Identifying the instrument
The nameplate with the order code is affixed to the side of the instrument. The supply voltage connected must correspond to the voltage specified on the nameplate. All necessary settings are described in these Operation Instructions. However, if any difficulties should still arise during start-up, you are asked not to carry out any unauthorized manipulations on the unit. This could endanger your rights under the instrument warranty! Please contact the nearest subsidiary or the head office in such a case. Please read these operating instructions before commissioning the instrument. Keep the manual in a place that is accessible to all users at all times. Please assist us to improve these operating instructions, where necessary.
Order code
Included in delivery
Operating Instructions B 70.1050.0
Order code
Installation notes
Supply | Measurement input and supply | |
230V AC and 115V AC | short-circuit-proof | electrically isolated from each other |
12 — 24V DC and 24V AC | not short-circuit-proof | not electrically isolated from each other |
Displays and controls
Setting the instrument functions (parameter level)
Time-out
If no key is pressed for 60 seconds, the instrument automatically switches back to process value display, see Overview of operation on the first inside page.
Controller
Allocating user rights (enabling level)
The setting at the enabling level defines user rights which determine whether a parameter is shown at the operating level, can be edited or is not shown at all.
User right | Display | Factory setting |
The parameter can be edited |
| |
Parameter is shown | – | |
The parameter is not shown | all other parameters |
Meas. input | Designation | Range | Meas. accuracy1/ ambient temperature error | Recognition of … | |
Probe short-circuit | Probe break | ||||
Resistance thermometer | Pt100 EN 60 751 | -200 to +600°C | 0.1%/ £100ppm/°C | yes | yes |
Pt1000 EN 60 751 | -200 to +600°C | 0.1%/ £100ppm/°C | yes | yes | |
KTY2X-6 (PTC) | -50 to +150 °C | 1%/ £100 ppm/°C | yes | yes | |
Resistance 0 — 3000 W | customer table 3 | 0.1%/ £100ppm/°C 3 | = 0W | yes | |
Measuring current with Pt100: 0.2 mA, with Pt1000, KTY2X-6 and resistance: 0.02 mA | |||||
Lead compensation is settable via the parameter Lead compensation resistance. Total resistance (sensor+lead) must not exceed 320W with Pt100 and 3200W with Pt1000, KTY2X-6, and resistance. | |||||
Thermo- couples | Fe-Con J EN 60 584 | -200 to +999 °C | 0.4%/ £100ppm/°C 2 | no | yes |
Fe-Con L DIN 43 710 | -200 to +900 °C | 0.4%/ £100ppm/°C 2 | no | yes | |
NiCr-Ni K EN 60 584 | -200 to +999 °C | 0.4%/ £100ppm/°C 2 | no | yes | |
-10 to 60 mV | customer table 3 | 0.1%/ £100ppm/°C 3 | no | yes | |
For the voltage input (-10 to 60 mV), the terminal temperature compensation for thermocouples can be used. Internal terminal temperature compensation can be switched off through the setup program (0°C). |
Meas. input | Designation | Range | Meas. accuracy1/ ambient temperature error | Recognition of … | |
Probe short-circuit | Probe break | ||||
Current | 0 to 20 mA | -2 to 22 mA scalable with and or customer table | 0.1%/ £100ppm/°C 3 | no | no |
4 to 20 mA | 2.4 to 21.6 mA scalable with and | 0.1%/ £100ppm/°C 3 | yes | yes | |
Input resistance RIN £ 3W | |||||
Voltage | 0 — 10 V | -1 to 11 V scalable with and or customer table | 0.1%/ £100ppm/°C | no | no |
Input resistance RIN ³ 100kW | |||||
1.) The accuracy refers to the measuring range span. 2.) valid from -50°C 3.) A valid customer table must be entered through the setup program and switched over to in the instrument. This may reduce the measuring accuracy. |
Ambient conditions
Ambient temperature range | 0 to +55 °C, with side-by-side mounting: 0 to +40 °C |
Storage temperature range | -40 to +70 °C |
Climatic conditions | £ 75% rel. humidity, no condensation |
Output
Relais K1 (changeover contact) | 150,000 operations at 10A/250V AC 50Hz resistive load 800,000 operations at 3A/250V AC 50Hz resistive load |
Supply
Supply voltage | 230V AC +10/-15%, 48 — 63Hz or 115V AC +10/-15 %, 48 — 63 Hz (isolated from measurement input) |
12 — 24 V DC +15/-15 %, 24V AC +15/-15%, 48 — 63Hz (not isolated from measurement input) | |
Power consumption | < 2VA |
Housing
Material | polycarbonate |
Mounting | DIN rail 35 mm x 7.5mm to EN 50 022 |
Operating position | unrestricted |
Weight | approx. 110 g |
Protection | IP20 |
Flammability class | UL 94 V0 |
Electrical data
Data backup | EEPROM |
Connection | screw terminals for wire cross-sections up to 2.5 mm2 |
Electromagnetic compatibility interference emission immunity to interference | EN 61 326 Class B to industrial requirements |
Electrical safety | EN 61 010, Part 1, overvoltage category III, pollution degree 2 |
The program and the interface with adapter are available as accessories and offer the following advantages:
Minimum hardware and software requirements:
JUMO
DOWNLOAD MANUALS:
JUMO B 70.1050.0 Digital Thermostat Operating Instructions
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…