The following Service Menus (SM) commonly require configuration. Please verify that these are set for your specific application. Additional configuration may be required. Refer to Table 2 for all available Service Menus.
WIRING: TERMINAL DESIGNATIONS
WARNING: DISCONNECT POWER BEFORE BEGINNING INSTALLATION.
TABLE 1. TERMINAL BLOCK DESIGNATIONS
C | 24 VAC, Unswitched side | C | 24 VAC, Unswitched side |
W1 | Stage 1 Heat | B/O | Reversing Valve |
W2 | Stage 2 Heat | AUX | Auxiliary Heat |
G | FAN | G | FAN |
A | A | ||
E | E | ||
Y1 | Stage 1 Cool | Y1 | Compressor Stage 1, Heat/Cool 1 |
Y2 | Stage 2 Cool (or Dehumidify) | Y2 | Compressor Stage 2 Heat/Cool 2 (or Dehumidify) |
RH | 24 VAC Power for heating, switched side | RH | 24 VAC Power for heating, switched side |
RC | 24 VAC Power for cooling, switched side | RC | 24 VAC Power for cooling, switched side |
SC | Sensor Common | SC | Sensor Common |
S1 | Indoor Remote Sensor | S1 | Indoor Remote Sensor |
S2 | Occupancy Sensor | S2 | Occupancy Sensor |
TABLE 2. ADVANCED CONFIGURATION: SERVICE MENUS
Some Service Menus may not be available, depending on the system type (SM 110).
MENU | FEATURE | OPTIONS | STD. DEFAULT | DESCRIPTION / COMMENTS |
100 | Schedule Format | 0-3 | 1 | Select the schedule format on the T4000 Series. (Menu not available on non-programmable thermostats.) 0 = nonprogrammable 1 = programmable 2 = 5-1-1 schedule 3 = 5-2 schedule |
101 | Daylight-Saving Time | 0,1 | 0 | Select daylight-saving time as it follows the standard format in the U.S.: It begins on the second Sunday of March at 2:00 AM and ends on the first Sunday of November at 2:00 AM. 0 = Disabled 1 = Enabled (2007 U.S. Format) |
110 | System Type | 1-13 | 1 | Select the appropriate system configuration (determines available Service Menus). 1 = 1 Heat/1 Cool conventional 2 = 1 Heat/1 Cool heat pump 3 = Heat only without a fan (2-wire systems) 4 = Heat only with fan 5 = Cool only 6 = 2 Heat/1 Cool heat pump (with auxiliary heat) 7 = 2 Heat/2 Cool multistage conventional 8 = 2 Heat/ 1 Cool multistage conventional 9 = 1 Heat/ 2 Cool multistage conventional 10 = 2 Heat/ 2 Cool heat pump (no auxiliary heat) |
120 | Fan Control (heating) | 0,1 | 0 | 0 = Fossil Fuel: Gas/Oil/Propane heat (equipment controls heating fan) 1 = Electric Furnace (thermostat controls heating fan) |
130 | O/B Reversing valve | 0,1 | 0 | When 0, output is active for cooling. When 1, output is active for heating. 0 = (O) Active with cooling 1 = (B) Active with heating |
140 | Auxiliary Heat | 0,1 | 0 | 0 = Electric backup heat 1 = Fossil fuel backup heat |
150 | Backlight | 0,1 | 0 | 0 = Backlight temporarily on 1 = Backlight always on (low intensity, 24V only) |
170 | Remote Sensor | 0-1 | 0 | Select sensor if used. Contact PECO for information on the T4000 Series Indoor Remote Zone Sensor. 0 = No Remote Sensors 1 = Indoor Sensor Only |
240 | Number of Program Periods | 2; 4 events | 4 | 2 = 2 events per day (Selections OCC1 and UnOcc1) 4 = 4 events per day (Selections Occ1-UnOcc1-Occ2- UnOcc2) |
250 | Clock format | 12 or 24 Hours | 12 | 12 = 12-hour clock mode 24 = 24-hour clock mode |
260 | Temperature Format (°F or °C) | 0,1 | 1 | 0 = Celsius 1 = Fahrenheit |
270 | Fan Off Delay Heat | 0-99 Seconds | 0 | Select the amount of time (in seconds) that the fan will run after the thermostat heat outputs are turned off. |
280 | Fan Off Delay Cool | 0-99 Seconds | 0 | Select the amount of time (in seconds) that the fan will run after the thermostat cool outputs are turned off. |
290 | Range Low | 50-90 °F or 10-32°C | 50°F (10°C) | Choose the lowest selectable temperature setpoint value. |
300 | Range High | 50-90 °F or 10-32°C | 90°F (32°C) | Choose the highest selectable temperature setpoint value. |
310 | Setback Low | Off; 50-82°F or 11-27°C | 55°F (13°C) | Select the heat setpoint for setback mode. 0 = Off 50-82°F (11-27°C) |
320 | Setback High | Off; 58-90°F or 11-32°C | 90°F (32°C) | Select the cool setpoint for setback mode. 0 = Off 58-90°F (11-32°C) |
330 | Zone Temp Offset | +/-9°F or +/- 4.5°C | 0°F (18 °C) | Adjusts the displayed value; may differ from actual zone temperature. |
340 | Keypad Lockout | 0-3 | 0 | Restricts access to certain features of device; Service Menu still available if enabled. 0 = No key pad lockout (Default) 1 = Disables Schedule and System keys 2 = Disables Schedule, System, and Fan keys 3 = Disables all keys |
MENU | FEATURE | OPTIONS | STD. DEFAULT | DESCRIPTION / COMMENTS |
341 | Enable Pin Access | 0,1 | 0 | Applies a 3 digit access code to enter Service Menu 342 0 = Disable, 1 = Enable |
342 | Set PIN Access Code | 000-999 | 000 | Choose a 3-digit code. |
350 | Fan Mode Enable | 1-3 | 3 | 1 = ON: Fan is turned on regardless of demand. 2 = Auto: Fan is turned on according to heating or cooling demand. 3 = ON or Auto: Allows occupant to select either 1 or 2 above. |
360 | System Mode Enable | 0-3 | 1 | Allows ability to determine which system modes the occupant can select. 0 = OFF, Auto (0 is NOT valid for following configurations: Heat Only; Cool Only.) 1 = OFF, Heat, Cool, Auto 2 = OFF, Heat, Cool 3 = Heat, Cool, Auto |
380 | Minimum Deadband Adjustment | 3-10°F, 1.5-5°C | 3°F | Select a changeover deadband value to prevent short cycling between heating and cooling modes. The value is adjustable to meet various HVAC system requirements. |
390 | Pre-Occupancy Purge | 0-3 hours | 0 hours | Select to energize fan for selected number of hours (0-3) prior to all occupied events. |
395 | Maximum Override Time Limit | 0=Time until next event; or 1-4 hours | 3 | Restricts the duration that a temporary hold can be set. The temporary hold is limited by the maximum amount of time as defined in this Service Menu. 0 = Remainder of time until the next scheduled event. 1 = 1 Hour 2 = 2 Hours 3 = 3 Hours 4 = 4 Hours |
400 | Cycles Per Hour (CPH) Cooling Stage 1 | 0-6 CPH | 0 CPH | Defines the number of cycles per hour for cooling (Stage 1). Select 0 to enable ON-OFF control for Stage 1 cooling. |
410 | Cycles Per Hour (CPH) Cooling Stage 2 | 0-6 CPH | 0 CPH | Defines the number of cycles per hour for cooling (Stage 2). Select 0 to enable ON-OFF control for Stage 2 cooling. |
420 | Cycles Per Hour (CPH) Heating Stage 1 | 0-12 CPH | 0 CPH | Defines the number of cycles per hour for heating (Stage 1). Select 0 to enable ON-OFF control for Stage 1 heating. |
430 | Cycles Per Hour (CPH) Heating Stage 2 | 0-12 CPH | 0 CPH | Defines the number of cycles per hour for heating (Stage 2). Select 0 to enable ON-OFF control for Stage 2 heating. |
450 | Cycles Per Hour Heating Stage 3 | 0-12 CPH | 0 CPH | Defines the number of cycles per hour for heating. Select 0 to enable ON-OFF control for Heating Stage 3. |
460 | Heat Recovery Rate | 0-18°F/Hr 0-10°C/Hr | 0°F/Hr | Defines the rate at which the device achieves the heat comfort setpoint. Select 0 to disable ramp recovery. |
470 | Cool Recovery Rate | 0-18°F/Hr 0-10°C/Hr | 0°F/Hr | Defines the rate at which the device achieves the cool comfort setpoint. Select 0 to disable ramp recovery. |
480 | Minimum Off Time | 1-10 minutes | 4 minutes | Sets the minimum off time for both the heat and cool output. |
490 | Humidity Control Enable (Select models only) | Selects how humidity will be controlled. When dehumidify control is enabled, the Y2 terminal becomes dehumidify. 0 = Disabled 1 = Dehumidify Control | ||
500 | Programmable/ Intermittent Fan | 0-2 | 0 | 0 = Disable 1 = Programmable Fan: Fan operates continuously in occupied periods or with demand in unoccupied periods. 2 = Intermittent Fan: Fan operates based on the on and off times set in menus 501 and 502. |
501 | Intermittent Fan On Time | 1-60 minutes | 5 minutes | Defines the on time for the Intermittent Fan. |
502 | Intermittent Fan Off Time | 0-60 minutes | 25 minutes | Defines the off time for the Intermittent Fan. Select 0 for continuous fan. |
MENU | FEATURE | OPTIONS | STD. DEFAULT | DESCRIPTION / COMMENTS |
520 | Default Display Icons | 0-4 | 0 | Select icons that will be displayed in the Default Display screen. 0 = Time, Temp, Setpoint (SP) 1 = Time, Temp 2 = Time 3 = Temp 4 = None |
530 | Revision | — | — | Displays firmware revision information (for technician); not adjustable. |
540 | Factory Default Reset | 0,1 | 0 | Select 1 (enable) to restore the factory default settings for the thermostat. Select 0 to disable. 0 = Disable 1 = Enable Note: Press the “Done” key to complete the process. |
600 | System Test Main Output (Cool) | 0-2 | 0 | Select the option to activate fan output for 10 minutes; select 0, Done, or a different Service Menu to disable. 0 = Disable (Default) 1= Cool Stage 1 2 = Cool Stage 2 |
610 | System Test Main Output (Heat) | 0-3 | 0 | Select an option to activate the fan output for 10 minutes; select 0, Done or a different Service Menu to disable. Note: Outputs will be activated based upon the system configuration. 0 = Disable (Default) 1 = Heat Stage 1 2 = Heat Stage 2 3 = Heat Stage 3 |
620 | System Test Fan Output | 0,1 | 0 | Select 0 or 1 to activate the fan output for 10 minutes; select 0, Done, or a different Service Menu to disable. Note: For Service Menus 610 and 620, outputs activated based upon the system configuration 0 = Disable Fan Output 1 = Enable Fan Output Note: Outputs will be activated based on the system configuration. |
COPYRIGHT 2015 PECO ASTRONICS. ALL RIGHTS RESERVED P/N 70930 3220-2322 REV 01
DOWNLOAD MANUALS:
Peco T4522-001 Programmable Thermostat User Guide
OTHER MANUALS:
Peco T4000 Programmable Thermostat Installation Guide
Peco T4000 Programmable Thermostat Operating Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…