WARNING
GENERAL VIEW AND KEY FUNCTIONS
EXAMPLE OF INSTALLATION
PRELIMINARY OPERATIONS
WALL BASE AND TERMINALS
Connect the device to the terminals:
FIXING AND REMOVING THE THERMOSTAT
FITTING OR REPLACING BATTERIES
CHANGING FUNCTION MODE
Changing from COMFORT temperature to ECONOMY temperature and vice versa
Press Mode once. The symbol and the set temperature will start flashing; press OK within 5 seconds to confirm.
Changing from NORMAL FUNCTION to OFF
Press Mode twice. The word OFF and the set antifreeze temperature will start flashing; press OK within 5 seconds to confirm.
Changing from WINTER to summer and vice versa
Changing from OFF to NORMAL FUNCTION
Press Mode once to return to the previous function mode
CHANGE T set TEMPERATURE DEFAULT
BATTERIES’ LOW OR FLAT SIGNAL
ABSENCE OF LINE POWER SUPPLY
In case of absence of power supply the thermostat display switches off completely deactivating heat regulation and saving and storing all settings effected, when the power supply resumes, the display switches on again and the device returns to its normal function.
It is preferable that programming is accessed by the installer or expert user since changing some of the default settings could compromise the correct function of the installation
In the program menu you access the various functions impulse pressing the Mode key, these being in sequence:
SETTING OF THE TEMPERATURE SCALE
The thermostat is preset in production for viewing the temperatures in Celsius degrees, it is possible however to change to the Fahrenheit scale or viceversa with the following procedure
ADJUSTMENT OF ROOM TEMPERATURE READING
If for any reason the thermostat is installed in a position for which the measured temperature might be influenced (eg. an external wall which in the winter is on average colder that the rest of the house) it is possible to set an Offset (adjustment reading) of the measured temperature, the adjustment which can be set is from-2 °C to+2 °Cor from -3.6 to+3.6 °F.
BLOCK MAX TEMPERATURE SETTING (winter) and MIN TEMPERATURE (summer)
In particular cases of thermostat installation, eg. In public buildings, hotels etc. it could be useful to limit the temperature set to comfort in order to avoid erroneous settings by nonauthorized personnel.
It is, therefore, possible to limit the maximum temperature settings if the thermostat is in Winter mode (heating) or limit the minimum temperature setting of the thermostat is in Summer mode (cooling). In the default configuration, no block has been set.
Example: block maximum Comfort temperature Winter mode
Example: block minimum Comfort temperature for Summer mode (cooling)
TEMPERATURE REGULATION
The thermostat has been manufactured to work in differential mod (ON/OFF) with thermal differential reading (hysteresis) preset at 0. 5 °C(setting from0,2 °Cto 1,2°C) . The hysteresis reading must be set on the basis of the thermal inertia of the system; a low reading is advisable for systems with radiators (eg, in cast iron) and a high reading for fan coil systems
. As opposed to the differential, the temperature can be adjusted PROPORTIONALLY (PROP) setting cycles from 7 to 20 minutes (default 10 minutes) This system maintains the desired temperature more stable, whilst increasing the user’s comfort sensation and saving on energy consumption
SELECT TEMPERATURE ADJUSTMENT MODES (DIFFERENTIAL ON/OFF or PROPORTIONAL)
This procedure enables the selection of the temperature adjustment modes between the Differential ON:OFF (manufacturer’s default) and Proportional PROP.
SETTING OF THE HYSTERESIS
The hysteresis reading in the ON:OFF adjustment modemust be set on the basis of the thermal inertia of the system; a low reading is advisable for systems with radiators (eg, in cast iron) and a high reading for fan coil systems. The readings which can be set from 0,2 °C to 1,2 °C (0,3 °F to 2,1 °F); the default reading is 0,5 °C (0,9 °F).
DURATION OF THE PROPORTIONAL CYCLE
The duration of the control cycle for the PROPmode can be set from 7 to 20 minutes; a long cycle is advisable for systems with high thermal inertia (cast iron radiators, floor heating systems) and a short cycle for systems with low thermal inertia (fan coil). The default setting is 10minutes.
ADJUST OR EXCLUDE ANTIFREEZE PROTECTION
When the thermostat is OFF, it is programmed to protect the system in case of frost when the temperature goes below +4.0 °C (+39.2 °F); thus setting is adjustable from +4.0 °C to +12.0 °C (+39.2 °F÷+53.6 °F). It is possible to exclude this function. In this case the system will be exposed to eventual damage caused by frost. miss ina ka mbl ly kar ja rahi
RESET
Resetting should be done by the installer or expert user as with this operation all the settings and programming previously defined according to the type of installationwill be lost. Once the reset operation is done, the thermostat restores all the default settings provided by the manufacturer
EVENTUAL FAULTS AND SOLUTIONS
DOWNLOAD MANUALS:
PERRY 1TP TE531B DIGITAL THERMOSTATS USER INSTRUCTIONS
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…