper actuator | | GSD… | N4603 |
Damper actuator | | GQD… | N4604 |
Rotary damper actuator | | GXD… | N4622 |
Title | Document ID |
Mounting Instructions | CB1M3066.1xx |
Operating Instructions | CB1B3066.1xx |
CE declarations | CB1T3066.1xx |
Environmental declarations | CB1E3066en |
All the documentation can be downloaded at the following Internet address: http://siemens.com/bt/download
Security
| CAUTION |
National safety regulations Failure to comply with national safety regulations may result in personal injury and property damage.
|
Mounting
Mount the thermostat on a recessed square conduit box with fixed centers of 60.3 mm. The mounting location on a wall should not be in niches or bookshelves, not behind curtains, above or near heat sources and wind outlets or inlets, and not exposed to direct radiation. The mounting height is about 1.5 m above the floor.
Refer to the Mounting Instructions CB1M3066.1xx enclosed with the thermostat.
WARNING | |
Wiring, protection and earthing must be installed in compliance with local regulations. No internal line protection for supply lines to external consumers (Q11, Q12, Q14 ). Risk of fire and injury due to short circuits! ● The AC 230 V mains supply line must have an external circuit breaker with a rated current of no more than 10 A. ● Adapt the line diameters as per local regulations to the rated value of the installed overcurrent protection device. ● Only use valves rated for AC 24…230 V. ● Disconnect from supply before opening the cover. |
Commissioning
After power up, the thermostat reset and all LCD segments flash, indicating that the reset is successful. This takes about 3 seconds. Then, the thermostat is ready for commissioning by qualified HVAC staff. The control parameters of the thermostat can be adjusted to ensure optimum performance of the entire system (see “Parameter settings”).
Calibrating the sensor
If the displayed room temperature does not match the actual temperature, you can calibrate the temperature sensor by modifying the parameter P07.
Setpoint and range limitation
For the purpose of energy saving, it is suggested to review the setpoints and setpoint ranges (parameters P03, P05 and P06). Change the setpoint to suit your individual needs.
Control sequence
Only heating sequence is available.
ON
The valve or compressor receives the OPEN command via control output Q14 when both of the following conditions are met.
OFF
The valve or compressor receives the CLOSE command via control output Q14 when both of the following conditions are met.
Minimum output on/off time Q14 and Q12
The minimum output on/off time of Q14 and Q12 is 1 minute by default. It means that any readjustment of the setpoint will be hold for 1 minute before Q14 and Q12 react.
Parameter settings
To optimize the control performance, you can use local HMI to adjust a number of control parameters. All control parameter settings will be retained or restored with power loss. Proceed as follows to change the control parameters:
Parameter reset
Parameter | Description | Setting range | Factory setting |
P03 | Setpoint of heating in Protection Mode | OFF, 5…40°C | 8 °C |
P05 | Minimum setpoint limitation in Comfort Mode (WminNorm) | 5 °C…WmaxNorm | 5 °C |
P06 | Maximum setpoint limitation in Comfort Mode (WmaxNorm) | WminNorm…40 °C | 35 °C |
P07 | Sensor calibration | -3…3 K | 0 K |
P08 | Switching differential heating SDH | 0.5…4 K | 1 K |
P17 | Selection of °C or °F | °C or °F | °C |
P18 | Display of room temperature or setpoint | OFF: Setpoint ON: Room temperature | ON |
Temperature control
The thermostat acquires the room temperature via its built-in sensor and maintains the setpoint by delivering 2-position valve control commands. The switching differential is 1 K in heating mode (factory setting, adjustable via parameter P08).
Display
The current room temperature or the setpoint of the current operating mode (adjustable via parameter P18) displays on the screen. Factory setting is to display the current room temperature. The heating symbol
Operating Mode
The thermostat provides both Comfort Mode and Protection Mode.
Comfort Mode
In Comfort mode, press the + / – buttons to maintain the heating setpoint.
Protection Mode
In Protection mode, the heating setpoint (adjustable via parameter P03) is maintained. Factory setting of heating setpoint is 8 °C.
Switching differential heating (SDH)
The temperature hysteresis range (adjustable via parameter P08) controls the activation/deactivation of heating output. Factory setting of SDH is 1 K.
Disposal
The device is considered an electronic device for disposal in accordance with the European Guidelines and may not be disposed of as domestic garbage.
Technical data on specific applications are valid only together with Siemens products listed under “Equipment combinations”. Siemens rejects any and all warranties in the event that third-party products are used.
Power supply | |
Operating voltage | AC 230 V +10%/-15% |
Frequency | 50/60 Hz |
Power consumption | Max. 8 VA |
Input relay | |
Control input Q11 Rating | AC 24…230 V 5 mA…4(2) A |
Output relay | |
Control output Q14 (N.O.) / Q12 (N.C.) Rating | AC 24…230 V 5 mA…4(2) A |
Operational data | |
Switching differential – Heating mode | 0.5…4 K (factory setting: 1 K) |
Setpoint setting range – Comfort mode – Protection mode | 5…40 °C (factory setting: 20 °C) OFF, 5…40 °C (factory setting: 8 °C)) |
Built-in room temperature sensor – Measuring range – Accuracy at 25 °C – Temperature calibration range | 0…49 °C <±0.5 K ±3.0 K |
Resolution of settings and display – Temperature setpoints – Current temperature value displayed | 0.5 °C 0.5 °C |
Ambient Conditions and protection classification | |
Classification as per EN 60730 – Devices of safety class – Pollution class | II II |
Degree of protection of housing to EN 60529 | IP30 |
Climatic ambient conditions – Storage as per EN 60721-3-1 – Transport as per EN 60721-3-2 – Operation as per EN 60721-3-3 | Class 1K3 Class 2K3 Class 3K5 1) |
Standards, directives and approvals | |
EU conformity (CE) | CB1T3066.1xx |
RCM conformity | A5W90002893 |
Environmental compatibility | The product environmental declaration (CB1E3066en ) contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal). |
Housing flammability class according to UL94 | V-0 |
All the documentations can be downloaded at the following Internet address: http://siemens.com/bt/download.
No condensation is allowed
General | |
Connection terminals | Solid wires or prepared stranded wires: 1×0.4-1.5 mm2 |
Weight | 0.17 kg |
Color of front housing | White, RAL 9003 |
Connection terminals
Wall-hung boiler AC 230 V
Floor/Radiator heating AC 24 V
The thermostat supports the heating applications:
Room thermostat controls the valve of the floor heating or radiator application Room thermostat directly controls a gas-fired wallhung boiler N1 Room thermostat RDD310/MM Y1 2-port valve
Issued by
Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a
© Siemens Switzerland Ltd, 2015 – 2019 Technical specifications and availability subject to change without notice
DOWNLOAD MANUALS:
SIEMENS RDD310MM Flush mount room thermostat Product Specifications Guide
SIEMENS RDD310/MM Flush Mount Room Thermostat Product Specifications Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…