Pro1 Technologies
P.O. Box 3377
Springfield, MO 65808-3377 Toll-Free: 888-776-1427
Web: www.pro1iaq.com
Hours of Operation: M-F 9 AM – 6 PM Eastern
Thermostat Application Guide
Description | |
Gas or Oil Heat | Yes |
Electric Furnace | Yes |
Heat Pump (No Aux. or Emergency Heat) | Yes |
Heat Pump (With Aux. or Emergency Heat) | Yes |
Multi-Stage Systems | Yes |
Heat Only Systems | Yes |
Heat Only Systems – Floor or Wall Furnace | Yes |
Cool Only Systems | Yes |
Millivolt Conventional Systems | Yes |
Two Transformer Systems | No |
Power Type
A trained, experienced
the technician must install this product. Carefully read these instructions. You could damage this product or cause a hazardous condition if you fail to follow these instructions.
The thermostat should be installed approximately 4 to 5 feet above the floor. Select an area with average temperature and good air circulation.
Pick an installation location that is easy for the user to access. The temperature of the location should be representative of the building.
Subbase Installation
For vertical mount put one screw on the top and one screw on the bottom. For horizontal mount put one screw on the left and one screw on the right.
Do not install thermostats in locations
Electrical Hazard
Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.
Mercury Notice
All of our products are mercury-free. However, if the product you are replacing contains mercury, dispose of it properly. Your local waste management authority can give you instructions on recycling and proper disposal.
Mount Thermostat
Align the 4 tabs on the subbase with corresponding slots on the back of the thermostat, then push gently until the thermostat snaps in place.
Battery Installation
Battery installation is recommended even if the thermostat is hardwired (C terminal connected). When the thermostat is hardwired and batteries are installed, the thermostat will activate a compressor delay of 5 minutes when the thermostat detects a power outage from the hardwired power supply.
Getting to know your thermostat
Important
The low battery icon is displayed when the AA battery power is low. Whenever the thermostat detects low battery voltage from the AA batteries, the low battery icon will begin flashing on the screen for 21 days (if the batteries are not changed). If the batteries are not changed 22 days after the thermostat detects low battery voltage, the thermostat screen will only show the flashing battery icon until the buttons are pressed. If the batteries are not changed 43 days after the thermostat detects low battery voltage, the thermostat screen will only show the flashing battery icon until buttons are pressed and the set points will offset to 85°F/29°C in cooling and 55°F/13°C in heating. At this stage, set point changes can be made temporarily but, the set points will change back to defaulted values after a 4-hour period. The thermostat will continue to perform this low battery flashing, temperature offset condition until the internal voltage threshold is reached. When the thermostat internal voltage threshold is reached, all relays will be opened and the thermostat will become inoperable until new batteries are installed.
Caution: Electrical Hazard Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.
Terminal Designations
R | Transformer Power | Transformer Power |
C | Transformer Common | Transformer Common |
B | Changeover Valve Energized in HEAT | Energized in HEAT |
O | Changeover Valve Energized in COOL | Energized in COOL |
G | Fan Relay | Fan Relay |
W/E | First Stage of Emergency HEAT | First Stage of HEAT |
W2 | Second Stage of HEAT/ EMERGENCY HEAT | Second Stage of HEAT |
Y | First Stage of HEAT and COOL | First Stage of COOL |
This thermostat has a technician setup menu for easy installer configuration. To set up the thermostat for your particular application:
The Technician Setup Menu
Swing Setting Tip
The temperature swing, sometimes called differential or cycle rate, can be customized for this individual application. For most applications choose a swing set that is as long as possible without making the occupants uncomfortable
Room Temperature Calibration | This feature allows the installer to change the calibration of the room temperature display. For example, if the thermostat reads 70˚ degrees and you would like it to read 72˚ then select +2. | CAL 0 | You can adjust the room temperature display to read 4˚above or below the factory calibrated reading. | 0 |
Compressor Short Cycle Delay | The compressor short cycle delay protects the compressor from short cycling. This feature will not allow the compressor to be turned on for 5 minutes after it was last turned off. | Cd | Selecting “ON” will not allow the compressor to be turned on for 5 minutes after the last time the compressor was switched off. Select “OFF” to remove this delay. | 0N |
Swing Setting Tip
The temperature swing, sometimes called differential or cycle rate, can be customized for this individual application. For most applications choose a swing set that is as long as possible without making the occupants uncomfortable.
F or C | Select F for Fahenheit temperature read out or select C for Celsius read out. | FC F | F for Fahrenheit C for Celsius | F |
Dual Fuel | For Dual Fuel applications (Gas/ Fossil fuel Auxiliary Heat), turn this setting ON to LOCKOUT the Heat Pump (Y) when Auxiliary Heat (W2) is on. If desired- This can also be used with Electric Auxiliary. | OFF Will allow Y(1st stage of Heat) and W2 (Aux Heat) to run together if called for. ON Will de-energize Y terminal 45 seconds after a call for Auxiliary Heat (W2). | OFF | |
Auxiliary | ||||
for Heat | ||||
Pump | ||||
Will only | ||||
appear if | ||||
Heat pump | ||||
setting is | ||||
turned ON. | ||||
Cooling Swing | The swing setting often called “cycle rate”, “differential” or “ anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles. | The cooling swing setting is adjustable from 0.2˚ to 2˚. For example: A swing setting of 0.5˚ will turn the cooling on at approximately 0.5˚ above the setpoint and turn the cooling off at approximately 0.5˚ below the setpoint. | 0.8 | |
Heating Swing | The swing setting often called “cycle rate”, “differential” or “anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles. | HE | The heating swing setting is adjustable from 0.2˚ to 2˚. For example: A swing setting of 0.5˚ will turn the heating on at approximately 0.5˚ below the setpoint and turn the heating off at approximately 0.5˚ above the setpoint. | 0.8 |
Cooling Setpoint Limit | This feature allows you to set a minimum cool setpoint value. The setpoint temperature cannot be lowered below this value. | 44 CL | Use the and key to select the minimum cool setpoint. | 44 |
Heating Setpoint Limit | This feature allows you to set a maximum heat setpoint value. The setpoint temperature cannot be raised above this value. | 90 HL | Use the and key to select the maximum heat setpoint. | 90 |
Wiring Diagrams
Temporary and Permanent Hold Feature
Temporary Hold: If you press the
Permanent Hold: If you press the HOLD button on the left of your screen, you will see HOLD appear to the right of the ambient temperature in the display. The thermostat will now permanently stay at this setpoint and can be adjusted using the
To Return to Running Schedule: Press the RUN button on the left of your screen to exit either temporary or permanent hold. (If using programming) Gently slide a screwdriver into the bottom edge of the
badge. Gently turn the screwdriver counterclockwise. The badge is held on by a magnet in the well of the battery door. The badge should pry off easily. DO NOT USE FORCE.
About The Badge
All of our thermostats use the same universal magnetic badge. Visit the company website to learn more about our free private label program.
Morning Recovery | This feature will start heating early to bring the building temperature to its programmed setpoint by the beginning of the WAKE, OCCUPIED time period. | REC | Use the or key to turn on or off. | ON |
Program Options | You can configure this thermostat to have 7 Day or 5+1+1 programming. | 5d Pr | Use the and key to select 7d for 7 Day or 5d for 5+1+1 programmable. | 5d |
Conventional & Heat Pump
The switch converts the thermostat between conventional and heat pump operation. Heat Pump: Configures the thermostat for heat pump operations. Conventional: Configures the thermostat for conventional operations
Set Time
Programming
All of our programmable thermostats are shipped with an energy-saving pre-program. You can customize this default program by following the steps on page 14. Your thermostat can be programmed to have all the weekdays the same, a separate program for Saturday, and a separate program for Sunday. There are four time periods for each program (WAKE, LEAVE, RETURN, SLEEP).
You can use the table below to plan your customized program schedule
Set Program Schedule
To customize your program schedule, follow these steps
Weekday:
Repeat steps 4 thru 7 for the Saturday WAKE time period, LEAVE time period, RETURN time period, and the Saturday SLEEP time period.
Saturday:
Repeat steps 4 thru 7 for the Sunday WAKE time period, LEAVE time period, RETURN time period, and the Sunday SLEEP time period. If using 7-Day Programming use the previous steps for every individual day.
Download Manual:
Pro1 Technologies T625-2 Programmable Thermostat Installational Manual
OTHER MANUALS
Pro1 Technologies T625-2 Programmable Thermostat Operational Manual
Pro1 Technologies T625-2 Programmable Thermostat Product Specification Guide
Pro1 Technologies T625-2 Programmable Thermostat Installational Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…