Mco-home A8-9 Electrical Heating Thermostat Instruction MANUAL

Mco-home A8-9 Electrical Heating Thermostat

MCOHome A8-9 is a Z-Wave enabled multiple environmental monitoring sensors, with 3.5 inch TFT clear display and compliant to Z-Wave Plus standard. It is built in with Temperature, Humidity, PM2.5, CO2, VOC, PIR, illumination, Noise, Smoke sensors. Device can be added into any Z-Wave network, and is compatible with any other Z-Wave certified devices.

Technical Data

  • Temperature: 0~50℃
  • Humidity: 0%RH~99%RH
  • PM2.5: 0~500ug/m3
  • CO2: 0~5000ppm
  • VOC: 0-64000ppb
  • PIR: 0 or 1 Detection angle up to 120°
  • Illumination: 0~40000Lux
  • Noise: 30dB~100dB
  • Smoke: 0 or 1

Specification

  • Power Supply: DC12V
  • Self-dissipation:<3W
  • Work environment:-20~+60℃ <99%RH (Non-condensation)
  • Dimension: 110* 110*32mm
  • Hole Pitch: 60mm or 82mm
  • Housing: Tempered glass+ PC Alloy
  • Installation: Wall-mounted (Vertical)

Safety Information

To protect yourself and others from danger and to protect the device from damage, please read the safety information before using it.

Important

  • A qualified electrician with the understanding of wiring diagrams and knowledge of electrical safety should complete installation following the instructions.
  • Before installation, please confirm the real voltage complying with the device’s specification.
  • Cut off any power supply to secure the safety of people and device.
  • During installation, protect the device from any physical damage by dropping or bumping. If happens, please contact the supplier for maintenance.
  • Keep the device away from acid-base and other corrosive solids, liquids, gases, to avoid damage.
  • Avoid overexertion during operation, to protect device from mechanical damage.
  • Read all instructions and documentation and save for future reference.

Installation &Wiring

Location

Device is suggested to be installed indoor, a place with around 1.5m height above the floor where represents the average CO2 concentration. It should be away from direct sunlight, any cover, or any heat source, to avoid false signal for temperature control.

Notice

  • Device must be wall-mounted vertically. Do not lay it flat or upside down while working.
  • Do not mounted it in a wind gap, or cover its bottom, which may affect the detected data.
  1. Step 1: Remove the steel frame from the backside of the device, and then fix it onto the installation box with 2 screws.
  2. Step 2: Wire the adaptor.
  3. Step 3: Put the device back onto the steel frame, it will attach with the frame firmly by built-in magnets.
  4. Step 4: Check the installation and power, the device is ready for work.

Operation

Power on/ power off

  • Wire the adaptor and the device is powered on. It will display all detected information by the sensors.

Display interface

Hold Key F1 can switch among the following 4 display interfaces:

  1. Data detecting: display all sensors’ data
  2. Network: Z-Wave Add/Remove
  3. Data calibration: to calibrate the detected data manually
  4. Local time setting

Z-Wave Operation

Note: A Security Enabled Z-Wave Controller must be used in order to fully utilize the product.

Add &Remove Z-Wave network

  • Activate Add/Remove mode in the gateway. When device is powered on, hold F1 to choose interface for Add or Remove Z-Wave network.
  • Click F2 five times until turns blue.
  • Hold F2 and the device enters into learning mode, then turns blue and the device is added into Z-Wave network.
  • Follow the same steps to remove the device from network.

Association Group

Device supports 1 association group:

AG

identifier

Max

Node ID

Command Classes Trigger situation
0x01 1 COMMAND_CLASS

_SENSOR_MULTIL EVEL_V5, SENSOR_MULTILE VEL_REPORT_V5

Detected value will be reported according to:
  1. PM2.5 The value difference between current value and previous reported value >0x01 set value, set value ≠0;
  2. CO2 The value difference between current value and previously reported value> 0x02 set value, set value≠0;
  3. Temperature The value difference between current value and previous reported value > 0x03 set value, set value≠0;
  4. Humidity The value difference between current value and previous reported value > 0x04 set value, set value≠0;
  5. VOC The value difference between current value and previous reported value > 0x05 set value, set value≠0;
  6. Illumination The value difference between current value and previous reported value > 0x06 set value, set value≠0;
  7. Noise The value difference between current value and previous reported value > 0x07 set value, set value≠0;
  8. PIR The current state is different from previous reported state, set value≠0;
  9. Smoke The current state is different from previous reported state, set value≠0;
  10. Smoke IntervalReport Timer set value: 0x0A and set value≠0;
  11. PIR IntervalReport Timer set value: 0x0B and set value≠0;
  12. PM2.5 IntervalReport Timer set value: 0x0C and set value≠0;
  13. CO2 IntervalReport Timer set value: 0x0D and set value≠0;
  14. Temperature IntervalReport Timer set value:

Command Class supported by the device: ( Supports S2 unauthenticated level)

  • COMMAND_CLASS_VERSION,
  • COMMAND_CLASS_MANUFACTURER_SPECIFIC,
  • COMMAND_CLASS_DEVICE_RESET_LOCALLY,
  • COMMAND_CLASS_POWERLEVEL,
  • COMMAND_CLASS_ASSOCIATION,
  • COMMAND_CLASS_ASSOCIATION_GRP_INFO,
  • COMMAND_CLASS_CONFIGURATION,
  • COMMAND_CLASS_SENSOR_MULTILEVEL,
  • COMMAND_CLASS_FIRMWARE_UPDATE_MD

Command Class supported by the device: (Not supports S2)

  • COMMAND_CLASS_ZWAVEPLUS_INFO,
  • COMMAND_CLASS_TRANSPORT_SERVICE_V2,
  • COMMAND_CLASS_SECURITY_2,
  • COMMAND_CLASS_SUPERVISION

Restore Factory Setting

  1. Press & hold F1 to enter Z-Wave setting interface, then press & hold F1 again to enter parameters setting interface;
  2. Press & hold F2 to enter setting interface and select “default”;
  3. Click F2 3 times and displays “OFF”–>“ON”–>“OK”–>“OFF”, factory setting is restored.

Note: Please use this procedure only when the network primary controller is missing or otherwise inoperable.

Data Calibration

  • Hold F1 to choose interface for data calibration. Then hold F2 to switch among the sensors. Choose one and click F2, F1 to change the data. After finished, hold F1 can return data detecting interface.

Local time setting

  • Hold F1 to choose interface for local time setting. Then hold F2 to switch among “Hour-Minute-Second-Year-Month-Date”. Click F2, F1 can change the data of flashing item.
  • After finished, hold F1 can return data detecting interface.

Parameters table

Add Parameter Byte Options Default Range

0x01

PM25_Delta_Level

1

=0    Turn off report

>=1 Report when change > n * 1ug/m3

0

0-127

0x02

CO2_Delta_Level

1

=0    Turn off report

>=1 Report when change > n * 5ppm

0

0-127

0x03

Temp_Delta_Level

1

=0    Turn off report

>=1 Report when change > n*0.5℃

0

0-127

0x04 Humidity_Delta_Level 1 =0    Turn off report

>=1 Report when change >n%

0 0-127

0x05

VOC_Delta_Level

1

=0    Turn off report

>=1-127*5ppb Reportchange

0

0-127

 

0x06

Lux_Delta_Level

 

2

=0    Turn off report

>=1 Report when change > n*1 Lux

 

0

0-32767

0x07

dB_Delta_Level

1

=0    Turn off report

>=1 Report when change > n*1dB

0

0-127

0x08

PIR_Delta_Level

1

=0    Turn off report

=1    Report change

0

0-1

0x09 SMOKE_Delta_Level 1 =0    Turn off report

=1 Report change

1 0-1

0x0A

Smoke_Timer

2

=0    Turn off report

>=35    Report    every    n*1s interval

60

0,35-32767

 

0x0B

PIR_Timer

 

2

=0    Turn off report

>=35    Report    every    n*1s interval

 

60

0,35-32767

0x0C

PM25_Timer

2

=0    Turn off report

>=35Report      every      n*1s interval

120

0,35-32767

0x0D CO2_Timer 2 =0    Turn off report 120 0,35-32767
>=35    Report    every    n*1s

interval

0x0E

Temp_Timer

2

=0    Turn off report

>=35    Report    every    n*1s interval

180

0,35-32767

0x0F

Humidity_Timer

2

=0    Turn off report

>=35    Report    every    n*1s interval

180

0,35-32767

0x10

VOC_Timer

2

=0    Turn off report

>=35    Report    every    n*1s interval

180

0,35-32767

0x11

Lux_Timer

2

=0    Turn off report

>=35    Report    every    n*1s interval

300

0,35-32767

0x12

dB_Timer

2

=0    Turn off report

>=35    Report    every    n*1s interval

300

0,35-32767

0x2F Temp. unit 1 =0 ℃

=1 ℉

0 0-1

 

0x32

 

T_OffSet

 

1

0 ~ 127:

((n-100)/10)=(-10~2.7)℃

-128 ~ -1: ((156+n)/10)=(2.8~15.5)℃

 

100

 

-128-127

0x33

RH_OffSet

1

n-20=(-20~20)%

20

0~40

0x34 CO2_OffSet 2 (n-500)=(-500~500)ppm 500 0~1000

 

0x35

 

PM2.5_OffSet

 

1

0 ~ 127:

n-100=(-100~27)ug/m3

-128 ~ -1:

156+n=(28~155)ug/m3

 

100

 

-128-127

0x36 Lux_OffSet 2 n-5000=(-5000~5000)lux 5000 0~10000

 

0x37

 

VOC_Correct

 

1

0 ~ 127:

n-100=(-100~27)ppb

-128 ~ -1: 156+n=(28~155)ppb

 

100

 

-128-127

0x38 dB_Correct 1 (n-50)=-50~50 50 0~100
0xFF Write Only 1 ==0x55 Restore factory setting

==0xAA Restore default para.

Warranty

1-year Limited Warranty

MCOHome warrants this product to be free from defects in material and workmanship under normal and proper use for one year from purchase date of the original purchaser. MCOHome will, at its option, either repair or replace any part of its products that prove defective by reason of improper workmanship or materials.THIS LIMITED WARRANTY DOES NOT COVER ANY DAMAGE TO THIS PRODUCT THAT RESULTS FROM IMPROPER INSTALLATION, ACCIDENT, ABUSE, MISUSE, NATURAL DISASTER, INSUFFICIENT OR EXCESSIVE ELECTRICAL SUPPLY, ABNORMAL MECHANICAL OR ENVIRONMENTAL CONDITIONS, OR ANY UNAUTHORIZED DISASSEMBLY, REPAIR OR MODIFICATION.

This limited warranty shall not apply if:

  1. the product was not used in accordance with any accompanying instructions.
  2. the product was not used for its intended function. This limited warranty also does not apply to any product on which the original identification information has been altered, obliterated or removed, that has not been handled or packaged correctly, that has been sold as second-hand or that has been resold contrary to Country and other applicable export regulations.

Reference

Download Manual:

Mco-home A8-9 Electrical Heating Thermostat Instruction MANUAL

Mco-home A8-9 Electrical Heating Thermostat Instruction MANUAL

wpx_thermostats

Recent Posts

Johnson Controls T7000e LCD Digital Thermostat Installation Guide

Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide

1 year ago

Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’S GUIDE

Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE

1 year ago

Hetta HS01RF WIRELESS THERMOSTAT KIT USER MANUAL

Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…

1 year ago

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat USER MANUAL

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…

1 year ago

Honeywell RLV450 PROGRAMMABLE THERMOSTAT USER GUIDE

Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…

1 year ago

Honeywell RLV431 Programmable Thermostat User Guide

Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…

1 year ago