Pro1

Pro1 T755s Non-Programable Thermostats Installation Manual

Pro1 T755s Non-Programable Thermostats

Thermostat Application Guide

Description
Gas or Oil Heat Yes
Electric Furnace Yes
Heat Pump (No Aux. or Emergency Heat) Yes
Heat Pump (With Aux. or Emergency Heat) Yes
Multi-Stage Systems Yes
Heat Only Systems Yes
Heat Only Systems – Floor or Wall Furnace Yes
Cool Only Systems Yes
Millivolt Yes

Power Type

  • Battery Power
  • Hardwire (Common Wire)
  • Hardwire (Common Wire) with
  • Battery Backup

A trained, experienced technician must install this product.
Carefully read these instructions. You could damage this product or cause a hazardous condition if you fail to follow these instructions.

Wall Locations

The thermostat should be installed approximately 4 to 5 feet above the floor. Select an area with average temperature and good air circulation.

Do not install thermostats in locations:

  • Close to hot or cold air ducts
  • That are in direct sunlight
  • With an outside wall behind the thermostat
  • In areas that do not require conditioning
  • Where there are dead spots or drafts (in corners or behind doors)
  • Where there might be concealed chimneys or pipes

Installation Tip

Pick an installation location that is easy for the user to access. The temperature of the location should be representative of the building.

Subbase Installation

  1. Horizontal Mount
  2. Vertical Mount

For vertical mount put one screw on the top and one screw on the bottom.
For horizontal mount put one screw on the left and one screw on the right.

Installation Tip: Electrical Hazard

Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.

Mercury Notice

All of our products are mercury-free. However, if the product you are replacing contains mercury, dispose of it properly. Your local waste management authority can give you instructions on recycling and proper disposal or you can mail the thermostat to the address on the warranty section for proper disposal.

Installation Tips

Mount Thermostat


Align the 4 tabs on the subbase with corresponding slots on the back of the thermostat, then push gently until the thermostat snaps in place.
Battery Installation


Battery installation is recommended even if the thermostat is hardwired (C terminal connected). When the thermostat is hardwired and batteries are installed, the thermostat will activate a compressor delay of 5 minutes when the thermostat detects a power outage from the hardwired power supply.

Important:
High-quality alkaline batteries are recommended. Rechargeable batteries or low-quality batteries do not guarantee a 1-year life span.

About The Private Label Badge

All of our thermostats use the same universal magnetic badge. Visit the company website to learn more about our free private label program.

Gently slide a screwdriver into the bottom edge of the badge. Gently turn the screwdriver counterclockwise. The badge is held on by a magnet in the well of the battery door. The badge should pry off easily. DO NOT USE FORCE.

Getting to know your thermostat

  1. LCD Display
  2. Glow in the dark light button
  3. Fan Button
  4. System Button
  5. Temperature Setpoint Buttons
  6. User Buttons
  7. Private Label Badge

Thermostat Quick Reference

Getting to know your thermostat

  1. Indicates the current room temperature
  2. Time and day of the week
  3. Low Battery Indicator: Replace batteries when this indicator is shown.
  4. Menu Options: Shows different options.
  5. Program Time Periods: This thermostat has 4 programmable time periods per day.
  6. System Operation Indicators:
    The COOL ON , HEAT ON, or icon will display when the COOL, HEAT, or (fan) is on. The compressor delay feature is active if these are flashing.
  7. The hold is displayed when the thermostat program is permanently overridden.
  8. Setpoint: Displays the selected setpoint temperature.
  9. System: Indicates current mode of operation.
  10. Stages: Stage 1 will appear on the display when the 1st stage of heat or cool is on. +2 will appear on the display when the 2nd stage of heat or cool is on. +3 will appear on the display when the 3rd stage of heat or cool is on.
  11. Globe: Globe is displayed if an energy-efficient temperature has been selected.

Important

The low battery indicator is displayed when the AA battery power is low. If the user fails to replace the battery within 21 days, the screen will only show the low battery indicator but maintain all functionality. If the user fails to replace the batteries after an additional 21 days (days 22-42 since the first “low battery” display) the setpoints willchange to 55˚F (Heating) and 85˚F (Cooling). If the user adjusts the setpoint away from either of these, it will hold for 4 hours then return to either 55˚F or 85˚F. After day 63 the batteries must be replaced immediately to avoid freezing or overheating because the thermostat will shut the unit off until the batteries are changed.

Wiring

  1. If you are replacing a thermostat, make note of the terminal connections on the thermostat that is being replaced. In some cases the wiring connections will not becolor coded. For example, the green wire may not be connected to the G terminal.
  2. Loosen the terminal block screws. Insert wires then retighten terminal block screws.
  3. Place non-flammable insulation into wall opening to prevent drafts.

Caution:
Electrical Hazard

Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.

Warning

All components of the control system and the thermostat installation must conform to Class II circuits per the NEC Code.

Terminal 2 Heat 2 Cool Conventional System 2 Heat 2 Cool Heat Pump System 3 Heat 2 Cool Heat Pump System
RC Transformer power (cooling) Transformer power (cooling) Transformer power (cooling)
RH Transformer power (heating) Transformer power (heating) Transformer power (heating)
C Transformer common Transformer common Transformer common
B Energized in heating Heat pump changeover valve energized in heating Heat pump changeover valve energized in heating
O Energized in cooling Heat pump changeover valve energized in cooling Heat pump changeover valve energized in cooling
G Fan relay Fan relay Fan relay
W/E The first stage of heat The first stage of emergency heat The first stage of emergency heat
W2 The second stage of heat Auxiliary heat relay, the second stage of heat Auxiliary heat relay, third stage of heat
Y The first stage of cool The first stage of heat & cool The first stage of heat & cool
Y2 The second stage of cool The second stage of cool The second stage of cool & second stage of heat
S1/S2 Remote Sensor Remote Sensor Remote Sensor

Wiring Diagrams

Wiring Tips

C Terminal
The C (common wire) terminal does not have to be connected when the thermostat is powered by batteries.
Wire Specifications
Use shielded or non-shielded 18-22 gauge thermostat wire.

Installation Tip: Do not overtighten terminal block screws, as this can damage the terminal block. A damaged terminal block can keep the thermostat from fitting on the sub-base correctly or cause system operation issues. Max Torque = 6in-lbs.

  1. Power supply
  2. Factory-installed jumper. Remove only when installing on 2 transformer systems.
  3. Use either O or B terminals for the changeover valve.
  4. Optional 24 VAC common connection when the thermostat is used in battery power mode.

Note: This thermostat is hardwire powered when the 24V transformer is connected to the Common and RC terminals of the thermostat.

Note:
In many systems with no emergency heat relay a jumper can be installed between W/E and W2.
Note: This thermostat is hardwire powered when the 24V transformer is connected to the Common and RC terminals of the thermostat.

Note: In many systems with no emergency heat relay a jumper can be used between E and W2.

Features

Temporary and Permanent Hold Feature

When cool or heat is turned on, the thermostat will display HOLD and RUN SCHED on the left of your screen when you press the  button.
Temporary Hold: At this time if you do nothing, the temperature will remain at this setpoint temporarily for 4 hours.
Permanent Hold: If you press the HOLD key on the left of your screen, you will see HOLD appear below the setpoint temperature in the display. The thermostat will now permanently stay at this setpoint and can be adjusted using the keys.
To Return to Running Schedule: Press the RUN SCHED button on the left of your screen to exit either temporary or permanent hold.

Filter Change Reminder

If your installing contractor has configured the thermostat to remind you when the air filter needs to be changed, you will see FILT in the display when your air filter needs to be changed.
Resetting the filter change reminder: When the FILT reminder is displayed, you should change your air filter and reset the reminder by holding down the second button from the top left side of the thermostat for 3 seconds.

Tech Settings

Technician Setup Menu

This thermostat has a technician setup menu for easy installer configuration. To set up the thermostat for your particular application:

  1. Press the MENU button.
  2. Press and hold the TECH SET button for 3 seconds. This 3-second delay is designed so that homeowners do not accidentally access the installer settings.
  3. Configure the installer options as desired using the table below.
    Use the keys to change settings and the NEXT or PREV key to move from one step to another.
    Note: Only press the DONE key when you want to exit the Technician Setup options.
  4. Press the DONE key to exit.

Tech Settings          LCD Will Show                 Adjustment Options                Default

Filter Change Reminder

This feature will flash a reminder after the elapsed run time to remind the user to change the filter. A setting of “OFF” will disable this feature. OF

FILTER

You can adjust the filter change reminder from “OFF” to 2000 hours of runtime in 50-hour increments. OFF

Room Temperature Calibration

This feature allows the installer to change the calibration of the room temperature display. For example, if the thermostat reads 70˚ and you would like it to read 72˚ then select +2. 0

CALIBRATE

You can adjust the room temperature display to read up to 4˚above or below the factory-calibrated reading. 0˚F

 

Cooling Swing

The swing set often called “cycle rate”, “differential” or “anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles. 0.5

COOL SWING

The cooling swing setting is adjustable from 0.2˚ to 2˚. For example, A swing setting of 0.5˚ will turn the

cooling on at approximately 0.5˚ above the setpoint

and turn the cooling off at approximately 0.5˚ below the setpoint.

0.5˚

Swing Setting Tip
The temperature swing, sometimes called differential or cycle rate, can be customized for this individual application. For most applications choose a swing set that is as long as possible without making the occupants uncomfortable.

Tech Settings            LCD Will Show                                     Adjustment Options                Default

 

Heating Swing

The swing set often called “cycle rate”, “differential”, or “anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles. 0.4

HEAT SWING

The heating swing setting is adjustable from 0.2˚ to 2˚. For example, A swing setting of 0.5˚ will turn the heating on at approximately- ly 0.5˚ below the setpoint and turn the heating off at 0.5˚ above the setpoint.

0.4˚

PTAC Mode

This setting allows the thermostat to operate a PTAC. This will allow for multiple fan speeds selectable in the next two tech settings. OF

PTAC MODE

Use the and buttons to select ON/OFF. ON

PTAC Fan

Speeds

(Only displayed if PTAC mode is ON)

This setting allows you to choose the number of fan speeds the thermostat will control.

G = Low-Speed Fan

B/O = Medium Speed Fan Y2 = High Speed Fan

2

FAN SPEEDS

Use the and buttons to select, 2 or 3.

1. Speeds: ON, Auto

2. Speeds: Low, High, Auto

3. Speeds: Low, Med, High, Auto

2

PTAC Medium This setting will select the terminal for medium fan speed operations. The selected terminal cannot be used for reversing valve operations when the heat pump is enabled. 0

MED FAN TERM

Use the buttons to select O/B terminals.

0

Fan Speed
Terminal
(Only displayed
if PTAC mode is
ON and PTAC fan
speeds is set to 3)

 

Heat Pump

When turned on the thermostat will operate a heat pump. EM. Heat will show as an option in the system switch tech setting.

Use the and button to adjust.

OF

HEAT PUMP

OFF configures the thermostat for conventional systems.

ON configures the thermostat for heat pump systems.

OFF

Swing Setting Tip
The second stage will turn on at 2x the swing set. The second stage will turn off when 1x the swing is reached. For example, if the swing setting is .5degrees for heating and the thermostat is set at 70˚F, the first stage will turn on at approximately 69.5˚F. The second stage will turn on at 69˚F. The second stage will turn off at 69.5˚F and the first will turn off at 70.5˚F. If the third stage is used, it will turn on at 68.5˚F and turn off at approximately 69˚F.

 

System Stages

This setting allows you to select the number of heat and cool stages. 2H2C

 

SET STAGES

Use the    and      buttons to select 1H/1C, 2H/1C, 2H/2C, 3H/1C, 3H/2C, 4H/2C.

 

Note: Heat and cool choices are limited based on conventional, heat pump, or PTAC system configuration.

2H

 

System Set

You can configure the system switch for the particular application. Heat – Off – Cool, Heat – Off, Cool – Off, Heat – Off – Cool – Auto.

Note: Emergency Heat is available in heat pump mode only.

 

 

SYSTEM SET

 

AutoOff Em.Heat

Cool

Use the     or      buttons until the desired application is flashing. AUTO = (Auto Changeover) Heat
Off
Cool
Dual Fuel Auxiliary For Heat Pump

(Only displayed if heat pump is set to ON)

This setting allows the system to run Gas, Oil, Propane or any

other types of auxiliary heat. The thermostat will default to electric auxiliary heat in heat pump applications.

OF

DUAL FUEL

Use the and but- tons to select ON/OFF.

OFF

Electric or Gas Fan Operation

 

(Only displayed if heat pump is set to ON)

Select GAS to have the system control the fan during a call for heat, select Electric to have the thermostat control the fan during a call for heat.

Note: If heat pump is set to “ON” this step will not show, and will default to ELECTRIC.

GAS

 

 

 

 

FAN SET

Use and buttons to change the setting.

GAS

Satisfy Setpoint Staging

(Only displayed if there are more than one stage of

heat or cool)

This feature allows the thermostat to keep multiple stages of heat or cool energized until the setpoint is satisfied. OF

SS STAGING

Use the    or buttons to turn on of off.

OFF

Staging Delay

(Only displayed if there are more than one stage of

heat or cool)

This feature allows a delay to occur if an additional stage is needed. This allows the previous stage extra time to satisfy the setpoint.

Note: Will not show if using an outdoor sensor with balance point temperature.

OF

STAGING DELAY

Use the    or      key to select OFF, 5, 10, 15, 30, 45,

60, or 90 minutes.

OFF

Minimum Compressor On Time

This feature allows the installer to select the minimum run time for the compressor. For

example, a setting of 4 will force the compressor to run for at least 4 minutes every time the compressor turns on, regardless of the room temperature.

OF

MIN COMP ON

You can set the minimum compressor run time to “OFF”, “3”, “4”, or “5” minutes.

If 3, 4 or 5 is selected, the compressor will run for at least the selected time before turning off. Use the

and buttons to change the setting.

OFF

Compressor Short Cycle Delay

The compressor short cycle delay protects the compressor from “short cycling”. This feature will not altlow the compressor to be turned on for 5 minutes after it was last turned off.

 

 

 

 

 

COMP DELAY

Selecting “ON” will not allow the compressor to be turned on for 5 minutes after the last time the compressor was on. Select “OFF” to remove this delay. Use the and buttons to change the setting.

ON

 

Cooling Fan Delay

The cooling fan delay setting will delay the fan from coming on in cool mode and keep it running after the compressor shuts off for a short time to save energy in some systems. OF

COOL FAN DL

You can set the cooling fan delay to OFF, 10, 30, 60 or 90

seconds. If 10, 30, 60, or 90 is selected the fan will not

turn on for that many seconds when there is a call for cool and will run for that many seconds after satisfying a call for cool.

OFF

Program Options

You can configure this thermostat to have 7-Day, 5+1+1 programming or nonprogrammable. 5d

PROG

Use the    and      key to select 7d for 7 Day, 5d

for 5+1+1, or 0d for non programmable.

5d

 

Pro Recovery

This feature will start heating and cooling early to bring the building temperature to its programmed setpoint by the beginning of the WAKE, RETURN and OCCUPIED

time periods.

 

 

 

 

PRO RECOVERY

Use the or key to select on or off.

ON

Heat Setpoint Limit This feature allows you to set a maximum heating setpoint limit. The setpoint temperature cannot be raised above this value. HE

HEAT LIMIT

Use the    or      key to select the maximum heat setpoint and the minimum cooling setpoint. 90˚F
Cool Setpoint Limit This feature allows you to set a minimum cooling setpoint limit. The setpoint temperature cannot be lowered below this value. CO

COOL LIMIT

Use the or key to select the minimum cooling setpoint. 44˚F

˚F or ˚C

This feature allows you to display temperatures in either Fahrenheit or Celsius. oF

F OR C SET

˚F for Fahrenheit

˚C for Celsius

˚F

12 or 24 Hour Clock

You can select either a 12 or 24 hour clock setting. 12

CLOCK SET

Use the or key to select 12 or 24-hour clock. 12H

 

 

 

Display Light

The display light can be configured to stay on all the time or turn on when any key is pressed. There are LOW and

HIGH selections for continuous ON selection.

NOTE: The thermostat will need to be hardwired in order for the LOW and HIGH display light functions to work properly. “ALWAYS ON LIT” will alternate in the text field with “HARDWIRE ONLY” when HIGH is selected. These prompts will alternate every three seconds.

 

If the thermostat is hardwired this feature will default to LOW.

dL

ALWAYS ON LIT

 

 

 

 

 

 

dL

HARDWIRE ONLY

Use the buttons to select OFF, LOW, or HIGH.

OFF configures the display light to come on when the light key or any button is pressed.

LOW configures the display light to stay on at a low intensity constantly. When a button is pressed, the display light will transition to high intensity.

HIGH configures the display light to remain on at high intensity all the time.

OFF

If Battery

Powered

 

 

 

 

 

 

LOW

If Hardwired

Contractor Call Number Note
If the contractor call number is selected ON, the phone number entered will show in the display if there has been a continuous call for heating or cooling for 24 hours or if the light button is held down for 3 seconds. To remove the phone number from the display, hold the light button down for 3 seconds.

 

 

Contractor Call Number

This feature allows you to put your phone number in the display. You can choose ON or OFF.

Notes:

If the contractor call number is selected ON, the phone number entered will show in the display if there has been a continuous call for heating or cooling for 24 hours or if the light button is held down for 3 seconds. To remove the phone number from the display, hold the light button down for 3 seconds.

OF

 

PHONE NUMBER

If selected ON, you will see the input screen after pressing NEXT STEP. Use the

or button to select the desired number and the FAN or SYSTEM key to move from one character to another. See note below for operation.

 

OFF

Remote Sensor Operation

(Only displayed if a sensor is connected

to S1 and S2 terminals)

You can configure the thermostat for one of three remote sensor applications: 0 No Sensor, 1

Indoor, 2 Outdoor, 3 Floor.

0 Use the left and right arrows to select one of three options. View the S1/ S2 terminal chart on next page for an explanation of these options.

0

REMOTE MODE

Local Temp Sensor

(Only displayed if remote sensor setting is set to 1)

You can disable the sensor on the T855SH thermostat. At least one R251S indoor remote sensor must be connected to disable the

local T855S sensor. Note: Will only show if the remote sensor is set to 1.

 

 

 

 

 

 

LOCAL TEMP

ON enables local T855SH sensor. OFF disables local T855SH sensor.

ON

Number Enables the use of up to sixteen indoor sensors R251S. Note: Will only show Remote Sensor is set to 1 and Local Temp Sensor is

set to on.

1

NUMBER REMOTE

You can use 1, 4, 9, or 16 indoor sensors. Refer to the R251S Install Manual for de- tailed connection information

1

of Indoor
Remotes
(Only displayed
if remote sensor
setting is set to 1)
Dual Fuel Balance Point

(Only displayed if remote sensor setting is set to 2 and Dual Fuel AUX = On)

An outdoor temperature above balance point will cause the thermostat to energize the Y terminal(s) only in calls for heat. An outdoor temperature below balance point will cause the thermostat to energize the W2 terminal only in calls for heat. OF

BALANCE POINT

Use the    and     buttons to select OFF, 10, 15, 20, 25,

30, 35, 40, 45, 50 degrees.

OFF

S1 / S2 Terminal

Options Mode Description Requires
1 Indoor The local and remote temperatures are averaged. R251S
2 Outdoor The outdoor temperature is flashed in the clock. R250S
3 Floor The floor temperature is shown in tech. R250S

Tech Settings                   LCD Will Show                          Adjustment Options                Default

Balance Point Run Time

(Only displayed if remote sensor setting is set

to 2)

Balance point run time will allow the W2 auxiliary terminal to ener- gize even if outdoor temperature is above selected balance point temperature. If enabled, auxiliary will energize for the current cycle after the balance point run time has expired.

Note: Only shows if Balance Point is set to an outdoor temperature.

OF

 

BP RUN TIME

Off, 15, 30, 45, 60, 75, 90

 

OFF

Floor Temperature

(Only displayed if remote sensor

the setting is set to 3)

The temperature of the floor sensor will be displayed.

 

Note: Only shows when REOP is set to 3.

Use and buttons to adjust.

76

FLOOR TEMP

N/A

N/A

Floor High Limit

(Only displayed if remote sensor setting is set

to 3)

This setting allows you to set a maximum floor temperature

limit for heat. Heat will be locked out when the floor temperature is above this value. Note: Only shows when REOP is set to 3.

86

HIGH LIMIT

Use the or buttons to select the High Limit for the floor sensor.35 – 120

86

Floor Low Limit

(Only displayed if remote sensor setting is set to 3)

This setting allows you to set a minimum floor temperature

limit for heat. Heat will turn on automatically when the floor temperature is below this value. Note: Only shows when REOP is set to 3.

50 Use the or keys to select the Low Limit for the floor sensor.

35 – 120

50

LOW LIMIT

Programming

Set Time

  1. With the system switch set to OFF, press the MENU button
  2. Press SET TIME
  3. The day of the week will be flashing. Use the key to select the current day of the week.
  4. Press NEXT STEP
  5. The current hour is flashing. Use thekey to select the current hour. When using 12-hour time, make sure the correct a.m. or p.m. choice is selected.
  6. Press NEXT STEP
  7. Minutes are now flashing. Use thekey to select current minutes.
  8. Press DONE when completed.

Programming
All of our programmable thermostats are shipped with an energy-saving pre-program. You can customize this default program by following the steps on the next page. There are four time periods for each program (WAKE, LEAVE, RETURN, SLEEP).
A Note About Auto Changeover:
In Auto you have the ability to switch between Auto Heat or Auto Cool by pressing the system key. This can be done once the current mode has reached its set point. For example: if in Auto Heat, the heat setpoint must be satisfied before the thermostat will allow you to switch to Auto Cool.
You can switch out of Auto by holding down the system key. To get back into Auto, you must toggle the system key to Auto.

All of our programmable thermostats are shipped with an energy saving pre-program. You can customize this default program by following the steps on page 16. There are four time periods for each program (WAKE, LEAVE, RETURN, SLEEP).

Specifications

  • The display range of temperature … 41˚F to 95˚F (5˚C to 35˚C)
  • The control range of temperature… 44˚F to 90˚F (7˚C to 32˚C)
  • Load Rating……………………………………….. 1 amp per terminal, 1.5 amp maximum all terminals combined
  • Swing (cycle rate or differential) …… The heating is adjustable from 0.2˚ to 2.0˚
    Cooling is adjustable from 0.2˚ to 2.0˚
  • Power source …………………………………….18 to 30 VAC, NEC Class II, 50/60 Hz for hardwire
    Battery power from 2 AA Alkaline batteries
  • Operating ambient …………………………. 32˚F to +105˚F (0˚C to +41˚C)
  • Operating humidity ………………………… 90% non-condensing maximum
  • Dimensions of thermostat …………….. 4.7” W x 4.3” H x 0.9” D

REFERENCE:

Download Manual:

Pro1 T755s Non-Programable Thermostats Installation Manual

Other Manual:

Pro1 T755s Non-Programable Thermosts Operation Manual

Pro1 T755s Non-Programable Thermostats Installation Manual

wpx_thermostats

Recent Posts

Johnson Controls T7000e LCD Digital Thermostat Installation Guide

Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide

1 year ago

Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’S GUIDE

Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE

1 year ago

Hetta HS01RF WIRELESS THERMOSTAT KIT USER MANUAL

Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…

1 year ago

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat USER MANUAL

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…

1 year ago

Honeywell RLV450 PROGRAMMABLE THERMOSTAT USER GUIDE

Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…

1 year ago

Honeywell RLV431 Programmable Thermostat User Guide

Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…

1 year ago