Pro1 Technologies
P.O. Box 3377
Springfield, MO 65808-3377
Toll Free : 888-776-1427
Web: www.pro1iaq.com
Hours of Operation: M-F 9AM – 6PM Eastern
Thermostat Application Guide
Description | |
Gas or Oil Heat | Yes |
Electric Furnace | Yes |
Heat Pump (No Aux. or Emergency Heat) | Yes |
Heat Pump (With Electric Aux.) | Yes |
Heat Pump (With Gas Aux.) | No |
Multi-Stage Systems | No |
Heat Only Systems – Floor or Wall Furnace | Yes |
Cool Only Systems | Yes |
High and Low Fan Speed | Yes |
Millivolt | No |
Emergency Heat | No |
Conventional Single Stage Furnace | Yes |
Geothermal | Yes |
Power Type
A trained, experienced technician must install this product.
Carefully read these instructions. You could damage this product or cause a hazardous condition if you fail to follow these instructions.
The thermostat should be installed approximately 4 to 5 feet above the floor. Select an area with average temperature and good air circulation.
Do not install thermostat in locations:
Installation Tip
Pick an installation location that is easy for the user to access. The temperature of the location should be representative of the building.
For vertical mount put one screw on the top and one screw on the bottom.
For horizontal mount put one screw on the left and one screw on the right.
Installation Tip: Electrical Hazard
Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.
Mercury Notice All of our products are mercury free. However, if the product you are replacing contains mercury, dispose of it properly. Your local waste management authority can give you instructions on recycling and proper disposal.
Align the 4 tabs on the subbase with corresponding slots on the back of the thermostat, then push gently until the thermostat snaps in place.
Battery Installation
Battery installation is optional if the thermostat is hardwired (R and C terminal connected to 24V power).
Important:
High quality alkaline batteries are recommended. Rechargeable batteries or low quality batteries do not guarantee a 1-year life span.
Important
The low battery indicator is displayed when the AA battery power is low. If the user fails to replace the battery within 21 days, the screen will only show the low battery indicator but maintain all functionality. If the user fails to replace the batteries after an additional 21 days (days 22-42 since first “low battery” display) the setpoints will change to 55˚F (Heating) and 85˚F (Cooling). If the user adjusts the setpoint away from either of these, it will hold for 4 hours then return to either 55˚F or 85˚F. After day 63 the batteries must be replaced immediately to avoid freezing or overheating because the thermostat will shut the unit off until the batteries are changed.
Removing The Private Label Badge
Gently slide a screwdriver into the bottom edge of the badge. Gently turn the screwdriver counter clockwise. The badge is held on by a magnet in the well of the battery door. The badge should pry off easily. DO NOT USE FORCE.
About The Badge
All of our thermostats use the same universal magnetic badge. Visit the company website to learn more about our free private label program.
Base Module – PTAC Installation
Range between the T631W-2 and the base module is up to 100 feet with no obstructions and up to 50 feet through standard building materials. To optimize the range try placing the base module with no metal between it and the thermostat.
The base module is designed to be mounted behind the front grille of a packaged terminal air conditioner (PTAC). Refer to the PTAC manufacturer’s manual for instruction to remove the front grille. Check clearance to ensure the fit of front grille after base module installation. See below for a few location recommendations.
When Working With A Vertical Unit
When Working With A Metal Sleeve Cabinet, Room Cabinet, or PTAC Cover
Caution: Electrical Hazard
Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.
Warning: All components of the control system and the thermostat installation must conform to Class II circuits per the NEC Code.
C Terminal
The C (common wire) terminal does not have to be connected when the thermostat is powered by batteries.
Wire Specifications
Use shielded or non-shielded 18-22 gauge thermostat wire.
Note: Most PTAC systems support two speed fan operation. In a single speed fan PTAC system or conventional single speed fan system, a jumper should be installed between GL and GH on the thermostat.
Typical 1H/1C System: 2 Speed Fan
Typical 1H/1C System: 1 Speed Fan
Typical 1H/1C Heat Pump System: 2 Speed Fan
Typical 2H/1C Heat Pump System: 2 Speed Fan
Wiring Note: The base module is packaged with labeled thermostat wire. Wire appropriately into the PTAC board terminals.
Note: The thermostat and Base Module come factory linked (communicating) out of the box. However, if the link is lost, use the process on page 14 to re-link the devices.
Note:
The base module may be mounted using adhesive tape, such as double-sided tape or hook and loop strips. The base module must be hardwired (C & R terminals connected to 24V power). Use sec-ondary source of securement to prevent module from dropping into the condenser drain pan.
Connecting to a PTAC:
When connecting the Base Module to a PTAC, refer to the PTAC manufacturer instructions to enable remote thermostat operation.
Wiring
Installation Tip
Do not overtighten terminal block screws, as this can damage the terminal block. A damaged terminal block can keep the thermostat from fitting on the subbase correctly or cause system operation issues. Max Torque = 6in-lbs.
Terminal | 1 Heat 1 Cool Conventional System | 1 Heat 1 Cool Heat Pump System | 2 Heat 1 Cool Heat Pump System |
R | Transformer power (cooling) | Transformer power (cooling) | Transformer power (cooling) |
C | Transformer common | Transformer common | Transformer common |
B/O | Energized in heating | Heat pump changeover valve energized in heating | Heat pump changeover valve energized in heating |
B/O | Energized in cooling | Heat pump changeover valve energized in cooling | Heat pump changeover valve energized in cooling |
GL | Fan Relay, Low | Fan Relay, Low | Fan Relay, Low |
GH | Fan Relay, High | Fan Relay, High | Fan Relay, High |
W | First stage of heat | N/A | Second stage of heat |
Y | First stage of cool | First stage of heat & cool | First stage of heat & cool |
This thermostat is shipped from the factory to operate a conventional heating and cooling system. This thermostat will also operate a heat pump system. See the “heat pump” configuration step on page 12 of this manual to configure the thermostat for heat pump applications.
Electric: The thermostat operation jumper pin should be put in the ELEC position. This setting allows the thermostat to operate the fan during a call for heat. Most PTAC systems will require ELEC Fan Operation Setup.
Gas: For systems that control the fan during a call for heat, put the jumper pin into the GAS position.
Fahrenheit/Celsius Display
Select F or C with the jumper pin to select desired display.
Compressor Short Cycle Delay
The compressor short cycle delay protects the compressor from short cycling. This feature will not allow the compressor to be turned on for 5 minutes after it was last turned off.
Using the jumper on the back of the thermostat, selecting ON will not allow the compressor to be turned on for 5 minutes after the last time the compressor was on. Selecting OFF will remove this delay.
Important The RESET button must be pressed after changing any switch or jumper pin setting. Batteries must be installed for this operation.
Tech Setup Steps | LCD Will Show | Adjustment Options | Default | |
Room Temperature Calibration | This feature allows the installer to change the calibration of the room temperature display. For example, if the thermostat reads 70˚ and you would like it to read 72˚ then select +2. | CA 0 | You can adjust the room temperature display to read up to 4˚above or below the factory calibrated reading. | 0˚F |
Change Over Valve Selection | Select 0 for a changeover valve that energizes in cooling. Select b for a change over valve that energizes in heating. | C0 0 | 0 for cooling changeover valve. b for heating changeover valve. | 0 |
Heat Pump | When turned on the thermostat will operate a heat pump. Y will be the first stage of heat & cool, W will be the second stage of heat. | HU 0F | OFF configures the thermostat for non heat pump systems. ON configures the thermostat for heat pump systems. | OFF |
Heating Temperature Setpoint Limit | This feature allows you to set a maximum heat setpoint value. The setpoint temperature cannot be raised above this value. | HE 90 | 45.0˚ – 90.0˚ F 7.0˚ – 32.0˚ C | 90˚F |
Cooling Temperature Setpoint Limit | This feature allows you to set a minimum cool setpoint valve. The setpoint temperature cannot be lowered below this value. | CL 45 | 45.0˚ – 90.0˚ F 7.0˚ – 32.0˚ C | 45˚F |
Link Establish | This step is used to connect T631W-2 to Base Module. Refer to page 14 for connection instructions. | LE | NA | NA |
Swing Settings | LCD Will Show | Adjustment Options | Default | |
Cooling Swing (SYSTEM COOL) | The swing setting, often called “cycle rate”, “differential” or “anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles. | 08 | The cooling swing setting is adjustable from 0.2˚ to 2˚. For example: A swing setting of 0.5˚ will turn the cooling on at approximately 0.5˚ above the setpoint and turn the cooling off at approximately 0.5˚ below the setpoint. | 0.8˚ |
Heating Swing (SYSTEM HEAT) | The swing setting, often called “cycle rate”, “differential or “anticipation” is adjustable. A smaller swing setting will cause more frequent cucles and a larger swing setting will cause fewer cycles. | 08 | The heating swing setting is adjustable from 0.2˚ to 2˚. For example: A swing setting of 0.5˚ will turn the heating on at approimately 0.5˚ below the setpoint and turn the heating off at approximately 0.5˚ above the setpoint. | 0.8˚ |
Swing Setting
The second stage will turn on at 2x the swing setting. The second stage will turn off when 1x the swing is reached. For example, if the swing setting is 0.8˚ for heating and the thermostat is set at 70˚ F, the first stage will turn on at approximately 69.2˚ F. The second stage will turn on at 68.4˚F and the first will turn off at 70.8˚ F
Establishing Communication between T631W-2 & the base module
The thermostat and base module come factory linked out of the box. If however, communication is lost, follow this easy- Two Step process to re-establish the communication link.
Note:
The Blue LED on the base module will be on when power is present. The Blue LED will flash 3 times every time it recieves a signal from T631W-2. When a relay is on the corresponding LED relay indicator will be on.
If the base module does not receive a signal from the T631W-2 for 15 minutes it will turn off all relays until communication is reestablished. The Blue LED on the base module will also turn off to show communication has been lost.
T631W-2 Thermostat
Base Module
Download Manual:
Pro1 Technologies T631W-2 Non-Programmable Wireless PTAC Thermostat Installational Manual
OTHER MANUALS
Pro1 Technologies T631W-2 Non-Programmable Wireless PTAC Thermostat Operational Manual
Pro1 Technologies T631W-2 Non-Programmable Wireless PTAC Thermostat Product Specifications Guide
Pro1 Technologies T631W-2 Non-Programmable Wireless PTAC Thermostat Installational Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…