King Electric

King Electric UDG-4999 Programmable Thermostat Quick Start Guide

King Electric UDG-4999 Programmable Thermostat

WARNINGS
To avoid electric shock, disconnect the heating system power supply at the main panel before installation and maintenance of the thermostat. Keep thermostat air vents clean and free from obstruction. This thermostat is an electrical device and must be installed in compliance with National and/or local electrical codes. Installation must be performed by qualified personnel where required by law. If a power module with an equipment ground fault protection device (EGFPD) is to be installed where national and/or local electrical codes require a ground fault circuit interrupter (GFCI), a separate GFCI must also, be installed.

HOME SCREEN

  1. GFCI/EGFPD Test Button
  2. Application
  3. temperature
  4. Heating indicator – when visible, the
  5. The day and time system is heating.
  6. Target temperature or setpoint
  7. 4-Event Program
  8. Access Main Menu
  9. On/Off/GFCI/EGFPD Reset Button Press to turn the system ON
    Hold to turn the system OFF
    Press to reset the GFCI/EGF

CLASSIFICATION

The product is a Class II device (reinforced insulation) and must be connected to the following leads:

  • Phase L1 (L) 120/208/240 V
  • Neutral L2 (N)
  • Max. load 15 A (resistive load)
  • The thermostat is intended to be used with underfloor heating.

The heating element is in accordance with the supply voltage. The terminals are suitable for field wiring cables of 12 to 22 AWG.

TECHNICAL DATA

  • Supply Range……………………………………………….. 120/240 Vac 50/60 Hz
  • Load ………………………………………………………..max. 15 A (resistive load)
  • Max. power at e.g. ……………………………………………. 1800 W at 120 Vac
  • ………………………………………………………………………. 3120 W at 208 Vac
  • ………………………………………………………………………. 3600 W at 240 Vac
  • a. UDG (GFCI)…………………………………………….. Class A (5 mA trip level)
  • b. ADG (EGFPD)……………………………………………………. (15 mA trip level)
  • Temperature range ……………………………… +5 to +40°C / +41 to +104°F
  • Amb. temp. range ………………………………….. 0 to +25°C / +32 to +77°F
  • Construction of Control………….. Electronic room thermostat
  • for regulating electrical underfloor heating.
  • Method of Mounting Control………………………… Independently mounted
  • control for flush mounting
  • Type of Action…………………………………………………………………. Type 2.B.
  • Rated Impulse Voltage ……………………. 2500 V
  • Control Pollution Degree ……………………………………………………………… 2
  • USA – Design Patent No. …………………………………………………………. D768092
  • Canada No. ………………………………………………………………………………161353

CERTIFICATION
UL is Listed in the US and Canada
According to the following standards
Thermostat: UL 60730-1, UL 60730-2-9
CSA E60730-1, CSA E60730-2-9 UL file number: E157297
UDG GFCI: UL 943 4th ed. CSA C22.2 No. 144.1-06
ADG EGFPD UL 1053 CSA C22.2 No. 0.

QUICK START GUIDE

  1. The floor sensor is recommended placed in a nonconductive installation pipe, which is embedded in the floor. The pipe must be sealed in the end and placed as high as possible in the concrete layer. The floor sensor must be centered in between the heating cable. The power supply voltage must match the voltage rating of the heating cable.
  2. Loosen the screw at the bottom and remove the faceplate. Do not attempt to remove the screw completely
  3. Turn the power source OFF at the breaker panel. Connect power supply wires to the line side and heating cable wiring to the load side of the power base. AWG between 12 – 20.
    Note! Do not detach the screws from the terminal. When fastening the screws use a torque between 0.8 – 1.2 Nm / 0.6 – 0.9 lb-ft.
  4. The floor sensor cable must be routed to the junction box separate from the power wires and the heating cable cold lead. Ensure that the insulation on the electrical wiring and the floor sensor inside the junction box are not damaged. Thread the floor sensor cable through the hole in the power base. Push the electrical wires to the back of the electrical box.
  5. Install the power base into the electrical box.Secure the power base to the wall.
  6. Make the sensor connections. The Floor sensor has no polarity. Connect it to terminals C and D. The power module connects to terminals A and B*.efer to the instructions included with the power module.
  7. Remount the faceplate. Tighten the screw at the bottom. Perform GFCI/EGFPD test.

The trademark is registered and belongs to OJ Electronics A/S · © 2017 OJ Electronics A/S

REFERENCE:

DOWNLOAD MANUALS:

King Electric UDG-4999 Programmable Thermostat Quick Start Guide

OTHER MANUALS:

King Electric UDG-4999 Programmable Thermostat Installational Manual

King Electric UDG-4999 Programmable Thermostat Quick Start Guide

wpx_thermostats

Recent Posts

Johnson Controls T7000e LCD Digital Thermostat Installation Guide

Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide

1 year ago

Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’S GUIDE

Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE

1 year ago

Hetta HS01RF WIRELESS THERMOSTAT KIT USER MANUAL

Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…

1 year ago

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat USER MANUAL

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…

1 year ago

Honeywell RLV450 PROGRAMMABLE THERMOSTAT USER GUIDE

Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…

1 year ago

Honeywell RLV431 Programmable Thermostat User Guide

Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…

1 year ago