The original operating instructions were drafted in German. The operating instructions in other languages have been translated from german.
Validity of the operating instructions
These operating instructions are valid for “R-Tronic RT B” (EnOcean) and “R-Tronic RTF B” (EnOcean) wireless thermostats.
Type plate
The type plate is located on the back of the device.
Extent of supply
Please check your delivery for any damage caused during transit and for completeness. Items included in the delivery:
Contact
Declaration of conformity
Oventrop GmbH & Co. KG hereby declares that this product complies with the basic requirements and other relevant provisions of the applicable EC Directives. The declaration of conformity can be obtained from the manufacturer
Correct use
Operating safety is only guaranteed if the product is used correctly. The “R-Tronic” wireless thermostat is used to transmit actual and nominal temperatures of rooms to a “gateway” that controls building automation applications. It supports a variety of “EEP” EnOcean profiles for the European market. This allows the thermostat to be connected to various gateways, such as “butler” or “R-CON FBH”. Apart from transmitting temperature values, additional functions can also be activated, such as fan speed control. In addition, the wireless thermostat can also be used to control freely definable “Sonderfunktionen” (RPS telegram). Any other use of the product will be considered incorrect use. Claims of any kind against the manufacturer and/or his authorized representatives due to damage caused by incorrect use will not be accepted. Observance of the operating instructions is part of compliance with incorrect use.
Warnings
Type and source of danger!
Possible consequences if the danger occurs or the warning is ignored.
Possibilities of avoiding the danger.
The signal words identify the severity of the danger arising from a situation.
Safety notes
The danger caused by inadequately qualified personnel
Any work on this product must only be carried out by qualified tradesmen.
Availability of the operating instructions
Overview of “R-Tronic” without time profile control
Overview of “R-Tronic” with time profile control
Functional description
Together with an actuator, the “R-Tronic” wireless thermostat is used to wirelessly control the temperature of rooms as well as zones within rooms. Depending on the model, power is provided to “R-Tronic” via two batteries or a power pack (100 – 240 V ~/50 – 60 Hz). The communication between the “R-Tronic” and the actuator for radiator control is carried out via a wireless connection. The term “teach-in” refers to a wireless connection that is established between two appliances
Menu structure
Radio-frequency | 868.3 MHz |
Radio range inside buildings | Dependent on materials and interference sources |
Transmission interval | 10 min. (winter mode); 30 min. (summer mode) |
Operation mode | Type 1 (EN 60730-1) |
Protection type | IP20 (EN 60529) |
Protection class | III – Protective low-voltage |
Ambient temperature | +5 °C to +50 °C |
Power supply | Battery type: AA (LR6) 1.5 V, alkaline (no rechargeable batteries); opt. mains operation |
Battery life span | Approx. 2 years (battery capacity > 2,600 mAh) |
Display | LCD |
T measuring range (°C) | 0 °C to +50 °C |
RH measuring range (%) | 0 to 100 % RH (only for “RTF B”) |
Accuracy at +25 °C | ± 1 K |
Accuracy at +25 °C and 20 – 80 % RH | ±4.5 % RH |
Casing | ABS (ASA), traffic white (similar to RAL 9016) |
Casing dimensions | 85 x 85 x 35 mm (W x H x D) |
Accessories
You can obtain spare parts and accessories from specialist stores. The following items are available as accessories
Description | Item number |
Flush-mounted power pack (100 – 240 V ~/50 – 60 Hz) with wall bracket | 1150692 |
Mains adaptor (100 – 240 V ~/50 – 60 Hz) with table stand | 1150694 |
“RP-S F” wireless repeater with switching function for installation in a shock-proof socket (230 V) | 1150699 |
Flush-mounted “RP-C F” wireless repeater for EnOcean wireless technology, 230 V/50 Hz | 1153060 |
Cover frame, 88 x 88 mm | 1150693 |
Transport and storage
Transport the product in its original packaging. Store the product under the following conditions
Temperature range | -10 °C to +65 °C |
Relative air humidity | Max. 70 % |
Particles | Dry and dustproof |
Mechanical influences | Protected from mechanical agitation |
Radiation | Protected from UV rays and direct sunlight |
Chemical influences | Do not store together with solvents, chemicals, acids, fuels or similar substances |
Installation location
As an alternative to wall attachment, you can operate the wireless thermostat using a table stand (available optionally as an accessory). The table stand should be self-supporting, e.g. placed upright on a table and uncovered. | |
Ensure that the radio range cannot be adversely affected by spatial factors such as the room geometry or objects, materials and interference sources. Such factors may produce a “radio shadow”, e.g. behind metal objects. |
Wall attachment of the fixing plate of the “R-Tronic” with wall bracket (battery operation)
Proceed as follows to access the menu:
Press and hold the menu button for at least one second to access the “MAIN MENU”.
The “MAIN MENU” contains the following main areas: “TEMPERA- TURES”, (“TIME PROFILE”), “SETTINGS”, “INFORMATION” (refer to Illustr. 3 on page 28). |
You can navigate within the “R-Tronic” menus and select the desired functions via the menu button (refer to Illustr. 1 on page 26 (6)). You can access all the sub-menus and functions by turning (navigating) and pressing (confirming the selection and saving). You can press the Back button to go back to the previous step.
Once the display has been activated, it returns to the default view after several seconds if no additional operating steps are performed. |
The following symbols are shown on the display of the wireless thermostat.
Overview of the supported EnOcean equipment profiles (EEP)
The wireless thermostat supports a total of five EEP profiles, which, together with a gateway, each controls different and, in some cases, numerous functions. Always ensure that only a single profile can be activated during commissioning. The overview of user navigation controlled via the display (refer to Illustr. 3 on page 28) shows the respective activation process for each individual EEP profile. “R-Tronic RTB”:
Function EEP profile | ACTUAL VALUE1 | Nominal value2 | Fan speeds3 | Room occur- pancy4 | Function keys (+) (–)5 |
A5-10-02 | x | x | x | x | |
A5-10-03 | x | x | |||
A5-10-04 | x | x | x | ||
A5-10-06 | x | x | x | ||
A5-10-06 + RPS | x | x | x | x |
1 ACTUAL VALUE | Measured room temperature (°C) |
2 Nominal value | Desired room temperature (°C) |
3 Fan speeds | OFF, I, II, III, AUTO |
4 Room occupancy | present/absent |
5 Function keys | Freely definable, e.g. on/off, value increase (+)/value decrease (-) |
6 Humidity | Measured humidity (% RH) |
Function EEP profile | ACTUAL VALUE1 | Nominal value2 | Fan speeds3 | Room occur- pancy4 | Function keys (+) (–)5 | Humidity6 |
A5-10-11 | x | x | x | x | ||
A5-10-11+RPS | x | x | x | x | x | |
A5-10-12 | x | x | x | |||
A5-10-22 | x | x | x | x | ||
A5-10-23 | x | x | x | x | x |
The setting of the EEP profile
Ensure that your gateway is compatible with the EnOcean Equipment Profile (EEP). During initial commissioning, adjust the settings as follows to set the desired EEP:
A5-10-02 | A5-10-03 | A5-10-04 | A5-10-06 | A5-10-06 + RPS |
A5-10-23 | A5-10-12 | A5-10-22 | A5-10-11 | A5-10-11 + RPS |
English | English | English | English | English |
Fan YES | Fan NO | Fan YES | Fan NO | Fan NO |
Room occu- pancy YES | Special function NO | Room occupancy NO | Special function NO | Special function YES |
Room occupancy NO | Room occupancy YES | |||
► The selected EEP now appears on the display and is activated. |
Changing the EEP profile
If you want to change the EEP profile or if you mistakenly activated the wrong profile, you must set the thermostat back to its factory settings. A different profile or the correct profile can then be activated during reinstallation.
Teaching in of the gateway
Activation of the EEP profile does not establish an automatic communication link to the gateway. A link is established once a so-called send telegram is sent via the “R-Tronic”. Once the gateway receives this telegram, the teach in process for the wireless thermostat begins.
To send the teach in telegram to the gateway, proceed as follows:
Nominal value setting
Room occupancy setting
If the A5-10-02, A5-10-06, A5-10-06 + RPS, A5-10-11, A5-10-11 + RPS, or A5-10-23 EEP profile was activated during commissioning, the “Room occupied” function is available on “R-Tronic”. This can be switched on when the room is occupied and switched off when exiting the room. You can switch the setting in the display menu from “Present” to “Absent” and vice versa by pressing the menu button twice.
Menu lock setting
Once the teach in process has been completed, the menu lock is automatically activated and the “padlock” symbol appears. It is not possible to navigate to the main menu when the menu lock is activated (7.1 on page 32
Reset “R-Tronic” to factory settings
Proceed as follows to reset the “R-Tronic” to its factory setting:
Error messages
Error message | Cause |
BATTERY EMPTY | |
REPLACE BATTERIES | |
POWER SUPPLY DEFECT | The power supply for “R-Tronic” is currently insufficient. |
RADIO MODULE ERROR | |
INIT ERROR | There is an initialisation error. |
MEMORY DEFECT | Error in the electronic memory. |
T-SENSOR DEFECT | Defective temperature sensor |
H-SENSOR DEFECT | Defective humidity sensor |
TIME PROFILE INVALID | Individual time profile incorrectly programmed |
Advice for the user
Functions such as lighting control (on/off) or blind operation (open/close) are not stored directly in “R-Tronic”, but must be configured in the connected “Gateway”.
Directive 2012/19/EU WEEE:
Waste electrical and electronic equipment (WEEE) must not be disposed of with domestic waste, but must be dropped off at a collection point for the recycling of electrical and electronic appliances
DOWNLOAD MANUALS:
Oventrop 1150780 R-Tronic Wireless Thermostat Operating Instructions
Oventrop 1150780 R-Tronic Wireless Thermostat Operating Instructions
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…