The TZEMT500B Thermostat is compatible with single and multistage forced air systems, including:
The TZEMT500B Thermostat may be compatible with some other system types, including:
The TZEMT500B Thermostat is not compatible with the following system types:
WARNING
MERCURY NOTICE
When this control is replacing an old control that contains mercury in a sealed tube, do not dispose of your old control in the trash. Dispose of properly. Contact your local waste management authority for instructions regarding recycling and proper disposal of the old control. A listing of heating, ventilating and air conditioning wholesalers that participate in the Thermostat Recycling Corporation’s recycling program are available at www.thermostat-recyle.org.
Remove existing wall plate.
Separate the face of the new thermostat from the wall plate.
NOTE: It is not recommended that this Z-waveTM thermostat be mounted onto metal structures. Metal may adversely affect the radio frequency (RF) communication between the thermostat and the Z-waveTM bridge.
Mark two mounting holes using new wall plate.
Install new wall plate.
Attach all wires securely to the new thermostat.
(See the Field Wiring Diagrams on the following page.)
Indoor Unit | Outdoor Unit | |||||
1 Stage Cooling | 2 Stage Cooling | 2 Step Cooling | 1 Stage Heat Pump | 2 Stage Heat Pump | 2 Step Heat Pump | |
1 or 2 Stage Gas Furnace (PSC/CTM) | A | NA | NA | C 1 | NA | NA |
2 Stage VSPD Gas Furnace | A | A | B | C 1 | C 1 | D 1 |
COM Furnace | A | A | A | C 1 | C 1 | C 1 |
Air Handler (PSC/CTM) | A | NA | NA | C | NA | NA |
VSPD Air Handler | A | A | B | C | C | D |
COM Air Handler | A | A | A | C | C | C |
Oil Furnace (PSC) | E | NA | NA | E 1 | NA | NA |
Oil Furnace (VSPD) | E | E | F | E 1 | E 1 | F 1 |
Enhanced Dehumidification Mode | See Notes 3, 4 |
System Type A – 1 or 2 Stage Heating with 1 or 2 Stage Cooling
System Type B – 2 Stage Variable Speed Gas Furnace or Variable Speed Air Handler with 2 Step Cooling
System Type C – PSC, CTM, Variable Speed, or 24 Volt Communicating Air Handler or gas furnace with 1 or 2 Stage/Step Heat Pump
X2OSystem Type D – Variable Speed Air Handler or Furnace with 2 Step Heat Pump
System Type E – Oil Furnace with 1 or 2 Stage Cooling or Heat Pump
System Type F – Variable Speed Oil Furnace with 2 Step Coolingor Heat Pump
Enhanced Dehumidification Mode
When the TZEMT500B is connected to variable speed indoor products,the enhanced dehumidification mode can reduce indoor airflow to improve dehumidification during the cooling run cycle. When 24 VAC is present at the BK terminal,(HC to H1 = N.C.) airflow will be 100 percent. When 24 VAC is removed from BK, (HC to H1 = N.O.) airflow will be reduced by 20 percent. See Notes 11 and 12 Not applicable with 2 step outdoor products combined with legacy variable speed indoor products that requireBK for high stage airflow: System Types B, D, or F on page 4.
Optional Remote Temperature Sensors Installation
Wire specification (RS1 & RS2): 2 conductors, 18 gauge wire. Make sure that the sensor wires have a cable separate from the thermostat cable. Best results for distances of 100 feet or less. Accuracy may be affected for distances up to a maximum of 200 feet. Shielded cable is recommended for distances over 100 feet and less than 200 feet.
CAUTION: Keep this wiring at least one foot away from large inductive loads such as electronic air cleaners, motors, line starters, lightning ballasts, and large distribution panels. Failure to follow these wiring practices may introduce electrical interference (noise) which can cause erratic system operation. Shielded cable is required if the above wiring guidelines cannot be met. Be sure to ground only one end of the shield to the thermostat common terminal. Tape back the other end of the shield.
Remote Sensors Part Numbers
Remote Temperature Sensor Connections and Operation:
Indoor sensor connected to RS1. Replaces internal sensor. RS2 not connected.
Indoor sensor connected to RS2. Averages temperature with internal sensor. RS1 not connected.
Indoor sensors connected to RS1 and RS2. Averages RS1 and RS2 sensor temperatures. Internal sensor is not used.
Outdoor sensor connected to RS2. Reports outdoor temperature to comfort control.
Indoor sensor connected to RS1 and Outdoor sensor connected to RS2. RS1 replaces the internal sensor. RS2 reads the outdoor temperature.
If necessary, cut the internal jumper wire (JP1).
Cutting the JP1 jumper
The jumper is located on back of the thermostat face as shown in the illustration to the right. Cut the jumper using small diagonal cutters being careful not to damage the board.
Attach the thermostat face to the wall plate.
Turn power to heating and cooling system back on.
The thermostat display should turn on and begin displaying information. If the thermostat display does not come on, go back through the installation steps and look for problems
Set Time and Date
If your System Type is:
Mechanical Settings
For Gas Furnace – Multistage Mechanical Settings
For Electric Furnace Mechanical Settings
Heat Pump Mechanical Settings
Enable Dual Fuel
Optional Remote Temperature Sensors Installation
Remote sensor input RS2 can be configured for use as indoor or outdoor temperature sensing. An outdoor temperature sensor is required for Dual Fuel Restricted mode. The factory default setting for RS2 is “IN” for use with remote indoor temperature sensing and/or averaging. To configure RS2 to sense outdoor temperature, complete the following steps:
Test All Modes of Operation
Fan, Cooling, and Heating.
Prepare the bridge for enrollment.
Note: If the bridge is already installed, follow the instructions as they are written in the following steps. If the bridge is not installed, follow the Quick Start Guide publication number shipped with the thermostat starter kit.
Enroll the thermostat into the bridge. (Inclusion)
Verify enrollment of the thermostat.
Establish Online Control of the Thermostat.
Exclusion (Only used to unenroll a thermostat from the bridge)
Z-Wave™ controllers from various manufacturers may support the Z-Wave™ Thermostat General V2 Device class used by the Z-Wave™ Thermostat. If you are using a controller that is not a Nexia bridge, consult the instructions that came with the controller to find out how to enroll a new device.
Item | Description | Notes |
Clock Display | The current time is displayed in the upper left corner of the main screen. The time will blink when the clock has not been set. | See Set Clock for more information. |
Dynamic Labels and Function Control Buttons | The buttons are defined by the dynamic labels above each button. As you navigate through menus, the labels for the buttons will change. | |
Setpoint Display and Setpoint Up/Down Buttons | The current heat and cool setpoints are displayed. These setpoints may be set using the Z-Wave control system, the thermostat’s internal schedule, or by pressing the Setpoint Up/Down buttons. In HEAT mode, the Setpoint Up/Down buttons change the heat setpoint. In COOL mode, they change the cooling setpoint. In AUTO mode, the buttons change the last call’s heating or cooling setpoint. | The setpoints will push each other if they are adjusted to within the minimum heat/cool separation setting. This is normally 3 degrees. The internal schedule is disabled by default. See Schedules for more information. |
Temperature Display | The thermostat displays the current temperature as sensed by the internal temperature sensor. | The internal temperature sensor can be adjusted as necessary. See Internal Sensor Calibration for more information. |
Menu Button | Button used to access other thermostat menus | Other thermostat menus can be accessed by pressing the MENU button. |
System Mode Button | Button used to change the system mode | Off: System off Heating: Heating only on Cooling: Cooling only on Auto: Heating/Cooling on as necessary |
Fan Mode Button | Button used to change the fan mode: | Auto: Fan on when cooling/heating is necessary On: Fan constantly on Fan Cycler (note 1) Smart Continuous Fan (notes 1, 2) |
Schedule Mode Button | Button used to change the schedule mode: | Hold: System maintains the current temperature setpoints. Schedules are disregarded. Run: Run the system schedule (or Z-Wave controlled schedule) Energy Saving Mode: Temperature setpoints in ESM Setpoints are maintained. See ESM Setpoints on for more information. |
Note 1 See the Installer Settings menu to enable Note 2 See the User Settings menu to set RH setpoint |
The model TZEMT500BB32MAA thermostat provides typical thermostat control of a central heating and cooling HVAC system. These thermostats also features a Z-Wave™ module for remote control
Normally, the thermostat displays the thermostat control screen as shown above
Minimized Display Mode
Optionally, you can set the thermostat to show only the temperature in minimized display mode. This mode can be enabled or disabled in the Users Settings screen. See Screen Timeout for more information.
Menu Maps – User Settings
Menu Maps – INSTALLER Settings
Filter Service
The Filter Service screen will show the accumulated Runtime hours as well as the Service Interval that will be used to trigger a Filter Message. Any type of HVAC operation that causes the HVAC system fan to run will cause the Filter Runtime value to increase. When the Runtime hours equals the Service Interval hours, a “Filter” message to remind you to replace the filter. Once the filter has been replaced, press the Reset button to reset the Filter Runtime value to zero.
Filter Settings
To View/Reset Filter Runtime
Change the Filter Service Interval
Disable the Filter Service Interval
The Maintenance Service screen shows the accumulated Heat and Cool Runtime hours as well as the Service Interval that will be used to trigger a Maintenance Message. Any HEAT or COOL type of HVAC operation will cause the respective Runtime values to increase. When the combined HEAT and COOL Runtime hours equals the Service Interval hours, a “Maint” message to remind you your HVAC system may require periodic maintenance. Press the Menu button to enter the Filter Service screen. The Reset button can be pressed and the HEAT and COOL Runtime values will be reset to zero.
Maintenance Service Interval
Change the Maintenance Service Interval
Disable the Maintenance Service Interval
This is the time before any screen reverts to the Minimized Screen (temperature display only), after you stop pushing buttons. Minimized Screen feature is disabled by setting this time to “0”.
Screen Timeout
Change the Screen Timeout
Disable the Minimized Display
RH% Setpoint
Balance Point
The F/C Settings screen is use to select the temperature display mode. Fahrenheit (F) or Celsius (C) are the two available modes
Change the Temperature Mode
Internal Sensor Calibration
The Sensor Calibration screen is used to change the temperature calibration of the internal temperature sensor. The temperature calibration can be changed by +/- 7 degrees. When the Sensor Calibration screen is selected, the current temperature calibration is displayed. In the example screen, the calibrated temperature is 77 and the number of degrees of offset being applied is 1.
Change the Sensor Calibration
Usage Graph
The Usage Graph shows daily heating and cooling runtime hours for a week. The button in the lower right corner will change depending on what is being displayed. When the heating time is displayed, the button will read Cool. When the cooling time is displayed, the button will read Heat Press the Heat/Cool button to display the heating/cooling time.
The Backlite/Display screen is used to set the backlight time-out and contrast. Backlite Timeout is the time (in seconds) from the last button press to the backlight going out. The time-out can be set between zero (0) and one hundred and twenty (120) seconds. Thirty (30) is the default setting. When set to zero (0), the backlight will remain always on. Contrast sets the contrast level of the LCD display. The contrast can be set between zero (0) and twenty (20). Ten (10) is the default setting. If the display is too light, using a higher number. If dark lines appear in the display, use a lower number.
Backlight
A. Adjust the Backlight
B. Adjust the Contrast
ESM Setpoints
Energy Saving Mode (ESM) Setpoints are the setpoints used when the Energy Saving Mode schedule is selected in the Schedule Mode screen.
Adjust ESM Setpoints
The Installer Settings screen is a hidden screen designed for use by qualified installers and service technicians. Do not change any settings in these screens unless you are a qualified installer or service technician
Setting | Range | Default | Description |
Display Lock | Y or N | N | Locks or unlocks the thermostat buttons. When the buttons are locked, the main menu can still be accessed, but no menu options may be selected. The Installer Settings hidden button operation is always operational, allowing Display Lock to be turned off. |
System Settings | See next page | ||
Max Heat SP | 55F to 90F (12C-32C) | 90F (32C) | Sets the maximum heating setpoint value. Will not ramp or accept setpoints higher than this maximum. |
Min Cool SP | 60F to 99F (15C-37C) | 60F (15C) | Sets the minimum cooling setpoint value. Will not ramp or accept setpoints lower than this minimum. |
Minimum Run Time (MRT) | 1- 9 Minutes | 3 | Sets the minimum run time before a heating/cooling cycle can turn off to prevent rapid cycling. Thermostat screen will display Cool ON or Heat ON while the minimum run time is being enforced. |
Minimum Off Time (MOT) | 5-9 Minutes | 5 | Sets the minimum off time before another heating/cooling cycle can begin to provide compressor short cycle protection. Thermostat screen will display WAIT when minimum off time is being enforced. |
T-Sense | 1-6 | 2 | Sample rate of temperature sensor Low Sample Rate = Less sensitive (slower response) High Sample Rate = More sensitive (faster response) |
Fan Cycler 1 Fan ON Time | 0-120 minutes | 0 (= OFF) | The fan cycler function cycles the HVAC system fan for an ON period followed by an OFF period continuously. Used to provide minimum air ventilation requirements. While the Fan ON time is set to a value greater than 0, an additional Cycler FAN mode is present when pressing FAN button. |
Fan Cycler 1 Fan OFF Time | 10-120 minutes | 10 | |
Remote Sensors | IN or OUT | IN | Used to enable remote temperature sensing, averaging, or for outdoor temperature setting for display and/or dual fuel restricted mode. |
Dehumidification Options | See Dehumid Option table | ||
Restore Defaults | n/a | n/a | Sets all of the thermostat settings back to the factory defaults. |
Changing these settings will affect the operation of the heating/cooling system. To view and edit these settings:
System Settings
Changing these settings will affect the operation of the heating/cooling system. To view and edit these settings:
Note on Delta Settings: The Delta T Setting is the delta, or difference between, the setpoint and current temp for determining when a heat or cool call comes on. The “delta” is the number of degrees away from the setpoint.
Setting | Range | Default | Description |
Mechanical Settings | See next page | ||
Balance Point | 5-70 F | 40 F | This is a user selectable value for when dual fuel “Restricted” mode is enabled. The temperature selected is the compressor lockout temperature. When the outdoor temperature is above this setpoint, only the heat pump will run for heating. When the outdoor temperature is below this setpoint, only the furnace will run for heating. |
Schedule Enable | Y or N | N | When enabled, the local thermostats scheduler function is enabled. |
Recovery Enable | Y or N | Y | The Recover feature is active only when “Schedule” is enabled and the schedule mode is set to “RUN” Recovery operation, when enabled, will start the cooling or heating system so that the desired comfort temperature is reached by the next scheduled set point time. The advance start time calculation is a learned process that is recalculated and adjusted each day until the room temperature is at the target temperature at the schedule time. When the thermostat is in Recovery mode the display will show “Recov”. Recovery works for all scheduled periods (1-4) and in HEAT, COOL or AUTO modes. While in Recovery the Aux-Heat stage will not engage. The maximum Recovery time is one hour. |
H/C Delta | 3 – 15 degrees | 3 | Sets the minimum separation between heating and cooling setpoints. Attempts to lower the cooling below the heating setpoint by this amount will PUSH the heating setpoint down to maintain this separation. Same for setting the heating setpoint above the cooling setpoint, it will PUSH the cooling setpoint up to maintain this separation. |
Heating Delta Stage 1 ON | 1 to 8 degrees | 1 | Sets the delta from setpoint that stage 1 heating starts. |
Heating Delta Stage 1 OFF | 0 to 8 degrees | 0 | Sets the delta from setpoint that stage 1 heating stops. Stage 1 turns off at setpoint minus (-) Delta Stage 1. |
Heating Delta Stage 2 ON | 2 to 8 degrees | 2 | Sets the delta from setpoint that stage 2 heating starts. |
Heating Delta Stage 2 OFF | 0 to 8 degrees | 0 | Sets the delta from setpoint that stage 2 heating stops. Stage 2 turns off at setpoint minus (-) Delta Stage 2. |
Heating Delta Aux Heat ON | 3 to 8 degrees | 3 | Sets the delta from setpoint that Aux Heat starts. |
Heating Delta Aux Heat OFF | 0 to 8 degrees | 0 | Sets the delta from setpoint that stage 1 heating stops. Aux Heat turns off at setpoint minus (-) Delta Aux Heat. |
Cooling Delta Stage 1 ON | 1 to 8 degrees | 1 | Sets the delta from setpoint that stage 1 cooling starts. |
Cooling Delta Stage 1 OFF | -2 to 8 degrees | 0 | Sets the delta from setpoint that stage 1 Cooling stops. Stage 1 turns off at setpoint plus (+) Delta Stage 1. |
Cooling Delta Stage 2 ON | 2 to 8 degrees | 2 | Sets the delta from setpoint that stage 2 cooling starts. |
Cooling Delta Stage 2 OFF | -2 to 8 degrees | 0 | Sets the delta from setpoint that stage 2 Cooling stops. Stage 2 turns off at setpoint plus (+) Delta Stage 2. |
Mechanical Settings
Changing these settings will affect the operation of the heating/cooling system. Options for mechanical setting will depend on the System Type selected. To view and edit these settings:
Setting | Range | Default | Description |
Type | Gas/Elec | Gas/Elec | Selects system type Gas/Electric |
Fan Type | Gas or Elec | Gas | Selects the Fan type if system is Gas or Electric |
2nd Stage Heat | Y or N | N | Enables the 2nd Stage Heat operation |
2nd Stage Cool | Y or N | N | Enables the 2nd Stage Cool operation |
Setting | Range | Default | Description |
Type | Heat Pump | Heat Pump | Selects system type Heat Pump |
C/O Type | w/Cool or w/Heat | w/Cool | Set the Heat pump Changeover type |
2nd Stage Heat | Y or N | N | Enables the 2nd Stage Heat operation |
Aux Heat (HP) | Y or N | Y | Enables the Auxiliary Heat operation. Typically the Aux Heat will be heat-strips in a Heat Pump system |
2nd Stage Cool | Y or N | N | Enables the 2nd Stage Cool operation |
Setting | Range | Default | Description |
Type | Heat Pump DF | Heat Pump DF | Selects system type Heat Pump with Dual Fuel (Gas or Oil Furnace) |
DF Type | Restricted / Non-restricted | Non-restricted | Non-restricted mode will follow thermostat demand for each heating stage. Restricted mode will lock out the compressor at a selectable outdoor temperature. Default balance point is 40° F. |
C/O Type | w/Cool or w/Heat | w/Cool | Set the Heat pump Changeover type |
2nd Stage Heat | Y or N | N | Enables the 2nd Stage Heat operation |
Aux Heat (HP) | Y or N | Y | Enables the Auxiliary Heat operation. Typically the Aux Heat will be heat-strips in a Heat Pump system |
2nd Stage Cool | Y or N | N | Enables the 2nd Stage Cool operation |
Balance Point | 5-70 | 40 | Balance point is used to select the “Restricted” compressor lockout temperature. |
Dehumidification Options Settings
Changing these settings will affect the operation of the heating/cooling system. To view and edit these settings:
Setting | Range | Default | Description |
Cooling Droop | 0-2 | 0 | 0=Off, 1=1 degree, 2=2 degrees. This is the amount of temperature overshoot allowed during low-load cooling conditions |
Smart Cont Fan | Y-N | N | Y=On, N=Off. When enabled, this feature will cancel continuous fan operation when room RH% is higher than the RH% setpoint. |
Enhanced Dehumidification | Y-N | N | Y=On, N=Off. When enabled and connected to a variable speed blower motor control, this feature will reduce the indoor blower speed when room RH% is higher than the RH% setpoint to provide additional dehumidification during the cooling run cycle. |
RH Calibration | -7 to +7 | 0 | Used to recalibrate the RH sensor |
Scheduling is usually controlled by your Z-Wave system. See the instructions that came with your Z-Wave system for more information; however, scheduling may also be controlled by the thermostat. ÎÎThe Schedules menu is hidden by default, but may be enabled in the Installer Settings. See Enable/Disable the Schedules Menu below for more information.. The thermostat has a 4 x 7 schedule, meaning the setpoints can be changed up to four times a day each day. Each day has a separate schedule. Schedules may be copied from one day to another day or group of days. See Copy a Day Schedule on page 26 for more information.
Enable/Disable the Schedules Menu
Because the Schedules menu is disabled by default, you must first enable it before any scheduling can be done at the thermostat. If you want to use your Z-Wave system for scheduling, scheduling must be disabled in the thermostat.
Load a Preset Schedule
There are two possible schedules that may be loaded: Preset Comfort and Preset Energy Save. These schedules may not be changed. When a schedule is loaded, it changes the current Heat and Cool schedule settings. You can then edit the Heat and Cool schedule, if necessary. Selecting Preset Comfort or Preset Energy Save schedules will overwrite the current Heat and Cool schedule.
Preset Schedule | Description |
Preset: Comfort | This is a preset schedule with mild setbacks, designed to maintain a comfortable temperature. |
Preset: Energy Save | This is a preset schedule with deeper setbacks, designed to conserve energy. |
View the Current Schedule
Set a Heat and Cool Schedule
Copy a Day Schedule
Smart Continuous Fan (SCF) Operation
Smart Continuous Fan will provide for continuous fan operation to control humidity. To use SCF, you must enable SCF operation in the Installers Settings menu under the Dehumidification Options menu. Set Smart Cont Fan to Y to enable it. To turn on SCF, set the Fan mode to SCF. When SCF fan mode is selected, the HVAC system fan will run continuously unless the humidity rises above the RH setpoint.The RH setpoint is set in the User Settings menu. Default RH is set to 50%. SCF fan operation is turned off when RH is above the setpoint. SCF operation is resumed at the end of the next cooling call.
U.S.A. and Canada Only This limited warranty is extended by the manufacturer to the original purchaser and to any succeeding owner of the real property to which the low voltage room comfort control is originally affixed and applies to products purchased and retained for use within the U.S.A. and Canada. The limited warranty period begins when the low voltage room comfort control installation is complete, verified by installer’s invoice or similar document. If installation completion and start-up date cannot be verified by installer’s invoice or similar document, limited warranty coverage begins six (6) months after the date of manufacture based on the low voltage room comfort control serial number. If any part of your low voltage room comfort control fails because of a manufacturing defect within five (5) years from the date the limited warranty period begins, Warrantor will furnish without charge a new low voltage room comfort control. Any local transportation, related service labor, and diagnosis calls, are not included. This limited warranty does not apply if the low voltage room comfort control was purchased direct (i.e. from internet websites or auctions) on an uninstalled basis. Additionally, this limited warranty will not apply unless the low voltage room comfort control is: (1) installed by a licensed or qualified HVAC technician, (2) applied and installed in accordance with the manufacturer’s recommendations in its Installer’s Guide, and (3) in compliance with all industry standards, national, state, and local codes. This limited warranty does not cover your low voltage room comfort control if it is damaged while in your possession; including, but not limited to (1) damage caused by unreasonable use of the low voltage room comfort control, (2) damage from failure to properly maintain the low voltage room comfort control as set forth in the Use and Care manual, (3) damage that is not considered a manufacturing defect, such as acts of God, malfunctions or failures resulting from fire, water, storms, lightning, earthquake, theft, riot, misuse, abuse, increased utility usage costs, (4) performance problems due to improper selection/equipment match-up, installation, or application, or (5) failures, defects, or damages (including, but not limited to, any failure or loss of data) caused by any third party product, service, or system connected or used in conjunction with your low voltage room comfort control. THE LIMITED WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER WARRANTIES AND LIABILITIES, WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESSED OR IMPLIED, IN LAW OF IN FACT, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR USE, AND IN NO EVENT SHALL WARRANTOR BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES. Some states do not allow limitations on how long an implied limited warranty lasts or do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This limited warranty gives you specific legal rights, and you may also have other rights which vary from state to state. Parts will be provided by our factory organization through an authorized service organization in your area listed in the yellow pages. If you wish further help or information concerning this limited warranty, contact
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
This equipment has been tested and found to comply with the limits for Class B Digital Device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures.
IC Notice
This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions:
Nexia
DOWNLOAD MANUAL
Nexia TZEMT500BB32MAA Home Energy Management Thermostat User Guide
Nexia TZEMT500BB32MAA Home Energy Management Thermostat User Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…