HONEYWELL THR842D Wireless Room Thermostat Installation Instructions

HONEYWELL THR842D Wireless Room Thermostat

Important notes

  • Paper Whiteness & Brightness levels of 90 (+/-5) should try to be achieved where possible. If not possible then notify Resideo of the closest alternative.
  • Printing and finishing should be to the best quality achievable by the process and free of blemishes, smudges or other visible defects.

Installation

The THR842D wireless room thermostat comprises a THR842D Room Thermostat and a Relay Box. These devices communicate on an 868MHz Radio Frequency (RF) band to control a single heating system component such as a boiler, pump or zone valve. RF communication is 2-way, allowing high performance energy efficient control, display of boiler information, and easy setup and communications check features.

Relay Box

Installation Notes

  • The RF link between the Room Thermostat (THR842D) and the Relay Box in Honeywell system packs is pre-configured at the factory and therefore should be installed at the same site.
  • If products from individual system packs are separated, or mixed with other pre-configured system packs during installation, or a faulty unit is being replaced, the desired units must be specially configured to allow them to communicate with each other.
  • This process is called Binding. Please refer to section 6) Binding / Rebinding Procedure.
  • THR842D or Relay box will not communicate with other RF products that use different frequencies or communications protocols.
  • The THR842D room thermostat requires no power source other than the batteries provided.
  • The Relay Box requires a permanent 230V~ supply.
  • The Relay Box should be installed before commencing the Room Thermostat installation.

Installing the Relay Box

  • For best performance, install in an open space. Leave at least 30cm distance from any metal objects including wall boxes and boiler housing.
  • Do not mount on metal wall boxes.
  • EMC compliance considerations
  • Keep AC mains supply/load cables separate from signal wiring.
  • Refer to Code of Practice standards EN61000-5-1 and -2 for guidance

Installing the THR842D Room Thermostat

Power up

RF Communication Test

Locating the Room Thermostat

  • For best performance, install in an open space where THR842D can sense the room temperature, and where the signal strength is high.
  • The Room Thermostat can be mounted on a wall or on the optional table stand.
  • Leave at least 30cm distance from any metal objects and at least 1 metre from any other electrical equipment.
  • Select the preferred location and test the Signal Strength before installation.

Signal Strength Test

Mounting the Room Thermostat

Test & Binding Flow-chart

Basic System Operation

Automatic Operation

Temporary Manual Override

Loss of RF communications

Installer Mode

To enter Installer Mode

To select a parameter

Display

To change a parameter

To change a parameter

Parameter flowchart

Parameters

Description Parameter Range of values Default Predefiniti
Minimum ON/OFF time / Ot 1,2,3,4,5 m 1 m
Cycle rate / Frecuencia de los ciclos / Nombre de cycles/heure / Aantal schakelingen per uur / Zykluszeit / Frequenza dei cicli / Ciklusidő / Počet cyklů / Częstotliwość cykli

/ Počet cyklov / Velocidade de ciclo / Frecvență ciclu / Brzina ciklusa

Cr {3,6,9,12} 6
Proportional band width Pb 1.5 … 3.0 K 1.5K

 

Description Parameter Range of values Default
Temperature measurement offset tO -3 … 3 K 0 K
Upper setpoint limit uL 21 … 35 °C 35°C
Lower setpoint limit LL 5 … 21 °C 5°C
ECO temperature ES 5 … 35 °C 18 °C
Heat/cool changeover HC 0 / 1 0
0 = Disable
Off setpoint adjust OS — (= Off), 5…16°C 5°C
Failsafe mode (loss of RF communications) LC 0 = Off

1 = On 20%

0 = Off
Reset parameters FS 0 / 1 1 (factory)

Binding/Rebinding Procedure

The binding operation shown is required if:

  • any of the system components (Room Thermostat or Relay Box) are replaced
  • Relay Box has incorrect or no binding data stored (for example, when pre-bound system pack components have been mismatched

Reset stored data in Relay Box

Put Relay Box into Binding Mode

Reset stored data in Room Thermostat

Put Room Thermostat into Binding Mode

Bind Room Thermostat to Relay Box

Honey Well

For assistance with this product please visit: livewell.honeywellhome.com

  • bk-electronic GmbH
  • Hardhofweg 40
  • 74821 Mosbach
  • Germany
  • Country of origin: UK

REFERENCE

DOWNLOAD MANUALS:

HONEYWELL THR842D Wireless Room Thermostat Installation Instructions

HONEYWELL THR842D Wireless Room Thermostat Installation Instructions

wpx_thermostats

Recent Posts

Johnson Controls T7000e LCD Digital Thermostat Installation Guide

Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide

1 year ago

Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’S GUIDE

Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE

1 year ago

Hetta HS01RF WIRELESS THERMOSTAT KIT USER MANUAL

Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…

1 year ago

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat USER MANUAL

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…

1 year ago

Honeywell RLV450 PROGRAMMABLE THERMOSTAT USER GUIDE

Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…

1 year ago

Honeywell RLV431 Programmable Thermostat User Guide

Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…

1 year ago