CAUTION
WARNING
VOLTAGE RATING | FAN AND SYSTEM SWITCHES | THERMOSTATIC SWITCHING (Pilot Duty) | |||
INDUCTIVE | RESISTIVE AMPS | PILOT DUTY | |||
FLA | LRA | ||||
24 VAC | NA | NA | NA | 24 VA | 10 VA |
120 VAC | 5.8 | 34.8 | 6.0 | 125 VA | N.A. |
240 VAC | 2.9 | 17.4 | 5.0 | 125 VA | N.A. |
277 VAC | 2.4 | 14.4 | 4.2 | 125 VA | N.A. |
These thermostats are designed to control On-Off, N.O., and N.C. valves, relays, and Erie® three wire floating valves. These units may include a fan switch with one or more fan speed selections.
MODE BUTTON OPERATION
OFF All thermostat outputs are off, and the fan is still operational if connected to a manual fan speed switch.
AUTO The thermostat automatically selects heating or cooling mode depending on the set point and room temperature. The appropriate HEAT or COOL indicator is enabled in addition to AUTO. A 3°F dead band is provided to prevent short cycling between heating and cooling modes. After the change-over, the control points automatically shift so that the heating-off point or the cooling-off point equals the set point temperature.
COOL The thermostat operates as a cooling-only thermostat. The heating outputs are disabled.
HEAT The thermostat operates as a heating-only thermostat. The cooling outputs are disabled. If constructed without a mode button, the thermostat operates in Auto mode, subject to the configuration of the 2/4 pipe jumper and pipe sensor input.
FAN SPEED SWITCH OPERATION
Fan speed is determined by manual selection from fan switch OFF to HIGH, MEDIUM, and/ or LOW. In units with the Cycling Fan Option (demand output), the Fan operation (CYCLING vs. CONTINUOUS) is determined by application connections. In the OFF position, all outputs are off and display blank.
UP/ DOWN ARROW OPERATION
A first touch of either arrow will display the set point (a single set point is employed for both heating and cooling). Continued pressure on either arrow will scroll the set point to new values. After three seconds with no pressure on either arrow, the selected set point becomes effective and the display of the room temperature resumes.
SETBACK OPERATION
Connection of the Setback Input to 24 VAC 1 will force the control into an unoccupied mode (see wiring diagram). Pressing an arrow key or the mode button on the thermostat cover will disable the setback input for one hour.
PIPE SENSOR OPERATION
If cold water is detected, the system will operate in summer mode and the Main output will be cooling. If hot water is detected, the system will operate in winter mode, the Main output will be heated and First Stage Secondary Output will be disabled. In the case of an ambiguous reading, neither hot or cold, the thermostat will initiate a purge cycle. THREE-WIRE FLOATING VALVE OPERATION Open and Close outputs are used to position the valve. Stroke time is factory set at two minutes. Outputs are off after reaching full-on or off position. Valves are periodically reset for accuracy.
OUTSIDE AIR DAMPER OPERATION
This output is ON any time the control is turned ON.
MAIN AND SECONDARY OUTPUT OPERATION | |||
OUTPUT | Three Wire Floating Operation | ON – OFF | |
Off With Demand | On With Demand | ||
MAIN 1 (Terminal 10) | Powers Main Valve Open | Off at Temperature Demand | On at Temperature Demand |
MAIN 2 (Terminal 12) | Powers Main Valve Closed | Cycles On With Demand | Cycles On With Demand |
SECONDARY 1 (Terminal 11) | Powers Secondary Valve Open | Summer: Off With Heat Demand Winter: Disabled | Summer: On With Heat Demand Winter: Disabled |
SECONDARY 2 (Terminal 13) | Powers Secondary Valve Closed | On at Second Stage Heating Demand | On at Second Stage Heating Demand |
Operation is determined by configuration. See Dip Switch Configuration Table.
For more information see: www.pecomanufacturing.com
Example: This Dip Switch Is Configured For On With Demand, °F Display, On-Off Operation, And 90/50 F Setback.
NOTE: Thermostat power must be cycled for changes in dip switch configuration to take effect.
CIRCUIT BOARD JUMPER CONFIGURATION | ||
Jumper Designation | Jumper Installed ON | Jumper Removed OFF |
JP1 | Local Sensing | Remote Sensing |
JP4 | 2 Pipe System* | 4 Pipe System |
Disables the Secondary 1 Output
Power-Up Operating Sequence
For ON-OFF configuration, this thermostat will go directly to normal operation.
For the three-wire floating configuration (TB158), the thermostat will operate as follows:
Item # | Function | Range | Default |
1 | Zone Temp Offset | -5.1F to 5.1F | 0F |
2 | Valve Stroke Time | 30 sec. To 5 min. | 120 sec. |
3 | Fan Delay to OFF | 0 to 10 Minutes | 0 Sec. |
4 | Compressor Minimum Off Time | 30 Sec. To 10 min. | 120 Sec. |
5 | Purge Cycle | 0 = Time Based 1 = Temperature Based | 1 |
Operation is determined by configuration. See Dip Switch Configuration Table. © COPYRIGHT 2005 PECO, INC. ALL RIGHTS RESERVED P/N 68838 3220-1473 Rev
For more information see: www.pecomanufacturing.com
DOWNLOAD MANUALS:
PECO TB158 MICROPROCESSOR THERMOSTAT Installation Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…