The 2218 Series Pneumatic Room Thermostats are designed for proportional control of pneumatic valves and damper actuators in environmental control systems where a dual-pressure air main is utilized for seasonal changeover of heating and cooling functions. Their design incorporates a highly sensitive, bimetal, thermostatic element, and a pilot-operated relay with pneumatic feedback for accuracy and stability over the entire operating range. Indexing the thermostat from summer control (reverse acting) to winter control (direct acting), or vice versa, is accomplished by remotely changing the main air pressure supply from 16 psig (summer) to 25 psig (winter). Models are also available that operate on slightly different pressures to replace many competitive devices. These thermostats have a serrated thumb wheel for setpoint adjustment. Models are also available with preassembled internal dial stops. Thermostat covers are available in various styles to meet particular requirements. Cover options include models with a setpoint scale and a thermometer, a setpoint scale only, a thermometer only, or blank. An external setpoint adjustment cover is available on some models or can be field-installed on covers where desired.
Environment
Humidity: 5 to 95% relative humidity, non-condensing. Locations: NEMA Type 1.
Table-1 Model Chart — Thermostats
Wholesale Number | Replaces Model | Action | Setpoint Range | Calibration Point | Throttling Range | Air Consumption | Description |
2218-132 | T32-301 | RA @ 16 psig DA @ 25 psig |
55 to 85 °F (13 to 29 °C) |
12 psig branch line pressure |
Adjustable 2 to 12 °F (1 to 7 °C) |
17 scim @ 16 psig 30 scim @ 25 psig |
Includes (2) 1/4″ x 3/16″ barbed couplings, 20-693 tubing, 20-714 wall plate, 20-711 mounting plate, and mounting screws. |
2218-142a | T32-3011 | ||||||
2218-133 | T33-301 | DA @ 16 psig RA @ 25 psig | |||||
2218-134 | T32-321 | RA @ 13 psig DA @ 18 psig | |||||
2218-301ab | T34-3011 | RA @ 16 psig (summer) DA @ 25 psig (winter) | Winter = 44 to 74 °F (7 to 23 °C) Summer = 76 to 85 °F (24 to 29 °C) | 9 psig branch line pressure | Fixed 4 °F (2 °C) Nominal 2 °F (1 °C) | 30 scim @ 16 psig 43 scim @ 25 psig |
Table-2 Model Chart — Uni-Kits®
Wholesale Number | Replaces Model | Action | Setpoint Range | Calibration Point | Throttling Range | Air Consumption | Description |
2218-532a | T32-3011 |
RA @ 16 psig DA @ 25 psig | 55 to 85 °F (13 to 29 °C) | 12 psig branch line pressure | Adjustable 2 to 12 °F (1 to 7 °C) | 17 scim @ 16 psig 30 scim @ 25 psig | Includes thermostat with stops, 21-933 full dial cover with blank cover conversion, and 22-022 conversion kit. |
2218-534ab | T34-3011 | Winter = 44 to 74 °F (7 to 23 °C) Summer = 76 to 85 °F (24 to 29 °C) | 9 psig branch line pressure | Fixed 4 °F (2 °C) Nominal 2 °F (1 °C) | 30 scim @ 16 psig 43 scim @ 25 psig | ||
2218-632 |
T32-301 | 55 to 85 °F (13 to 29 °C) | 12 psig branch line pressure | Adjustable 2 to 12 °F (1 to 7 °C) | 17 scim @ 16 psig 30 scim @ 25 psig | Includes thermostat, 22-1033 full dial cover with blank cover conversion, and 22-023 conversion kit. |
Table-3 Covers
Wholesale Number | Replaces Model | Color | Material | Dial Markings | Setpoint Adjustment | Thermometer |
21-923 | C1-42 | Satin Chrome | Metal | 55 to 85 °F |
Yes |
No |
22-923 | C1-46 | Plastic | ||||
22-823 | C1-47 | Beige | ||||
22-1023 | C1-48 | Euro-white | 10 to 30 °C | |||
21-928a | C2-42 | Satin Chrome | Metal |
Blank |
Concealed | |
22-928a | C2-46 | Plastic | ||||
22-828a | C2-47 | Beige | ||||
22-1028a | C2-48 | Euro-white | ||||
21-933 | C3-42 | Satin Chrome | Metal | 55 to 85 °F |
Yes |
Yes (External) |
22-933 | C3-46 | Plastic | ||||
22-833 | C3-47 | Beige | ||||
22-1033 | C3-48 | Euro-white | 10 to 30 °C | |||
21-939a | C4-42 | Satin Chrome | Metal | 55 to 85 °F |
Concealed | |
22-939a | C4-46 | Plastic | ||||
22-839a | C4-47 | Beige | ||||
22-1039a | C4-48 | Euro-white | 10 to 30 °C |
Table-3 Covers. (Continued)
Wholesale Number | Replaces Model | Color | Material | Dial Markings | Setpoint Adjustment | Thermometer |
21-943 | C5-42 | Satin Chrome | Metal |
Cooler – Warmer |
Yes |
No |
22-943 | C5-46 | Plastic | ||||
22-843 | C5-47 | Beige | ||||
22-1043 | C5-48 | Euro-white | ||||
21-948 | C6-42 | Satin Chrome | Metal | |||
22-948 | C6-46 | Plastic | ||||
22-848 | C6-47 | Beige | ||||
22-1048 | C6-48 | Euro-white | ||||
21-957a | C11-42 | Satin Chrome | Metal |
None |
Concealed | Yes (External) |
22-957a | C11-46 | Plastic | ||||
22-857a | C11-47 | Beige | ||||
22-1057a | C11-48 | Euro-white | ||||
21-960a | C14-42 | Satin Chrome | Metal |
Blank |
Concealed | Yes (Internal) |
22-960a | C14-46 | Plastic | ||||
22-860a | C14-47 | Beige | ||||
22-1060a | C14-48 | Euro-white | ||||
2890-010a | Kit | Satin Chrome | Metal | 55 to 85 °F or Blank | Yes or Concealed |
No |
2890-011a | Kit |
Plastic | ||||
2890-012a | Kit | Beige | ||||
2890-013a | Kit | Euro-white | 10 to 30 °C or Blank |
Table-4 Accessories
Wholesale Number | Replaces Model | Description |
20-676 | 10-18 | Aspirating box, stainless steel |
20-695 | 10-15 | Aspirating box, satin finish |
20-707 | 10-53 | Metal thermostat guard |
20-712 | 10-59 | Internal stop kit |
20-715 | 10-62 | Clear cover thermostat guard |
20-850 | — | Thermostat mounting plate |
20-881 | N2-4 | Thermostat calibration wrench |
21-473 | 10-73 | Drywall mounting bracket |
21-800 | 10-72 | Setpoint adjustment cover (black) |
21-801 | 10-81-48 | Setpoint adjustment cover (Euro-white) |
21-876 | 10-76 | Opaque cover thermostat guard |
22-022 | — | Thermostat conversion kit |
22-023 | — | Thermostat conversion kit |
22-138 | MCS-GA | Branch tap gauge adaptor |
900-002 | — | Thermostat calibration kit |
Inspection
Inspect the package for damage. If damaged, notify the appropriate carrier immediately. If undamaged, open the package and inspect the device for obvious damage. Return damaged products.
Requirements
Location
Caution:
Locate the thermostat where it will be exposed to an unrestricted circulation of air, which represents the average temperature of the controlled space.
Standard Mounting Options
Mount the thermostat according to the applicable figure (Figure-2 through Figure-8). See Figure-11 for mounting dimensions.
Figure-4 Thermostat Mounted with 22-022
Conversion Kit, Using Wall Plate and Skirt, to Replace Competitive Thermostats
Thermostat Mounted with 22-022
Figure-6 Thermostat Mounted with 22-023 Thermostat
Conversion Kit.
Figure-7 Thermostat Installation Using
Pipehead in Masonry Wall.
Figure-8 Surface Mounting of Thermostat,
Pipehead Application.
Optional Mounting
Eliminate the pipe head fitting by using the 22-022 thermostat conversion kit and the included instructions, plus the following:
Calibration of Single Bimetal Models
The 2218 series thermostats are factory calibrated with the throttling range set at 3 °F. They should not require calibration upon installation. However, if the throttling range is changed, or if limited summer control action at 8 psig main air pressure is required, recalibrate the thermostat as follows:
Standard Calibration
Special Calibration — 8 psig Summer Control
Switch Over Point Adjustment
If necessary, adjust the switch point as follows:
Note:
The switch point adjustment requires changes to the main air pressure, which could affect other parts of the system. This adjustment should instead be made on a test bench at which a variable main air supply is available.
Install a test gauge into the branch line, so that this pressure can be measured while making the switch point adjustment.
Calibration of Dual Bimetal Models
The 2218-301 thermostat is factory calibrated and should not require calibration upon installation. However, if the summer or winter setpoint requires calibration, or if the switch point
needs to be raised or lowered, recalibrate the thermostat as follows:
Summer Setpoint Calibration
Winter Setpoint Calibration
Switch Over Point Adjustment
Adjust the switch over point as follows:
Note:
The switch point adjustment requires changes to the main air pressure, which could affect other parts of the system. This adjustment should instead be made on a test bench at which a variable main air supply is available.
Install a test gauge into the branch line, so that this pressure can be measured while making the switch point adjustment.
Concealed Adjustment
If concealment of the setpoint adjustment is required, install a 21-800 (black) or 21-801 (Euro-white) setpoint adjustment cover as follows:
Internal Stop Kit (Accessory)
The internal stop kit, model 20-712, consists of two screws and two nuts (Figure-9 and Figure-10). Install this kit as follows:
The thermostat requires no maintenance. Regular maintenance of the total system is recommended to assure sustained, optimum performance.
FIELD REPAIR
None. Replace an inoperative thermostat with a functional unit.
DIMENSIONAL DATA
Copyright 2006, TAC
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
TAC
1354 Clifford Avenue
P.O. Box 2940
Loves Park, IL 61132-2940
Download Manual:
Schneider Electric 2218 Pneumatic Room Thermostats User Manual
Schneider Electric 2218 Pneumatic Room Thermostats User Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…