Description | |
Gas or Oil Heat | Yes |
Electric Furnace | Yes |
Heat Pump (No Aux. or Emergency Heat) | Yes |
Heat Pump (With Aux. or Emergency Heat) | No |
Multi-Stage Systems | No |
Heat Only Systems | Yes |
Heat Only Systems – Floor or Wall Furnace | Yes |
Cool Only Systems | Yes |
Millivolt | Yes |
Power Type
A trained, experienced
the technician must install this product. Carefully read these instructions. You could damage this product or cause a hazardous condition if you fail to follow these instructions
The thermostat should be installed approximately 4 to 5 feet above the floor. Select an area with average temperature and good air circulation.
Pick an installation location that is easy for the user to access. The temperature of the location should be representative of the building.
Do not install thermostats in locations:
Subbase Installation
For vertical mount put one screw on the top and one screw on the bottom. For horizontal mount put one screw on the left and one screw on the right.
Installation Tip:
Electrical Hazard
Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.
Mercury Notice
All of our products are mercury-free. However, if the product you are replacing contains mercury, dispose of it properly. Your local waste management authority can give you instructions on recycling and proper disposal or you can mail the thermostat to the address on the warranty section for proper disposal.
Align the 4 tabs on the subbase with corresponding slots on the back of the thermostat, then push gently until the thermostat snaps in place.
Battery Installation
Battery installation is recommended even if the thermostat is hardwired (C terminal connected). When thermostat is hardwired and batteries are installed, the thermostat will activate a compressor delay of 5 minutes when the thermostat detects a power outage from the hardwired power supply.
Important
High-quality alkaline batteries are recommended. Rechargeable batteries or low-quality batteries do not guarantee a 1-year life span.
Gas or Electric Setup
Gas: For systems that control the fan during a call for heat, put the fan operation switch in the GAS position. Electric: For systems that do not control the fan during a call for heat, put the fan operation switch to the ELECTRIC position.
NOTE: The compressor delay feature is active if these icons are flashing. The compressor will not turn on until the 5-minute delay has elapsed.
Important
The low battery icon is displayed when the AA battery power is low. Whenever the thermostat detects low battery voltage from the AA batteries, the low battery icon will begin flashing on the screen for 21 days (if the batteries are not changed). If the batteries are not changed 22 days after the thermostat detects low battery voltage, the thermostat screen will only show the flashing battery icon until the buttons are pressed. If the batteries are not changed 43 days after the thermostat detects low battery voltage, the thermostat screen will only
show the flashing battery icon until buttons are pressed and the set points will offset to 85°F/29°C in cooling and 55°F/13°C in heating. At this stage, set point changes can be made temporarily but, the set points will change back to defaulted values after a 4-hour period. The thermostat will continue to perform this low battery flashing, temperature offset condition until the internal voltage threshold is reached. When the thermostat’s internal voltage threshold is reached, all relays will be opened and the thermostat will become inoperable until new batteries are installed.
Removing The Private Label Badge
About The Badge
All of our thermostats use the same universal magnetic badge. Visit the company website to learn more about our free private label program.
Caution: Electrical Hazard
Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.
Wiring
Warning
All components of the control system and the thermostat installation must conform to Class II circuits per the NEC Code.
Installation Tip
Do not overtighten terminal block screws, as this can damage the terminal block. A damaged terminal block can keep the thermostat from fitting on the sub-base correctly or cause system operation issues. Max Torque = 6in-lbs.
Terminal Designations
Wiring Tips
RH & RC Terminals
For single transformer systems, leave the jumper wire in place between RH and RC. Remove the jumper wire for the two transformer systems.
Heat Pump Systems
If wiring to a heat pump, use a small piece of wire (not supplied) to connect terminals W and Y
Wiring Tips
RH & RC Terminals For single transformer systems, leave the jumper wire in place between RH and RC. Remove the jumper wire for the two transformer systems.
Heat Pump Systems
If wiring to a heat pump, use a small piece of wire (not supplied) to connect terminals W and Y
To exit Tech Settings, slide the System Switch to a different position or wait approximately 20 seconds.
Swing & Limit Settings
To exit Swing & Limit Settings, slide the System Switch to a different position or wait approximately 20 seconds.
Tech Settings | LCD Will Show | Adjustment Options | Default | |
Room Temperature Calibration | This feature allows the installer to change the calibration of the room temperature display. For example, if the thermostat reads 70 degrees and you would like it to read 72 then select +2. | CA 0 | You can adjust the room temperature display to read 4˚above or below the factory calibrated reading. | O |
Compressor Short Cycle Delay | The compressor short cycle delay prevents the compressor from switching on and off too often. | Cd | Selecting “ON” will not allow the compressor to be turned on for 5 minutes after the last time the compressor was switched off. Select “OFF” to remove this delay. | ON |
F or C | Select F for Fahrenheit temperature read out or select C for Celsius read out. | FC F | F for Fahrenheit C for Celsius | F |
Swing & Limit Settings | LCD Will Show | Adjustment Options | Default | |
Cooling Swing | The swing setting often called “cycle rate”, “differential” or “anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles. | CO
05 | The cooling swing setting is adjustable from 0.2˚ to 2˚. For example: A swing setting of 0.5˚will turn the cooling on at approximately 0.5˚ above the setpoint and turn the cooling off at approximately 0.5˚ below the setpoint. Use the + and – key to select the minimum cool setpoint. | 0.5 |
Cooling Setpoint Limit | This feature allows you to set a minimum cool setpoint value. The setpoint temperature can’t be lowered below this value. |
| 44 | |
Heating Swing | The swing setting often called “cycle rate”, “differential” or “anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles. | HE
04 | The heating swing setting is adjustable from 0.2˚ to 2˚. For example: A swing setting of 0.5˚will turn the heating on at approximately 0.5˚ below the setpoint and turn the heating off at approximately 0.5˚ above the setpoint. | 0.4 |
Heating Setpoint Limit | This feature allows you to set a maximum heat setpoint value. The setpoint temperature can’t be raised above this value. |
| Use the + and – key to select the maximum heat setpoint. | 90 |
Swing Setting Tip
The temperature swing, sometimes called differential or cycle rate, can be customized for this individual application. For most applications choose a swing set that is as wide as possible without making the occupants uncomfortable.
Pro1 Technologies
P.O. Box 3377
Springfield, MO 65808-3377
Toll-Free: 888-776-1427
Web: www.pro1iaq.com
Hours of Operation: M-F 9 AM – 6 PM Eastern
Download Manual:
Pro1 T601-2 Non-Programable Thermosts Installation Manual
Other Manual:
Pro1 T601-2 Programable Thermosts Operation Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…