The following Service Menus (SM) commonly require configuration. Please verify that these are set for your specifi c application. additional confi guration may be required. refer to Table 2 for all available Service Menus.
Wiring: Terminal designations
Fan Coil (Conventional) Heat Pump
C | 24 VAC, Unswitched side | C | 24 VAC, Unswitched side |
W1 | Stage 1 Heat | B/O | Reversing Valve |
W2 | Stage 2 Heat | AUX | Auxiliary Heat (Stage 3) |
G | FAN | G | FAN |
A | Economizer/Damper/Humidity | A | Economizer/Damper/Humidity |
E | Stage 3 Heat | E | Emergency Heat |
Y1 | Stage 1 Cool | Y1 | Compressor Stage 1/Heat/Cool 1 |
Y2 | Stage 2 Cool (or Dehumidify) | Y2 | Compressor Stage 2/Heat/Cool 2 (or Dehumidify) |
RH | 24 VAC Power for heating, switched side | RH | 24 VAC Power for heating, switched side |
RC | 24 VAC Power for cooling, switched side | RC | 24 VAC Power for cooling, switched side |
SC | Sensor Common | SC | Sensor Common |
S1 | Indoor Remote Sensor | S1 | Indoor Remote Sensor |
S2 | Occupancy Setback Input* | S2 | Occupancy Setback Input |
S3 | Outdoor Remote Sensor | S3 | Outdoor Remote Sensor |
Note: Contact PECO to learn more about Occupancy Setback Input sensor applications.
Table 2. advanced configuraTion: Service Menus
Some Service Menus may not be available, depending on system type (SM 110).
MENU | FEATURE | OPTIONS | STD. DEFAULT | DESCRIPTION / COMMENTS |
100* | Schedule Format | 0-3 | 1 | Select the schedule format on the T8000 Series. (Menu not available on non-programmable thermostats.) 0 = nonprogrammable 1 = programmable 2 = 5-1-1 schedule 3 = 5-2 schedule |
101 | Daylight-Saving Time | 0,1 | 0 | Select daylight-saving time as it follows standard format in U.S.: It begins second Sunday of March at 2:00 AM and ends on the first Sunday of November at 2:00 AM. 0 = Disabled 1 = Enabled (2007 U.S. Format) |
110 | System Type | 1-13 | 1 | Select the appropriate system configuration (determines available Service Menus). 1 = 1 Heat/1 Cool conventional 2 = 1 Heat/1 Cool heat pump 3 = Heat only without fan (2-wire systems) 4 = Heat only with fan 5 = Cool only 6 = 2 Heat/1 Cool heat pump (with auxiliary heat) and Emergency (Em) heat 7 = 2 Heat/2 Cool multistage conventional 8 = 2 Heat/ 1 Cool multistage conventional 9 = 1 Heat/ 2 Cool multistage conventional 10 = 2 Heat/ 2 Cool heat pump (no auxiliary heat) 11= 3 Heat/ 2 Cool heat pump (with auxiliary heat) and Emergency (Em) heat 12 = 3 Heat/ 1 Cool conventional 13= 3 Heat/ 2 Cool conventional |
120 | Fan Control (heating) | 0,1 | 0 | 0 = Fossil Fuel: Gas/Oil/Propane heat (equipment controls heating fan) 1 = Electric Furnace (thermostat controls heating fan) |
130 | Changeover valve (B/O terminal) | 0,1 | 0 | 0 = B/O terminal controls valve in cooling 1 = B/O terminal controls valve in heating |
140 | Auxiliary Heat | 0,1 | 0 | 0 = Electric backup heat 1 = Fossil fuel backup heat |
150 | Backlight | 0,1 | 0 | 0 = Backlight temporarily on 1 = Backlight always on (low intensity, 24V only) |
170 | Remote Sensor | 0-5 | 0 | Select sensor if used. Contact PECO for information on the T8000 Series Indoor Remote Zone Sensor. 0 = No Sensor 1 = Indoor Sensor 2 = Outdoor Sensor display only 3 = Outdoor Sensor display and lockout control 4 = Indoor, Outdoor Sensor display only 5 = Indoor, Outdoor Sensor display and lockout control |
180 | Heat Pump | 0-45°F | 0 | If an outside sensor is used, the compressor will be locked out when the outside air temp is below |
Compressor Lockout | (-18°C – 7°C) | the value selected. | ||
0 = None | ||||
15°F( -9°C); 20°F (-7°C); 25°F ( -4°C); 30°F ( -1°C); 35°F (2°C); 40°F (4°C); 45°F (7°C) | ||||
190 | Heat Pump Auxiliary | 0- 60°F | 0 | If an outside sensor is used, the auxiliary heat will be locked out when the outside air temperature |
Lockout | (-18°C – 15°C) | is above the value selected. | ||
0 = None | ||||
40°F (4°C); 45°F (7°C); 50°F (10°C); 55°F (13°C); 60°F (16°C) | ||||
230 | Furnace Filter | 0; 30; 60; 90; | 0 | Set a filter reminder timer; appears on digital display when timer expires (if programmed). |
Change Reminder | 120; 365 | 0 = Off | ||
10 days; 30 days; 60 days; 90 days; 120 days; 365 days | ||||
240 | Number of Program Periods | 2; 4 events | 4 | 2 = 2 events per day 4 = 4 events per day |
250 | Clock format | 12 or 24 Hours | 12 | 12 = 12-hour clock mode 24 = 24-hour clock mode |
260 | Temperature Format (°F or °C) | 0,1 | 1 | 0 = Celsius 1 = Fahrenheit |
270 | Fan Off Delay Heat | 0-99 Seconds | 0 | Select the amount of time (in seconds) that the fan will run after the thermostat heat outputs are turned off. |
280 | Fan Off Delay Cool | 0-99 Seconds | 0 | Select the amount of time (in seconds) that the fan will run after the thermostat cool outputs are turned off. |
MENU | FEATURE | OPTIONS | STD. DEFAULT | DESCRIPTION / COMMENTS |
290 | Range Low | 50-90 °F or 10-32°C | 50°F (10°C) | Choose the lowest selectable temperature setpoint value. |
300 | Range High | 50-90 °F or 10-32°C | 90°F (32°C) | Choose the highest selectable temperature setpoint value. |
310 | Setback Low | Off; 50-82°F or 11-27°C | 55°F (13°C) | Select the heat setpoint for setback mode. 0 = Off 50-82°F (11-27°C) |
320 | Setback High | Off; 58-90°F or 11-32°C | 90°F (32°C) | Select the cool setpoint for setback mode. 0 = Off 58-90°F (11-32°C) |
330 | Zone Temp Offset | +/-9°F or +/- 4.5°C | 0°F (18 °C) | Adjusts the displayed value; may differ from actual zone temperature. |
340 | Keypad Lockout | 0-3 | 0 | Restricts access to certain features of device; Service Menu still available if enabled. 0 = No key pad lockout (Default) 1 = Disables Schedule and System keys 2 = Disables Schedule, System, and Fan keys 3 = Disables all keys |
341 | Enable Pin Access | 0,1 | 0 | Applies a 3 digit access code to enter Service Menu 342 0 = Disable 1 = Enable |
342 | Set PIN Access Code | 000-999 | 000 | Choose a 3-digit code. |
350 | Fan Mode Enable | 1-3 | 3 | 1 = ON: Fan is turned on regardless of demand. 2 = Auto: Fan is turned on according to heating or cooling demand. 3 = ON or Auto: Allows occupant to select either 1 or 2 above. |
360 | System Mode Enable | 0-3 | 1 | Allows ability to determine which system modes the occupant can select. 0 = OFF, Auto (0 is NOT valid for following configurations: Heat Only; Cool Only.) 1 = OFF, Heat, Cool, Auto 2 = OFF, Heat, Cool 3 = Heat, Cool, Auto |
370 | Economizer/Outside Air Damper | 0-4 | 0 | 0 = Off 1 = Time Based Output 2 = Economizer 3 = Continuous Outside Air Damper 4 = Cycled Outside Air Damper |
380 | Minimum Deadband Adjustment | 3-10°F, 1.5-5°C | 3°F | Select a changeover deadband value to prevent short cycling between heating and cooling modes. The value is adjustable to meet various HVAC system requirements. |
390 | Pre-Occupancy Purge | 0-3 hours | 0 hours | Select to energize fan for selected number of hours (0-3) prior to all occupied events. |
395 | Maximum Override Time Limit | 0=Time until next event; or 1-4 hours | 3 | Restricts the duration that a temporary hold can be set. The temporary hold is limited by the maximum amount of time as defined in this Service Menu. 0 = Remainder of time until the next scheduled event. 1 = 1 Hour 2 = 2 Hours 3 = 3 Hours 4 = 4 Hours |
400 | Cycles Per Hour (CPH) Cooling Stage 1 | 0-6 CPH | 0 CPH | Defines the number of cycles per hour for cooling (Stage 1). Select 0 to enable ON-OFF control for Stage 1 cooling. |
410 | Cycles Per Hour (CPH) Cooling Stage 2 | 0-6 CPH | 0 CPH | Defines the number of cycles per hour for cooling (Stage 2). Select 0 to enable ON-OFF control for Stage 2 cooling. |
420 | Cycles Per Hour (CPH) Heating Stage 1 | 0-12 CPH | 0 CPH | Defines the number of cycles per hour for heating (Stage 1). Select 0 to enable ON-OFF control for Stage 1 heating. |
430 | Cycles Per Hour (CPH) Heating Stage 2 | 0-12 CPH | 0 CPH | Defines the number of cycles per hour for heating (Stage 2). Select 0 to enable ON-OFF control for Stage 2 heating. |
450 | Cycles Per Hour (CPH) Emergency Heating & Stage 3 Heat | 0-12 CPH | 0 CPH | Defines the number of cycles per hour for heating. Select 0 to enable ON-OFF control for Emergency Heating & Stage 3 Heat. |
MENU | FEATURE | OPTIONS | STD.MODEL DEFAULT | DESCRIPTION / COMMENTS |
460 | Heat Recovery Rate | 0-18°F/Hr 0-10°C/Hr | 0°F/Hr | Defines the rate at which the device achieves the heat comfort setpoint. Select 0 to disable ramp recovery. |
470 | Cool Recovery Rate | 0-18°F/Hr 0-10°C/Hr | 0°F/Hr | Defines the rate at which the device achieves the cool comfort setpoint. Select 0 to disable ramp recovery. |
480 | Minimum Off Time | 1-10 minutes | 4 minutes | Sets the minimum off time for both the heat and cool output. |
490 | Humidity Control Enable (Select models only) | 0-3 | 0 | Selects how humidity will be controlled. When dehumidify control is enabled, the Y2 terminal becomes dehumidify. Note: If option 3 is selected, Service Menu 491 becomes available. 0 = Disabled 1 = Dehumidify Control 2 = Humidify Control 3 = Dehumidify and Humidify Control |
491 | Humidity Deadband | 10-50 | 30% relative humidity (RH) | Selects the deadband in %RH between the humidify and dehumidify setpoints. Note: If option 3 is selected in Service Menu 490, Service Menu 491 becomes available. 10; 20; 30; 40; 50 |
500 | Programmable/ Intermittent Fan | 0-2 | 0 | 0 = Disable 1 = Programmable Fan: Fan operates continuously in occupied periods or with demand in unoccupied periods. 2 = Intermittent Fan: Fan operates based on the on and off times set in menus 501 and 502. |
501 | Intermittent Fan On Time | 1-60 minutes | 5 minutes | Defines the on time for the Intermittent Fan. |
502 | Intermittent Fan Off Time | 0-60 minutes | 25 minutes | Defines the off time for the Intermittent Fan. Select 0 for continuous fan. |
510 | Power Harvesting Enable (For use on systems in which a Common “C” power wire is unavailable) | 0-3 | 0 | Options 1-3 draw a small amount of current from load wire indicated to supplement battery supply. 0 = No power harvesting is available. Warning: Power Harvesting is intended to be used only as a 1 = Use Y1 as the battery supplement. battery supplement. If enabled, the feature preserves battery 2 = Use W1 as the battery supplement. life. If Power Harvesting is not compatible with your system, 3 = Use both Y1 and W1 as the battery supplement select “0” (default) to disable. If thermostat is powered from AC, select only “0” or off. Consult a technician if you have questions. |
520 | Default Display Icons | 0-4 | 0 | Select icons that will be displayed in the Default Display screen. 0 = Time, Temp, SP 1 = Time, Temp 2 = Time 3 = Temp 4 = None |
530 | Revision | — | — | Displays firmware revision information (for technician); not adjustable. |
540 | Factory Default Reset | 0,1 | 0 | Select 1 (enable) to restore factory default settings for thermostat. Select 0 to disable. 0 = Disable 1 = Enable Note: Press “Done” key to complete process. |
600 | System Test Main Output (Cool) | 0-2 | 0 | Select an option to activate the fan output for 10 minutes; select 0, Done or a different Service Menu to disable. 0 = Disable 1= Cool Stage 1 2 = Cool Stage 2 |
610 | System Test Main Output (Heat) | 0-3 | 0 | Select an option to activate the fan output for 10 minutes; select 0, Done or a different Service Menu to disable. Note: Outputs will be activated based upon the system configuration. 0 = Disable (Default) 1 = Heat Stage 1 2 = Heat Stage 2 3 = Heat Stage 3 |
620 | System Test Fan Output | 0,1 | 0 | Select 0 or 1 to activate the fan output for 10 minutes; select 0, Done or a different Service Menu to disable. 0 = Disable Fan Output 1 = Enable Fan Output Note: Outputs will be activated based upon the system configuration. |
630 | System Test Emergency Output | 0,1 | 0 | Select 0 or 1 to activate the Emergency output for 10 minutes; select 0, Done or a different Service Menu to disable. 0 = Disable Emergency Output 1 = Enable Emergency Output |
640 | System Test Economizer | 0,1 | 0 | Select 1 to activate the Economizer output for 10 minutes; select 0, Done or a different Service Menu to disable. 0 = Disable Economizer Output 1 = Enable Economizer Output |
© COPYRIGHT 2014 PECO ASTRONICS. ALL RIGHTS RESERVED.
Download Manual:
Peco T8532 Programmable Thermostat Quick Installation
Peco T8532 Programmable Thermostat Product Specification Sheet
Peco T8532 Programmable Thermostat Installation Instruction
Peco T8532 Programmable Thermostat Operating Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…