Peco T8532 Programmable Thermostat Quick Installation

Peco T8532 Programmable Thermostat

SeT clocK, Year, Month, day

  1. Press ▲/ ▼ to select 12 or 24 Hr mode, then press Next.
  2. Press ▲/ ▼to select hour, then press Next.
  3. Press ▲/ ▼to select minutes, then press Next.
  4. Press ▲/ ▼ to select current year, then press Next.
  5. Press ▲/ ▼ to select current month, press Next.
  6. Press ▲/ ▼ to select the calendar day number. Press Done to complete operation.
    Note: Select More > Clock, to access after setup.

Access Service Menus

  1. Hold lower right and lower left keys for fi ve seconds.
  2. Press Next or Go Back button to select a Service Menu.
  3. Press ▲/ ▼ to select Menu option.
  4. Press Done when complete.
    Note: Upon completion of installation, remove the plastic insulator tab from the back side of the thermostat.

Configure Service Menus

The following Service Menus (SM) commonly require configuration. Please verify that these are set for your specifi c application. additional confi guration may be required. refer to Table 2 for all available Service Menus.

  • SM 100 = Programmable or nonprogrammable
  • SM 110 = System Type
  • SM 120 = fan control
  • SM 130 = reversing valve
  • SM 240 = number of Program Periods
  • SM 260 = Temperature format (°f or °c)
  • SM 340 = Keypad lockout

Wiring: Terminal designations

  1. Connect wires for the appropriate system type (Table 1).
    WARNING: DISCONNECT POWER BEFORE BEGINNING INSTALLATION.
  2. CAUTION: Use copper wire only. Insulate or wire-nut all unused leads.
  3. Use care to avoid electrostatic discharge to thermostat
  4. CAUTION: Do not connect unused wires together
  5. ALL ELECTRICAL LOADS MUST BE CONNECTED TO TERMINAL C (24 VAC).

Table 1. Terminal block designations

Fan Coil (Conventional)                                    Heat Pump

C 24 VAC, Unswitched side C 24 VAC, Unswitched side
W1 Stage 1 Heat B/O Reversing Valve
W2 Stage 2 Heat AUX Auxiliary Heat (Stage 3)
G FAN G FAN
A Economizer/Damper/Humidity A Economizer/Damper/Humidity
E Stage 3 Heat E Emergency Heat
Y1 Stage 1 Cool Y1 Compressor Stage 1/Heat/Cool 1
Y2 Stage 2 Cool (or Dehumidify) Y2 Compressor Stage 2/Heat/Cool 2

(or Dehumidify)

RH 24 VAC Power for heating, switched side RH 24 VAC Power for heating, switched side
RC 24 VAC Power for cooling, switched side RC 24 VAC Power for cooling, switched side
SC Sensor Common SC Sensor Common
S1 Indoor Remote Sensor S1 Indoor Remote Sensor
S2 Occupancy Setback Input* S2 Occupancy Setback Input
S3 Outdoor Remote Sensor S3 Outdoor Remote Sensor

Note: Contact PECO to learn more about Occupancy Setback Input sensor applications.

Table 2. advanced configuraTion: Service Menus
Some Service Menus may not be available, depending on system type (SM 110).

MENU FEATURE OPTIONS STD. DEFAULT DESCRIPTION / COMMENTS
100* Schedule Format 0-3 1 Select the schedule format on the T8000 Series. (Menu not available on non-programmable thermostats.)

0 =  nonprogrammable

1 =  programmable

2 =  5-1-1 schedule

3 =  5-2 schedule

101 Daylight-Saving Time 0,1 0 Select daylight-saving time as it follows standard format in U.S.: It begins second Sunday of March at 2:00 AM and ends on the first Sunday of November at 2:00 AM.

0 =  Disabled

1 =  Enabled (2007 U.S. Format)

110 System Type 1-13 1 Select the appropriate system configuration (determines available Service Menus). 1 = 1 Heat/1 Cool conventional

2 =  1 Heat/1 Cool heat pump

3 = Heat only without fan (2-wire systems) 4 = Heat only with fan

5 =  Cool only

6 = 2 Heat/1 Cool heat pump (with auxiliary heat) and Emergency (Em) heat 7 = 2 Heat/2 Cool multistage conventional

8 =  2 Heat/ 1 Cool multistage conventional

9 =  1 Heat/ 2 Cool multistage conventional

10 = 2 Heat/ 2 Cool heat pump (no auxiliary heat)

11= 3 Heat/ 2 Cool heat pump (with auxiliary heat) and Emergency (Em) heat 12 = 3 Heat/ 1 Cool conventional

13=  3 Heat/ 2 Cool conventional

120 Fan Control (heating) 0,1 0 0 = Fossil Fuel: Gas/Oil/Propane heat (equipment controls heating fan) 1 = Electric Furnace (thermostat controls heating fan)
130 Changeover valve (B/O terminal) 0,1 0 0 = B/O terminal controls valve in cooling 1 =  B/O terminal controls valve in heating
140 Auxiliary Heat 0,1 0 0 =  Electric backup heat

1 =  Fossil fuel backup heat

150 Backlight 0,1 0 0 =  Backlight temporarily on

1 =  Backlight always on (low intensity, 24V only)

170 Remote Sensor 0-5 0 Select sensor if used. Contact PECO for information on the T8000 Series Indoor Remote Zone Sensor.

0 =  No Sensor

1 =  Indoor Sensor

2 =  Outdoor Sensor display only

3 = Outdoor Sensor display and lockout control 4 = Indoor, Outdoor Sensor display only

5 =  Indoor, Outdoor Sensor display and lockout control

180 Heat Pump 0-45°F 0 If an outside sensor is used, the compressor will be locked out when the outside air temp is below
Compressor Lockout (-18°C – 7°C) the value selected.
0 = None
15°F( -9°C); 20°F (-7°C); 25°F ( -4°C); 30°F ( -1°C); 35°F (2°C); 40°F (4°C); 45°F (7°C)
190 Heat Pump Auxiliary 0- 60°F 0 If an outside sensor is used, the auxiliary heat will be locked out when the outside air temperature
Lockout (-18°C – 15°C) is above the value selected.
0 = None
40°F (4°C); 45°F (7°C); 50°F (10°C); 55°F (13°C); 60°F (16°C)
230 Furnace Filter 0; 30; 60; 90; 0 Set a filter reminder timer; appears on digital display when timer expires (if programmed).
Change Reminder 120; 365 0 =  Off
10 days; 30 days; 60 days; 90 days; 120 days; 365 days
240 Number of Program Periods 2; 4 events 4 2 =  2 events per day

4 =  4 events per day

250 Clock format 12 or 24 Hours 12 12 = 12-hour clock mode 24 = 24-hour clock mode
260 Temperature Format (°F or °C) 0,1 1 0 =  Celsius

1 =  Fahrenheit

270 Fan Off Delay Heat 0-99 Seconds 0 Select the amount of time (in seconds) that the fan will run after the thermostat heat outputs are turned off.
280 Fan Off Delay Cool 0-99 Seconds 0 Select the amount of time (in seconds) that the fan will run after the thermostat cool outputs are turned off.
MENU FEATURE OPTIONS STD. DEFAULT DESCRIPTION / COMMENTS
290 Range Low 50-90 °F or

10-32°C

50°F (10°C) Choose the lowest selectable temperature setpoint value.
300 Range High 50-90 °F or

10-32°C

90°F (32°C) Choose the highest selectable temperature setpoint value.
310 Setback Low Off; 50-82°F or 11-27°C 55°F (13°C) Select the heat setpoint for setback mode. 0 = Off

50-82°F (11-27°C)

320 Setback High Off; 58-90°F or 11-32°C 90°F (32°C) Select the cool setpoint for setback mode. 0 = Off

58-90°F (11-32°C)

330 Zone Temp Offset +/-9°F or +/- 4.5°C 0°F (18 °C) Adjusts the displayed value; may differ from actual zone temperature.
340 Keypad Lockout 0-3 0 Restricts access to certain features of device; Service Menu still available if enabled. 0 = No key pad lockout (Default)

1 =  Disables Schedule and System keys

2 = Disables Schedule, System, and Fan keys 3 = Disables all keys

341 Enable Pin Access 0,1 0 Applies a 3 digit access code to enter Service Menu 342 0 =  Disable

1 =               Enable

342 Set PIN Access Code 000-999 000 Choose a 3-digit code.
350 Fan Mode Enable 1-3 3 1 =  ON: Fan is turned on regardless of demand.

2 = Auto: Fan is turned on according to heating or cooling demand. 3 = ON or Auto: Allows occupant to select either 1 or 2 above.

360 System Mode Enable 0-3 1 Allows ability to determine which system modes the occupant can select.

0 = OFF, Auto (0 is NOT valid for following configurations: Heat Only; Cool Only.) 1 = OFF, Heat, Cool, Auto

2 =  OFF, Heat, Cool

3 =  Heat, Cool, Auto

370 Economizer/Outside Air Damper 0-4 0 0 =  Off

1 = Time Based Output 2 = Economizer

3 = Continuous Outside Air Damper 4 = Cycled Outside Air Damper

380 Minimum Deadband Adjustment 3-10°F, 1.5-5°C 3°F Select a changeover deadband value to prevent short cycling between heating and cooling modes. The value is adjustable to meet various HVAC system requirements.
390 Pre-Occupancy Purge 0-3 hours 0 hours Select to energize fan for selected number of hours (0-3) prior to all occupied events.
395 Maximum Override Time Limit 0=Time until next event; or

1-4 hours

3 Restricts the duration that a temporary hold can be set. The temporary hold is limited by the maximum amount of time as defined in this Service Menu.

0 = Remainder of time until the next scheduled event. 1 = 1 Hour

2 =  2 Hours

3 =  3 Hours

4 =  4 Hours

400 Cycles Per Hour (CPH) Cooling Stage 1 0-6 CPH 0 CPH Defines the number of cycles per hour for cooling (Stage 1). Select 0 to enable ON-OFF control for Stage 1 cooling.
410 Cycles Per Hour (CPH) Cooling Stage 2 0-6 CPH 0 CPH Defines the number of cycles per hour for cooling (Stage 2). Select 0 to enable ON-OFF control for Stage 2 cooling.
420 Cycles Per Hour (CPH) Heating Stage 1 0-12 CPH 0 CPH Defines the number of cycles per hour for heating (Stage 1). Select 0 to enable ON-OFF control for Stage 1 heating.
430 Cycles Per Hour (CPH) Heating Stage 2 0-12 CPH 0 CPH Defines the number of cycles per hour for heating (Stage 2). Select 0 to enable ON-OFF control for Stage 2 heating.
450 Cycles Per Hour (CPH) Emergency Heating &

Stage 3 Heat

0-12 CPH 0 CPH Defines the number of cycles per hour for heating. Select 0 to enable ON-OFF control for Emergency Heating & Stage 3 Heat.
MENU FEATURE OPTIONS STD.MODEL DEFAULT DESCRIPTION / COMMENTS
460 Heat Recovery Rate 0-18°F/Hr

0-10°C/Hr

0°F/Hr Defines the rate at which the device achieves the heat comfort setpoint. Select 0 to disable ramp recovery.
470 Cool Recovery Rate 0-18°F/Hr

0-10°C/Hr

0°F/Hr Defines the rate at which the device achieves the cool comfort setpoint. Select 0 to disable ramp recovery.
480 Minimum Off Time 1-10 minutes 4 minutes Sets the minimum off time for both the heat and cool output.
490 Humidity Control Enable

(Select models only)

0-3 0 Selects how humidity will be controlled. When dehumidify control is enabled, the Y2 terminal becomes dehumidify. Note: If option 3 is selected, Service Menu 491 becomes available.

0 =  Disabled

1 = Dehumidify Control 2 = Humidify Control

3 =  Dehumidify and Humidify Control

491 Humidity Deadband 10-50 30% relative humidity (RH) Selects the deadband in %RH between the humidify and dehumidify setpoints. Note: If option 3 is selected in Service Menu 490, Service Menu 491 becomes available.

10; 20; 30; 40; 50

500 Programmable/ Intermittent Fan 0-2 0 0 =  Disable

1 = Programmable Fan: Fan operates continuously in occupied periods or with demand in unoccupied periods.

2 =  Intermittent Fan: Fan operates based on the on and off times set in menus 501 and 502.

501 Intermittent Fan On Time 1-60 minutes 5 minutes Defines the on time for the Intermittent Fan.
502 Intermittent Fan Off Time 0-60 minutes 25 minutes Defines the off time for the Intermittent Fan. Select 0 for continuous fan.
510 Power Harvesting Enable

(For use on systems in which a Common “C” power wire is unavailable)

0-3 0 Options 1-3 draw a small amount of current from load wire indicated to supplement battery supply.

0 = No power harvesting is available.                            Warning: Power Harvesting is intended to be used only as a 1 = Use Y1 as the battery supplement. battery supplement. If enabled, the feature preserves battery 2 = Use W1 as the battery supplement.          life. If Power Harvesting is not compatible with your system,

3 =  Use both Y1 and W1 as the battery supplement select “0” (default) to disable. If thermostat is powered from AC,

select only “0” or off. Consult a technician if you have

questions.

520 Default Display Icons 0-4 0 Select icons that will be displayed in the Default Display screen. 0 = Time, Temp, SP

1 = Time, Temp 2 = Time

3 =  Temp

4 =  None

530 Revision Displays firmware revision information (for technician); not adjustable.
540 Factory Default Reset 0,1 0 Select 1 (enable) to restore factory default settings for thermostat. Select 0 to disable. 0 = Disable

1 =  Enable

Note: Press “Done” key to complete process.

600 System Test Main Output (Cool) 0-2 0 Select an option to activate the fan output for 10 minutes; select 0, Done or a different Service Menu to disable.

0 = Disable

1=      Cool Stage 1

2 =  Cool Stage 2

610 System Test Main Output (Heat) 0-3 0 Select an option to activate the fan output for 10 minutes; select 0, Done or a different Service Menu to disable. Note: Outputs will be activated based upon the system configuration.

0 = Disable (Default) 1 = Heat Stage 1

2 =  Heat Stage 2

3 =  Heat Stage 3

620 System Test Fan Output 0,1 0 Select 0 or 1 to activate the fan output for 10 minutes; select 0, Done or a different Service Menu to disable.

0 =  Disable Fan Output

1 =  Enable Fan Output          Note: Outputs will be activated based upon the system configuration.

630 System Test Emergency Output 0,1 0 Select 0 or 1 to activate the Emergency output for 10 minutes; select 0, Done or a different Service Menu to disable.

0 = Disable Emergency Output 1 =  Enable Emergency Output

640 System Test Economizer 0,1 0 Select 1 to activate the Economizer output for 10 minutes; select 0, Done or a different Service Menu to disable.

0 = Disable Economizer Output 1 =  Enable Economizer Output

© COPYRIGHT 2014 PECO ASTRONICS. ALL RIGHTS RESERVED.

REFERENCE:

Download Manual:

Peco T8532 Programmable Thermostat Quick Installation

OTHER MANUALS:

Peco T8532 Programmable Thermostat Product Specification Sheet

Peco T8532 Programmable Thermostat Installation Instruction

Peco T8532 Programmable Thermostat Operating Manual

Peco T8532 Programmable Thermostat Quick Installation

wpx_thermostats

Recent Posts

Johnson Controls T7000e LCD Digital Thermostat Installation Guide

Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide

1 year ago

Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’S GUIDE

Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE

1 year ago

Hetta HS01RF WIRELESS THERMOSTAT KIT USER MANUAL

Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…

1 year ago

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat USER MANUAL

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…

1 year ago

Honeywell RLV450 PROGRAMMABLE THERMOSTAT USER GUIDE

Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…

1 year ago

Honeywell RLV431 Programmable Thermostat User Guide

Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…

1 year ago