JUNG

JUNG TR LS 236 WWM Room thermostat User Manual

JUNG TR LS 236 WWM Room thermostat

Operating instructions

Safety instructions

Electrical devices may only be mounted and connected by electrically skilled persons. Serious injuries, Are or are property damage possible? Please read and follow the manual fully. The danger of electric shock. Always disconnect before carrying out work on the device or load. A relative air humidity of max. 95% may not be exceeded. Avoid any moisture condensation. These instructions are an integral part of the product and must remain with the end customer.

Structure of the device

  • Insert
  • Frame
  • Cover
  • Rocker
  • Screw
  • Setting knob

Function

Intended purpose

The room temperature controller is used to regulate the temperature in closed rooms such as fcats, schools, function suites, workshops, etc.

Product characteristics

Neutral conductor required
TR 231 U / TR 241 U:
  • Separate terminal for temperature reduction of 5 K (e.g. during night time)
  • -ON/OFF switch with status LED
  • -When set temperature is reached the contact opens up.
TR 236 U / TR 246 U:
  • -No OFF-position
  • -Without switch and control LED
  • -When set temperature is reached the NO/NC contact switches over.

Information for electrically skilled persons

  • Mount the room temperature controller on an internal wall opposite the heat source if possible.
  • -Do not mount the room temperature controller on the outside walls.
  • -Avoid draughts from windows and doors.
  • -Ensure that the normal air circulation in the room reaches the controller without any obstacles.
  • External heat sources influence the accuracy of the controller. Avoid direct sunlight and do not place heat-emitting devices in the vicinity of the room temperature controller (heaters, lamps, etc.).
  • -Dimmers also generate heat.
  • If a controller is installed in a common switch frame with a dimmer, the distance between them should be as great as possible. When arranging them vertically, the controller must be installed underneath the dimmer.

Connection

Room temperature controllerS

Symbols used in the wiring diagram

  • L = L conductor
  • N = N-conductor
  • AC1 = 24 V power supply

AC2

  • = Connection for the clock signal to reduce the temperature
  • = Heating
  • = Cooling
  • RF = Resistor for thermal feedback
  • TA = Resistor for night reduction of room temperature

Installation

  • Mount the room temperature controller in a switch box in accordance with DIN 49073.
  • Mounting height: approx. 1.5 m above the floor
  • Clip the rocker (4) on the switch in the flush insert.
  • Place the center plate together with the frame on the flush insert.
  • The center plate must snap in place in the top left of the housing base.
  • Tighten the screw (5).
  • Clip on the setting knob (6).

Operation

Restricting the temperature setting range

The temperature controller is set to ex-works to the maximum setting range of 5 °C to 30 °C.

Procedure

  • Select the temperature limits.
  • Example: min 8 °C, max. 23 °C
  • Important!
  • First position the setting knob roughly in the center of the required setting range.
  • Example: The center point between 8 °C and 23 °C is approximately 15 °C.
  • Now remove the setting knob.
  • Set the red locating ring to the max. temperature limit.
  • Example: 23 °C
  • Rotate anti-clockwise.
  • The numbers on the outer dial apply!
  • Insert the tip of a pen in the hole and turn the red ring to the left until it reaches 23 °C (max. scale)
  • Set the blue locating ring to the min. temperature limit.
  • Example: 8 °C
  • Rotate clockwise.
    The numbers on the inner dial apply.
    Insert the tip of a pen in the hole and turn the blue ring to the right until it reaches 8 °C (min. scale).

  • Clip on the setting knob.
  • The pointer must be roughly in the center of the new setting range.
  • Example: approx. 15 °C

scale for setting the temperature with dials

  • 1 = approx. 5 °C
  • 2 = approx. 10 °C
  • 3 = approx. 15 °C
  • 4 = approx. 20 °C
  • 5 = approx. 25 °C
  • 6 = approx. 30 °C

Symbols

  • O OFF
  • I  On

Technical data

TR 231 U / TR 241 U:

  • Switching principle 1-pole break contact + on/of switch
  • Temperature range 5 … 30 °C
  • Nominal voltage
  • TR 231 U AC 230 V ~
  • TR 241 U AC 24 V ~
  • Nominal current* 10 (4) A
  • Differential of functioning temperature approx. 0.5 K
  • Temperature reduction approx. 4 K
  • Energy class I = 1 %
  • The value in brackets indicates the inductive load at a cos φ of 0.6.

TR 236 U / TR 246 U:

  • Switching principle 1-pole change over contact without switch
  • Temperature range 5 … 30 °C
  • Nominal voltage
  • TR 236 U AC 230 V ~
  • TR 246 U AC 24 V ~
  • Nominal current*
  • Heating 10 (4) A
  • Cooling 5 (2) A
  • The differential of functioning temperature approx. 0.5 K
  • The value in brackets indicates the inductive load at a cos φ of 0.6.

Accessories

  • Inserts
    • TR 231 U
    • TR 241 U
    • TR 236 U
    • TR 246 U
  • Covers
    • TR 231 PL ..
    • .. TR 241 PL ..
    • .. TR 236 PL ..
    • .. TR 246 PL ..
  • Special knob
    • MS TR 231 ..

Warranty

The warranty follows the specialty store in between the legal framework as provided for by law

JUNG TR LS 236 WWM Room thermostat User Manual

wpx_thermostats

Recent Posts

Johnson Controls T7000e LCD Digital Thermostat Installation Guide

Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide

1 year ago

Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’S GUIDE

Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE

1 year ago

Hetta HS01RF WIRELESS THERMOSTAT KIT USER MANUAL

Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…

1 year ago

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat USER MANUAL

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…

1 year ago

Honeywell RLV450 PROGRAMMABLE THERMOSTAT USER GUIDE

Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…

1 year ago

Honeywell RLV431 Programmable Thermostat User Guide

Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…

1 year ago