Product Compliance
This product complies with the essential requirements and other relevant provisions of Directives 2014/53/EU and 2011/65/EU. The full text of the EU Declaration of Conformity is available at the following internet address: www.saluslegal.com.
Safety Informations
WARNING!
Care for the natural environment is of paramount importance to us. The awareness that we manufacture electronic devices obliges us to dispose of used electronic components and devices safely. Therefore the company has received a registration number issued by the Chief Inspector for Environmental Protection. The crossed out symbol the trash can on the product means that the product must not be disposed of with ordinary waste containers. Sorting waste for recycling helps to protect the environment. It is the user’s responsibility to surrender used equipment to a designated collection point for recycling waste from electrical and electronic equipment.
The BTRP230V(50) from SALUS Controls is a stylish and accurate 5/2 or 24h programmable electronic thermostat with a large, easy to read Liquid Crystal Display (LCD). It is flush-mounted (in a 55 mm frame) temperature controller dedicated for surface heating / cooling, characterized by high thermal inertia. It is connected to the wired wiring centre KL08NSB. Thermostat has the function of creating your own schedules. It can control group (SLAVE) thermostats – via wiring centre it sends them an NSB (nighttime temperature reduction) signal and switches them to economic temperature. The time schedule is common to all thermostats (according to weekly (MASTER) thermostat), but temperatures are set individually on each thermostat.
The programmable room thermostat BTRP230V(50) is both a programmer and a room thermostat. A programmer allows you to set ‘ON’ and ‘OFF’ time periods to suit your own lifestyle. A room thermostat works by sensing the air temperature, switching on the heating when the air temperature falls below the thermostat setting and switching it off once this set temperature has been reached.
So, a programmable room thermostat lets you choose what times you want the heating to be on, and what temperature it should reach while it is on. It will allow you to select different temperatures in your home at different times of the day (and days of the week) to meet your particular needs.
Turning a programmable room thermostat to a higher setting will not make the room heat up any faster. How quickly the room heats up depends on the design of the heating system, for example, the size of boiler. Neither does the setting affect how quickly the room cools down. Turning a programmable room thermostat to a lower setting will result in the room being controlled at a lower temperature, and saves energy.
The way to set and use your programmable room thermostat is to find the lowest temperature settings that you are comfortable with at the different times you have chosen, and then leave it alone to do its job. The best way to do this is to set low temperatures first, say 18°C, and then turn them up by one degree each day until you are comfortable with the temperatures. You won’t have to adjust the thermostat further. Any adjustments above these settings will waste energy and cost you more money.
PRODUCT ADVANTAGES:
Package content
Proper thermostat location
Please note:
The ideal position to thermostat mounting is about 1,5m under floor level far from heating or cooling sources. Thermostat can’t be exposed to sunlight or any extreme conditions like for example draft.
Because of fire and explosion risk there is not allowed to use thermostat in atmosphere of explosive gases and flammable liquids (eg coal dust). In case if any of listed dangers occur you have to use additional protection measures – anti-dust and explosive gases (tight cover) or prevent their formation. Furthermore, thermostat can’t be used in condensation of water vapor conditions and be exposed to water action.
Mounting: to mount thermostat you can use accesories included with the set (mounting screws). Remove back housing to mount it to the wall box. After attachement put together front and back housing.
Connection description
I A – 4 wire installation with KL08NSB wiring centre
When HTRP230V(50) thermostat works as a MASTER (group controller) it means it takes control of SLAVE thermostats e.g. HTRS230V(30), HTR230V(20). MASTER thermostat controls SLAVE thermostat only when SLAVE thermostat is in AUTO mode. Comfort (SUN) and economy (MOON) setpoint temperatures are set individually on each thermostat but switching between those temperature is based on time schedule taken from HTRP230(50) thermostat which works like a group controller. Functions such as: setpoint temperature change, holiday mode, party mode or frost protection mode are not managed by MASTER thermostat.
I B – 4 wire installation with KL06 wiring centre
Pump logic module (for KL06) connection diagram
Pump and boiler logic module (for KL06) connection diagram
3 wire installation with KL08NSB wiring centre
3 wire installation with KL08NSB wiring center. Description of the operation rules:
work with RM-16A relay module – volt-free heating source control
work with RM-16A relay module – connection to a solid fuel boiler controller
PLEASE NOTE! Activate the thermostat in the solid fuel boiler controller.
Work with RM-16A relay module – connecting an electrical device with a higher power than the thermostat relay allows
PLEASE NOTE! The maximum current consumption of an electrical device should not exceed 16A.
LCD icon description
PLEASE NOTE! The LCD screen can be activated by using any button.
HTRP230V(50) offers a few work modes. Frame on a given icon indicates which mode is currently active. In manual mode
Example – comfort temperature mode setpoint editing:
Schedule mode
Programming schedule To program schedule, please follow steps below:
There are 4 possible schedule variants. Use
Schedule programming example for the WORKING DAYS variant:
Repeat steps 5 and 9 for the next time periods in the schedule to set whole program for selected variant. No time –:– on the display means given program is skipped. There are 6 programs/time periods in the schedule. Hold button for 3 seconds to save and exit schedule editing.
To run the schedule (activate thermostat’s automatic mode), use
In addition to editing and creating your own schedule, there are also 5 default profiles for built-in schedules. You can select and customize any of the programs listed below. Default programs are selectable through Installer Parameters (parameter D17).
To set time/date follow steps below:
DATE settings will automatically appear after clock setup:
Thermostat calibration is a function which allows user to recalibrate internal thermostat’s temperature sensor by a given number of degrees (in the range from -3,0 °C to 3,0 °C in 0,5 °C steps). To calibrate thermostat’s temperature sensor please follow steps below:
The heating / cooling mode for the thermostat can be changed manually or automatically via „CO” terminal. If 230V power is applied to the „CO” terminal – then thermostat automatically switches to cooling mode. If you use this function in automatic mode, set the d18 parameter value to „1”.
MANUALLY:
AUTOMATICALLY:
By external ON/OFF switch:
To enter installer parameters please follow steps below. Please refer to parameters table description before any changes. Use
dXX | Function | Parameter Values | Description | Default Values |
d01 |
Heating Control | This parameter defines the algorithm of the room temperature control. | ||
0 | PWM (Pulse-width modulation) algorithm ensures reduction of overdrive states and economic operation of the system. It is an advanced algorithm designed to precisely maintain room temperature. |
0 | ||
1 | SPAN ± 0.25°C | |||
2 | SPAN ± 0.5°C | |||
d02 | Room temp. offset | -3.0°C to + 3.0°C | Offset room temperature measuring is a function which allows user to recalibrate internal thermostat’s temperature sensor by a given number of degrees (in the range from -3,0 °C to 3,0 °C in 0,5°C steps). | 0.0°C |
d03 | OUT sensor probe (S1/S2) | 0 | Out sensor probe not connected | 0 |
1 | Out sensor probe connected | |||
d04 |
Air sensor or Floor sensor | 0 | Air sensor: If parameter d03 is inactive (d03 = 0) then internal sensor controls the temperature Air sensor: If parameter d03 is active (d03 = 1) then internal sensor is disabled and OUT sensor controls the temperature |
0 |
1 | Floor sensor: If parameter d03 is inactive (d03 = 0) then internal sensor controls the temperature Floor sensor: If parameter d03 is active (d03 = 1) then internal sensor is disabled and OUT sensor controls the floor protection temperature |
dXX | Function | Parameter Values | Description | Default Values |
d05 | Cooling Control | 1 | SPAN ± 0.25°C (± 0.5°F) | 2 |
2 | SPAN ± 0.5°C (± 1.0°F) | |||
d07 |
Valve Protection |
1 | Enable. Valve protection function is intended to protect thermostatic valves against getting stuck or jamming (e.g. in summer time when heating system is disa- bled). If thermostatdoesn’tsendasignalforheatingforaperiodof 7 days, then heating is turned on for a very short period of time just to move the actuators. |
1 |
d08 | Frost Setpoint | 5°C – 7°C | In Frost protection mode the thermostat is displaying actual room tem- perature and maintain „frost protection” setpoint temperature specified in thermostat settings. When thermostat works in Frost protection mode then you have no possibilities to change temperature setpoint. | 5.0°C |
d09 | 12/24 Hour Format | 0 | 12hours | 1 |
1 | 24hours | |||
d10 | Time zone (reserved for internet wireless) | from -13 to +13 hours | It gives you the possibility to fit the thermostat time zone to yours (every 1 hour step). | 0 |
d11 | Daylight Saving Time (DST) | 0 | Off | 1 |
1 | On | |||
d12 | Maximum limitation of heating setpoint | 5°C – 35°C | This parameter allows to limit temperature setpoint range by setting maximum setpoint for heating and cooling modes. Default temperature setting range: 5⁰C – 35⁰C | 35°C |
d13 | Minimum limitation of cooling setpoint | 5°C – 40°C | This parameter allows to limit temperature setpoint range by setting minimum setpoint for heating and cooling modes. Default temperature setting range: 5⁰C – 40⁰C | 5°C |
d14* | Floor sensor protection limit (heating high limit-HL) | 11°C – 45°C | Turn off relay output when floor sensing temp > protecting limit, step is 0.5°C | 27°C |
d15* | Floor sensor protection limit (heating low limit-LL) | 6°C – 40°C | Turn on relay output when floor sensing temp < protecting limit, step is 0.5°C | 10°C |
d16* | Floor sensor protection limit (cooling) | 6°C – 45°C | Turn off relay output when floor sensing temp < protecting limit, step is 0.5ºC | 6°C |
d17 | Preset program selection | 1-5 | Select one of these 5 default programs. Once selected, default program will overwrite present program. Selected default program can be edited by the user in the User Setting Mode. | 1 |
d18 | Heat/Cool Mode Selection | 0 | No connection | 0 |
1 | Connection | |||
d19** | Cooling Blocked | 0 | Cooling disabled | 0 |
1 | Cooling allowed | |||
d20 | Actuators loading selection for different temperature compensation. | 1 | x1 actuator loading |
1 |
2 | x2 actuators loading | |||
3 | x3 actuators loading | |||
4 | x4 actuators loading | |||
5 | x5 actuators loading |
Parameters d14, d15, d16 will be available only if parameter d04 is active (d04=1).
Cooling Blocked – at „1” we block cooling for a single room until the device receives a heating command. During the blocking of the cooling function no message is displayed.
Please note!
d19 parameter will be available only if d18 is set on 1.
To RESET BTRP230V(50) thermostat to it’s factory default settings please follow steps below:
Thermostat constantly monitors the operation of connected sensors. If it detects any failure then following error codes can be displayed.
Error code | ERROR DESCRIPTION | TROUBLESHOOTING |
Err02 | The maximum / minimum floor temperature has been exceeded | • Set the heating / cooling medium temperature or change D14 / D15 parameter. |
Err03 | Floor sensor is faulty | • If floor sensor is connected to S1/S2 input, check the wiring. • If floor sensor is not connected, check the D03/D04 parameters settings. |
Err04 | Floor sensor is shorted | • Check floor sensor wire insulation for any damages. Sensor resistance for 25°C=10kΩ. |
The HTRP230V(50) thermostat requires no special maintenance. Periodically, the outer casing can be wiped clean using a dry cloth (please DO NOT use solvents, polishes, detergents or abrasive cleaners, as these can damage the thermostat). There are no user serviceable parts within the unit; any servicing or repairs could only be carried out by Salus Controls or their appointed agents.
Power supply | 230 V AC 50 Hz |
Rating max | 0,5 A |
Temperature setback | Adjustable |
Temperature range | 5°C – 35°C |
Span | +/- 0,5°C |
Storage temperature | -20°C to +60°C |
Ambient temperature | 0 °C up to 45 °C |
Degree of protection | IP 30 |
CE conformity according to | Class II ( EN60730 ) |
Housing material | PC, V2 |
Color | RAL 9010 pure white |
Control method | PWM algorithm Hysteresis +/-0,5ºC or +/-0,25ºC |
Connection | Screw terminal |
Weight | 125 g net / 170 g gross |
Puls-wide-modulation (PWM) | Yes |
Clock, Timer | Yes, programmable |
Heating and Cooling | Yes, automatic modes changeover through CO terminal |
Parameter adjustment | Yes, in Installer Mode |
Dimensions | 85mm x 85mm x 25mm |
SALUS Controls warrants that this product will be free from any defect in materials or workmanship, and shall perform in accordance with its specification, for a period of five years from the date of installation. SALUS Controls sole liability for breach of this warranty will be (at its option) to repair or replace the defective product.
DISTRIBUTOR OF SALUS CONTROLS:
QL CONTROLS Sp. z o.o., Sp. k. Rolna 4,
43-262 Kobielice,
Poland
IMPORTER:
SALUS Controls Plc
Units 8-10 Northfield Business Park Forge Way, Parkgate
Rotherham
S60 1SD
United Kingdom
www.salus-controls.com
SALUS Controls is a member of the Computime Group.
Maintaining a policy of continuous product development SALUS Controls plc reserves the right to change the specification, design, and materials of products listed in this brochure without prior notice.
Download Manual:
SALUS HTRP230(50) Wired Digital THERMOSTAT User Manual
SALUS HTRP230(50) Wired Digital THERMOSTAT Quick Guide
SALUS HTRP230(50) Wired Digital THERMOSTAT Wiring Diagram
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…