Thermostat Application Guide
Description | |
Gas or Oil Heat | Yes |
Electric Furnace | Yes |
Heat Pump (No Aux. or Emergency Heat) | Yes |
Heat Pump (With Aux. or Emergency Heat) | No |
Multi-Stage Systems | No |
Heat Only Systems | Yes |
Cool Only Systems | Yes |
Millivolt | Yes |
Power Type
A trained, experienced technician must install this product. Carefully read these instructions. You could damage this product or cause a hazardous condition if you fail to follow these instructions.
Wall Locations
The thermostat should be installed approximately 4 to 5 feet above the floor. Select an area with average temperature and good air circulation.
Pick an installation location that is easy for the user to access. The temperature of the location should be representative of the building.
Subbase Installation
For vertical mount put one screw on the top and one screw on the bottom. For horizontal mount put one screw on the left and one screw on the right.
Do not install the thermostat in locations:
Installation Tip:
Electrical Hazard
Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.
Mercury Notice
All of our products are mercury-free. However, if the product you are replacing contains mercury, dispose of it properly. Your local waste management authority can give you instructions on recycling and proper disposal.
Mount Thermostat
Align the 4 tabs on the subbase with corresponding slots on the back of the thermostat, then push gently until the thermostat snaps in place.
Battery Installation
Important:
High-quality alkaline batteries are recommended. Rechargeable batteries or low-quality batteries do not guarantee a 1-year life span.
Getting to know your thermostat
Removing The Private Label Badge
About The Badge
All of our thermostats use the same universal magnetic badge. Visit the company website to learn more about our free private label program.
Important
The low battery indicator is displayed when the AA battery power is low. If the user fails to replace the battery within 21 days, the screen will only show the low battery indicator but maintain all functionality. If the user fails to replace the batteries after an additional 21 days (days 22-42 since the first “low battery” display) the setpoints will change to 55˚F (Heating) and 85˚F (Cooling). If the user adjusts the setpoint away from either of these, it will hold for 4 hours and then return to either 55˚F or 85˚F. After day 63 the batteries must be replaced immediately to avoid freezing or overheating because the thermostat will shut the unit off until the batteries are changed. Gently slide a screwdriver into the bottom edge of the badge. Gently turn the screwdriver counterclockwise. The badge is held on by a magnet in the well of the battery door. The badge should pry off easily. DO NOT USE FORCE.
Terminal Designations
Caution: Electrical Hazard Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.
Warning: All components of the control system and the thermostat installation must conform to Class II circuits per the NEC Code.
RH & RC Terminals
For single transformer systems, leave the jumper wire in place between RH and RC. Remove the jumper wire for the two transformer systems.
C Terminal
The C (common wire) terminal does not have to be connected when the thermostat is powered by batteries.
Wire Specifications
Use shielded or non-shielded 18-22 gauge thermostat wire.
Installation Tip: Do not overtighten terminal block screws, as this can damage the terminal block. A damaged terminal block can keep the thermostat from fitting on the sub-base correctly or cause system operation issues. Max Torque = 6in-lbs.
Heat Pump Systems
If wiring to a heat pump, use a small piece of wire (not supplied) to connect terminals W and Y.
Filter Change Reminder | This feature will flash “a reminder” in the display after the elapsed run time to remind the user to change the filter. A setting of “OFF” will disable this feature. | SE F1 OFF | You can adjust the filter change reminder from OFF to 2000 hours of runtime in 50 hour increments. | 0FF | |
Room Temperature Calibration | This feature allows the installer to change the calibration of the room temperature display. For example, if the thermostat reads 70˚ degrees and you would like it to read 72˚ then select +2. | 0 | You can adjust the room temperature display to read 4˚above or below the factory calibrated reading. | 0 | |
Minimum Compressor On Time | This feature allows the installer to select the minimum run time for the compressor. For example: a setting of 4 will force the compressor to run for at least 4 minutes every time the compressor turns on, regardless of the room temperature. | A OFF | You can select the minimum compressor run time from “off”, “3”, “4”, or “5” minutes. If 3,4, or 5 is selected, the compressor will run for at least the selected time before turning off. | 0FF | |
Compressor Short Cycle Delay | The compressor short cycle delay protects the compressor from short cycling. This feature will not allow the compressor to be turned on for 5 minutes after it was last turned off. | OF CO
| Selecting “ON” will not allow the compressor to be turned on for 5 minutes after the last time the compressor was switched off. Select “OFF” to remove this delay. | 0N | |
Cooling Swing | The swing setting often called “cycle rate”, “differential” or “ anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles. | 0.5 COOL SWING | The cooling swing setting is adjustable from 0.2˚ to 2˚. For example: A swing setting of 0.5˚ will turn the cooling on at approximately 0.5˚ above the setpoint and turn the cooling off at approximately 0.5˚ below the setpoint. | 0.5 |
Wiring Diagrams
Once a reminder has been turned on and set, the elapsed time can be checked by navigating to it’s Technical Setup step with a press of the SYSTEM BUTTON, the elapsed time will be displayed. It can also be reset at the time by a press and hold of the FAN BUTTON for 3 seconds. Resetting an expired reminder can be done without entering the tech setup, by a press and hold of the FAN BUTTON for 3 seconds.
A Note About Keypad Lockout
The function of activating your lockout choice takes place after you have exited the tech setup to lock or unlock the keypad and hold down the FAN and SYSTEM for 3 seconds.
Download Manual:
Pro1 Technologies T801 Non-Programmable Thermostat Installational Manual
OTHER MANUALS
Pro1 Technologies T801 Non-Programmable Thermostat Operational Manual
Pro1 Technologies T801 Non-Programmable Thermostat Product Specifications Guide
Pro1 Technologies T801 Non-Programmable Thermostat Installation Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…