Description | |
Gas or Oil Heat | Yes |
Electric Furnace | Yes |
Heat Pump (No Aux. or Emergency Heat) | Yes |
Heat Pump (With Aux. or Emergency Heat) | Yes |
Multi-Stage Systems | Yes |
Heat Only Systems | Yes |
Heat Only Systems – Floor or Wall Furnace | Yes |
Cool Only Systems | Yes |
Millivolt Conventional Systems | Yes |
Two Transformer Systems | No |
A trained, experienced technician must install this product. Carefully read these instructions. You could damage this product or cause a hazardous condition if you fail to follow these instructions.
Wall Locations
The thermostat should be installed approximately 4 to 5 feet above the floor. Select an area with average temperature and good air circulation.
Installation Tip
Pick an installation location that is easy for the user to access. The temperature of the location should be representative of the building
Do not install thermostats in locations:
Installation Tip:
Electrical Hazard
Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.
Mercury Notice
All of our products are mercury-free. However, if the product you are replacing contains mercury, dispose of it properly. Your local waste management authority can give you instructions on recycling and proper disposal.
For vertical mount put one screw on the top and one screw on the bottom. For horizontal mount put one screw on the left and one screw on the right.
Important
The low battery indicator is displayed when the AA battery power is low. If the user fails to replace the battery within 21 days, the screen will only show the low battery indicator but maintain all functionality. If the user fails to replace the batteries after an additional 21 days (days 22-42 since the first “low battery” display) the setpoints will change to 55˚F (Heating) and 85˚F (Cooling). If the user adjusts the setpoint away from either of these, it will hold for 4 hours and then return to either 55˚F or 85˚F. After day 63 the batteries must be replaced immediately to avoid freezing or overheating because the thermostat will shut the unit off until the batteries are changed.
Caution: Electrical Hazard Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.
Warning: All components of the control system and the thermostat installation must conform to Class II circuits per the NEC Code.
Wiring
Installation Tip
Do not overtighten terminal block screws, as this can damage the terminal block. A damaged terminal block can keep the thermostat from fitting on the sub-base correctly or cause system operation issues. Max Torque = 6in-lbs.
R | Heat Pump System 1 HEAT 1 COOL / 2 HEAT 1 COOL
Transformer Power | Conventional System 1 HEAT 1 COOL / 2 HEAT 1 COOL
Transformer Power |
C | Transformer Common | Transformer Common |
B | Changeover Valve Energized in HEAT | Energized in HEAT |
O | Changeover Valve Energized in COOL | Energized in COOL |
G | Fan Relay | Fan Relay |
W/E | First Stage of Emergency HEAT | First Stage of HEAT |
W2 | Second Stage of HEAT/ EMERGENCY HEAT | Second Stage of HEAT |
Y | First Stage of HEAT and COOL | First Stage of COOL |
Conventional System
1 HEAT 1 COOL / 2 HEAT 1 COOL
Technician Setup Menu
This thermostat has a technician setup menu for easy installer configuration. To set up the thermostat for your particular application:
Filter Change Reminder | This feature will flash “FILT” in the display after the elapsed run time to remind the user to change the filter. A setting of “OFF” will disable this feature. | 100 SE Next Step F1 Prev Step | You can adjust the filter change reminder from OFF to 2000 hours of runtime in 50 hour increments.Tap the second button from the top left side of the thermostat to display the current filter elapsed runtime. | 0FF |
Room Temperature Calibration | This feature allows the installer to change the calibration of the room temperature display. For example, if the thermostat reads 70˚ degrees and you would like it to read 72˚ then select +2. | CAL Next Step 0 Prev Step | You can adjust the room temperature display to read 4˚above or below the factory calibrated reading. | 0 |
Compressor Short Cycle Delay | The compressor short cycle delay protects the compressor from short cycling. This feature will not allow the compressor to be turned on for 5 minutes after it was last turned off. | Cd Next Step Prev Step | Selecting “ON” will not allow the compressor to be turned on for 5 minutes after the last time the compressor was switched off. Select “OFF” to remove this delay. | 0N |
Cooling Swing | The swing setting often called “cycle rate”, “differential” or “ anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles. |
Next Step
Prev Step | The cooling swing setting is adjustable from 0.2˚ to 2˚. For example: A swing setting of 0.5˚ will turn the cooling on at approximately 0.5˚ above the setpoint and turn the cooling off at approximately 0.5˚ below the setpoint. | 0.8 | ||
Heating Swing | The swing setting often called “cycle rate”, “differential” or “anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles. | dFHE Next Step
Prev Step
HE L Next Step
Prev Step
CO L Next Step
Prev Step | The heating swing setting is adjustable from 0.2˚ to 2˚. For example: A swing setting of 0.5˚ will turn the heating on at approximately 0.5˚ below the setpoint and turn the heating off at approximately 0.5˚ above the setpoint. | 0.8 | ||
Heating Setpoint Limit | This feature allows you to set a maximum heat setpoint value. The setpoint temperature cannot be raised above this value. | Use the and key to select the maximum heat setpoint. | 90 | |||
Cooling Setpoint Limit | This feature allows you to set a minimum cool setpoint value. The setpoint temperature cannot be lowered below this value. | Use the and key to select the minimum cool setpoint. | 44 | |||
F or C | Select F for Fahenheit temperature read out or select C for Celsius read out. | Next Step FC Prev SFtep | F for Fahrenheit C for Celsius | F | ||
12 or 24 Hour Clock | You can select either a 12 or 24 hour clock setting. |
Next Step
Prev Step | Use the and or 24 hour clock. | to select 12 | 12 |
The temperature swing, sometimes called differential or cycle rate, can be customized for this individual application. For most applications choose a swing set that is as long as possible without making the occupants uncomfortable.
2H/1C Heat Pump System – Factory Default Setting
Typical 2H/1C Heat Pump System with separate emergency heat
Conventional System 1H/1C, 2H/1C (Heat pump set to “OFF” in tech settings)
Temporary and Permanent Hold Feature (If using programming)
When cool or heat is turned on, the thermostat will display HOLD and RUN SCHED on the left of your screen when you press the or button.
Temporary Hold: At this time if you do nothing, the temperature will remain at this setpoint temporarily until the next time period.
Permanent Hold: If you press the HOLD key on the left of your screen, you will see HOLD appear below the setpoint temperature in the display. The thermostat will now permanently stay at this setpoint and can be adjusted using the or keys.
To Return to Running Schedule: Press the RUN SCHED button on the left of your screen to exit either temporary or permanent hold.
Filter Change Reminder
If your installing contractor has configured the thermostat to remind you when the air filter needs to be changed, you will see FILT in the display when your air filter needs to be changed.
Resetting the filter change reminder: When the FILT reminder is displayed, you should change your air filter and reset the reminder by holding down the second button from the top left side of the thermostat for 3 seconds.
About The Badge
All of our thermostats use the same universal magnetic badge. Visit the company website to learn more about our free private label program.
Gently slide a screwdriver into the bottom edge of the badge. Gently turn the screwdriver counter clockwise. The badge is held on by a magnet in the well of the battery door. The badge should pry off easily. DO NOT USE FORCE.
Pro Recovery | This feature will start heating and cooling early to bring the building temperature to its programmed setpoint by the begining of the WAKE or RETURN time period. | Next Step Prev Step | Use the and key to turn ON or OFF. | ON |
Program Options | You can configure this thermostat to have 7 Day, 5+1+1 program- ming or non programmable. | Next Step Prev Step | Use the and key to se- lect 7d for 7 Day, 5d for 5+1+1, or 0d for non programmable. | 5d |
Heat Pump | When set to ON this thermostat will operate a heat pump system (default). If set to OFF this thermostat will operate a conventional system, and the next tech step will not appear. | Next Step
| ON – Configured to operate heat pump system. OFF – Configured to operate conventional system See page 6 for terminal designations. | ON |
Prev Step | ||||
Dual Fuel Auxiliary for Heat Pump | For Dual Fuel applications (Gas/ Fossil fuel Auxiliary Heat), turn this setting ON to LOCKOUT the Heat Pump (Y) when Auxiliary Heat (W2) is on. If desired- This can also be used with Electric Auxiliary. | Next Step
| OFF Will allow Y(1st stage of Heat) and W2 (Aux Heat) to run together if called for. ON Will de-energize Y terminal 45 seconds after a call for Auxiliary Heat (W2). | OFF |
Will only appear if Heat pump setting is turned ON. | Prev Step |
Fan Operation | Select GAS for systems that control the fan during a call for heat. Select ELEC to have the thermostat control the fan during a call for heat. | Next Step Prev Step | EL – Electric for thermostat control GS- Gas for system control | EL |
Emergency Heat Stages | This feature controls the number of stages in Emergency Heat mode. It only appears if the Technician Setup Step for HEAT PUMP is ON. | Next Step Prev Step | Use the or key to select 1-stage or 2-stage operation. | 1 |
Satisfy Setpoint | This feature allows the thermostat to keep multiple stages of heat energized until setpoint is satisfied. | Next Step
Prev Step | Use the or key to turn ON or OFF. | OFF |
Staging Delay | This feature allows a delay to occur when a second stage is needed. This allows the previous stage extra time to satisfy the setpoint. | Next Step Prev Step | Use the or key to select OFF, 5, 10, 15, 30, 45, 60, or 90 minutes. | OFF |
Set Time
Programming
All of our programmable thermostats are shipped with an energy-saving pre-program. You can customize this default program by following the steps on page 15. There are four time periods for each program (WAKE, LEAVE, RETURN, SLEEP).
Set Program Schedule 5+1+1 or 7 Day
To customize your program schedule, follow these steps:
Saturday
Repeat steps 4 through 7 for the Saturday WAKE time period, LEAVE time period, RETURN time period, and the Saturday SLEEP time period.
Sunday
Repeat steps 4 through 7 for the Sunday WAKE time period, LEAVE time period, RETURN time period, and the Sunday SLEEP time period.
Set Program Schedule 5+1+1 or 7 Day (Continue… )
If using 7-Day Programming use the previous steps for every individual day. You can also use these time-saving functions. You must be in Set Sched Programming Mode (Press Menu >> Press Set Sched) for the following functions to work:
Download Manual:
Pro1 T725 Non-Programable Thermostats Installation Manual
Other Manual:
Pro1 T725 Non-Programable Thermosts Operation Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…