PECO TF115P-003 commercial THERMOSTAT
TF115P-003 RAINTIGHT THERMOSTAT
The PECO® TF115F-003 is a robust commercial thermostat—fully assembled, and ready to use — for plug-in temperature control of ventilation in greenhouses, warehouses, and industrial facilities. The rugged enclosure can be used for cooling or heating in indoor or outdoor applications. Note: For cooling applications, see the Wiring Diagram on page 2. The PECO® TF115F-003 control, which is housed in the raintight gray plastic enclosure, uses a stainless steel coil as a temperature-sensing bulb. The maximum sensing element withstands temperature is 145°F (62°C). Maximum temperature for the plastic enclosure is 140°F (60°C).
INSTALLATION INSTRUCTIONS
Locate the thermostat about four feet (1.2 m) above the floor on a wall in an area with good ventilation and an average temperature, where it will be responsive to changes in room temperature. The unit is to be assembled with cover, gasket, and four (4) screws installed and fully tightened (see Fig. 1). The TF115P-003 enclosure may be mounted onto a wall or panel surface with #8 or #10 screws.
- With the plug-in inserted to the 120 VAC outlet, a heater may be plugged into the series plug (see Fig. 2) to provide temperature-related operation.
- The power cord is attached to internal leads; default wiring is set for heating.
- Adjustable temperature range is 40° to 110° F (4° to 43° C)
- Temperature Dial: One dial division equals 2°F (1.1° C) (See Fig. 1)
- The cord seal must remain tightened around the power cord to maintain a rain-tight seal; if removed, the locking nut must be held stationary while the gland nut is fully tightened (see Fig 1, 2)
CAUTION! USE 120 VAC ONLY
TF115P-003 FRONT PANEL AND SIDE REFERENCE
WARNING
- READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS THERMOSTAT. Failure to observe the safety information and compliance with instructions could result in PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
- Retain these instructions for future reference. To prevent overheating or fire, use this control as an operating or regulating thermostat. ALWAYS USE A BACKUP CONTROL OR ALARM if a control failure could cause the controlled appliance to overheat or could cause a fire.
- Do not install, use or operate if the product appears damaged, the enclosure is cracked or broken, or the sensor has been bent, crimped, or is dirty.
- To avoid potential fire and/or explosion, do not use in potentially flammable or explosive atmospheres.
- IMPORTANT: Do not impact, dent or use the sensor for support. This will cause calibration and/or thermostat failure.
PRODUCT SPECIFICATIONS
VAC | INDUCTIVE | RESISTIVE AMPS | PILOT DUTY |
FLA | LRA | 13 | 125 VA |
120 | 4.4 | 26.4 |
- Temperature Control Range: 40° to 110° F (4° to 43° C)
- Differential: 3° F (1.7°C)
- Maximum Ambient Temperature: 140°F (60°C)
- Dimensions: 2.80”(L) X 2.5” (W) X 7” (H) inches
- Line cord: 6 feet, 7-wire, double insulated, 16 AWG,
- U.L. Listed, Plug: 3-pole male/female,
- 120 VAC plug style, American (grounded)
- Weight: 0.88 lbs
OPERATION AND CHECKOUT
Allow one hour or the necessary amount of time for the thermostat and system to stabilize for
normal operation. This thermostat is factory calibrated and requires no correction on-site.
By default, the TF115P-003 thermostat is wired for heating operation.
To Check Operation:
- Set Temperature Dial to desired temperature setpoint.
- Plug the controlled device (e.g., fan) into the series plug (female side of TF115P plug).
- Plug the TF115P power cord into the wall outlet. Note: The outlet must be 120 VAC.
- To start the operation, rotate Temperature Dial. Wait for the unit to turn on.
Note: For units that are wired for Heating operation (default) rotate the Dial at least five (5) degrees above the current ambient temperature. For units that are rewired During the cooling operation, rotate the Dial at least five (5) degrees below the current ambient temperature. - Return Temperature Dial to the desired temperature setpoint. (The TF115P will automatically control the desired temperature).
WIRING DIAGRAMS
HEATING (DEFAULT ) OPERATION
By default, the TF115P-003 is wired as a heating control (see Fig. 3).
COOLING OPERATION
WARNING: Disconnect power before changing the wiring.
To change the operation from a heating control to a cooling control, proceed with the following steps
- Remove TF115P plug from the outlet to disconnect the power.
- Unscrew four screws and remove the junction box cover (see Fig. 4).
- Disconnect the red and white wires by removing the wire nut.
- Connect the blue and white wires together with the wire nut (see Fig. 5)
- Twist the wire nut on the red wire only.
- Re-install the junction box cover and tighten four screws.
WARNING
TO ENSURE WATER TIGHTNESS, THE GASKET MUST BE RE-INSTALLED UNDER THE JUNCTION BOX COVER.
LIMITED WARRANTY
- WARRANTY COVERAGE. PECO Automation and Controls warrants to the original user of its products that the products will, at the date of initial purchase, meet the applicable specification for such products and will be free from any defects in materials or manufacture under normal use for 18 months after the date of manufacture.
- DISCLAIMER OF WARRANTY OF PRODUCT SUITABILITY. PECO Automation and Controls makes no warranty to the purchaser or any third party that its products are suitable for a particular application or design. Many states and localities have different codes or regulations governing the installation and/or use of PECO Automation and Controls products.
- PECO Automation and Controls cannot guarantee compliance with such regulations; the purchaser is solely responsible for the safe and correct installation and use of the product and for compliance with applicable codes and regulations.
- EXCLUSION OF IMPLIED WARRANTIES. This warranty is the only warranty applicable to this product and excludes all other warranties, including any WARRANTY OF MERCHANTABILITY, any warranty of fitness for a particular purpose, and any implied warranties otherwise arising from the course of dealing or usage of trade, except where the product purchased is subject to consumer product warranty laws, in which case ANY APPLICABLE IMPLIED WARRANTIES ARE LIMITED TO 18 MONTHS, or such shorter period as permitted or required under applicable law. Some states do not allow limitations on how long an implied warranty lasts, so the above limitations may not apply to you.
REMEDIES FOR NONCONFORMITY. If the product purchased does not conform to the applicable warranty, PECO Automation, and Controls will provide, at its option and in accordance with the procedures in the following section, one of the following remedies:(1) repair of the nonconforming product, (2) replacement with a conforming product, (3) refund of the original purchase price. THESE REMEDIES SHALL BE THE EXCLUSIVE AND SOLE REMEDY for any breach of warranty. - DO OBTAIN WARRANTY SERVICE. For any product believed to be defective within the limited warranty period, first, write or call the dealer from whom the product was purchased. The dealer will give additional directions. If unable to resolve satisfactorily, write to PECO Automation and Controls at the address below, giving the dealer’s name, address, date, and number of the dealer’s invoice, and describe the nature of the defect.
- LIMITATION OF LIABILITY. PECO Automation and Controls WILL NOT BE LIABLE FOR ANY INCIDENTAL, SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES resulting from any defect in the product purchased. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from State to State.
Manufactured by PECO, Inc. 11241 SE Highway 212 Clackamas, OR 97015 USA (PECO Automation and Controls is a division of PECO, Inc.)
Note: Even though this thermostat is sealed, water or dust may enter through improperly sealed wiring. The cover must be tightened securely to compress the gasket and provide a watertight seal. Use only the screws provided. Do not over-tighten.© COPYRIGHT 2019 PECO, INC. ALL RIGHTS RESERVED. 2 PECO is a registered trademark of PECO, Inc. All other trademarks, and/or registered trademarks, are the property of their respective owners.