System Types
Compatible with 24-volt systems such as forced air, hydronic, heat pump (including dual fuel), oil, gas and electric.
Does not work with electric baseboard heat (120/240V).
Mercury Notice:
If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact the Thermostat Recycling Corporation at 1-800-238-8192 or thermostat-recycle.org for information on how and where to properly and safely dispose an old thermostat.
Disconnect power before installation.
Can cause electrical shock or equipment damage.
Must be installed by a trained, experienced technician.
Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous condition.
Jumper Switch for humidifier, dehumidifier, or ventilation:
Terminal Voltage (50/60 Hz) Max. Current Rating | ||
W – O/B (Heating) | 18 to 30 VAC | 1.00 A |
W2 – Aux/E (Heating) | 18 to 30 VAC | 0.60 A |
Y (Cooling) | 18 to 30 VAC | 1.00 A |
Y2 (Cooling) | 18 to 30 VAC | 0.60 A |
K | 18 to 30 VAC | 1.00 A |
G (Fan) | 18 to 30 VAC | 0.50 A |
L (Output) | 18 to 30 VAC | 1.00 A |
U1, U2 | 18 to 30 VAC | 0.40 A |
ISU # | Description | Setting |
1160 | Temperature indication scale | 0 = Fahrenheit 1 = Celsius |
2120 | Heating system type | 1 = Conventional forced air heat 2 = Heat pump 3 = Radiant heat 5 = None (cool only) |
2140 | Heating equipment type | Conventional Forced Air Heat: 1 = Standard efficiency gas forced air 2 = High efficiency gas forced air 3 = Oil forced air 4 = Electric forced air 5 = Hot water fan coil |
Heat Pump: 7 = Air to air heat pump 8 = Geothermal heat pump | ||
Radiant Heat: 9 = Hot water radiant heat 12 = Steam | ||
2160 | Reversing valve O/B | 0 = O (O/B on cool) 1 = B (O/B on heat) |
2180 | Cool stages / compressor stages | 0, 1, 2 |
2200 | Heat stages / backup heat stages | Heat stages: 0, 1, 2 Backup heat stages: 0, 1 |
2220 | Fan operation in heat | 0 = No fan 1 = Equipment controls fan 2 = Thermostat controls fan |
2240 | Backup heat type | 31 = Electric forced air 32 = Gas/Oil Forced air (or Fossil forced air) |
2260 | External Fossil Fuel Kit | 0 = Thermostat controls backup heat 1 = External Fossil Fuel Kit controls backup heat |
3120 | Staging control | Comfort |
– backup heat | 2.0°F to 15.0°F from setpoint (in 0.5°F | |
differential | increments) | |
1.0°C to 7.5°C from setpoint (in 0.25°C | ||
increments) | ||
3140 | Backup heat upstage timer | Off 30, 45, 60, 75, 90 minutes 2, 3, 4, 5, 6, 8, 10, 12, 14, 16 hours |
3160 | Compressor lockout / | Off |
balance point | 5°F to 60°F (in 5°F increments) | |
-15.0°C to 15.5°C (in 2.5°C or 3.0°C | ||
increments) | ||
3180 | Backup heat lockout | Off 5°F to 65°F (in 5°F increments) -15.0°C to 18.5°C (in 2.5°C or 3.0°C increments) |
3200 | Cool cycles per hour | 1 – 6 |
3220 | Cool cycles per hour – stage 2 | 1 – 6 |
3240 | Heat cycles per hour | 1 – 12 |
3260 | Heat cycles per hour – stage 2 | 1 – 12 |
3280 | Backup heat cycles per hour | 1 – 12 |
4120 | Adaptive intelligent recovery | 0 = No 1 = Yes |
ISU # | Description | Setting |
4160 | Minimum setpoint (Note: Setting applies to both heat and cool setpoints) | 50°F to 99°F 10.0°C to 37.0°C |
4220 | Maximum setpoint (Note: Setting applies to both heat and cool setpoints) | 40°F to 90°F 4.5°C to 32.0°C |
8100 | Humidifier type | 0 = None 1 = Steam 2 = Bypass or fan powered |
8120 | Humidification – window protection | 0 = Off 1 = On |
8140 | Humidification control | 0 = Humidify only when heat is On 1 = Humidify only when fan is On 2 = Humidify on demand: Thermostat controls fan 3 = Humidify on demand: Humidifier controls fan |
9100 | Dehumidification equipment | 0 = None 1 = A/C with low speed fan 2 = A/C with high speed fan 4 = Whole house dehumidifier |
9140 | Dehumidification equipment setup | 0 = Normally open 1 = Normally closed |
9160 | Dehumidification – overcooling limit | 0, 1, 2, 3°F 0.0, 0.5, 1.0, 1.5°C |
9180 | Dehumidifier fan control | 0 = Thermostat controls fan 1 = Equipment controls fan |
10100 | Ventilation type | 0 = None 1 = ERV / HRV 2 = Passive (fan only) 3 = Fresh air damper |
10160 | Ventilation fan control | 0 = Thermostat controls fan 1 = Equipment controls fan |
10240 | Ventilation per cent on time | 10% to 100% (in 10% increments) |
10280 | Ventilation low-temperature lockout | Off -20°F to 40°F (in 5°F increments) -29.0°C to 4.5°C (in 2.5°C or 3.0°C increments) |
10300 | Ventilation high-temperature lockout | Off 80°F to 110°F (in 5°F increments) 26.5°C to 43.5°C (in 2.5°C or 3.0°C increments) |
10320 | Ventilation high dew point lockout | Off 65°F to 85°F (in 5°F increments) 18.5°C to 29.5°C (in 2.5°C or 3.0°C increments) |
11100 | Home heat setpoint | 40°F to 90°F 4.5°C to 32.0°C (in 0.5°C increments) |
11120 | Home cool setpoint | 50°F to 99°F 10.0°C to 37.0°C (in 0.5°C increments) |
11140 | Setpoint for away mode | 0 = Away setpoints 1 = Smart temperature setpoints |
11160 | Away heat setpoint | 40°F to 90°F 4.5°C to 32.0°C (in 0.5°C increments) |
11180 | Away cool setpoint | 50°F to 99°F 10.0°C to 37.0°F (in 0.5°C increments) |
14020 | Temperature display offset | -3°F to 3°F |
14025 | Humidity % offset | -12% RH to 12% RH |
NEED HELP?
For assistance with this product, please visit customer.resideo.com or call Customer Care toll-free at 1-800-633-3991.
FCC REGULATIONS
47 CFR § 15.19 (a)(3)
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
47 CFR § 15.21 (USA only)
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
47 CFR § 15.105 (b)
See https://customer.resideo.com/en-US/support/residential/codes-and-standards/FCC15105/Pages/default.aspx for additional FCC information for this product.
IC REGULATIONS
RSS-GEN
This device contains licence-exempt transmitter(s)/receiver(s) that comply with Innovation, Science and Economic Development Canada’s licence-exempt RSS(s). Operation is subject to the following two conditions:
The operation of this equipment is subject to the following two conditions:
©2019 Resideo Technologies, Inc.
This product is manufactured by Resideo Technologies, Inc., Golden Valley, MN, 1-800-633-3991.
The Honeywell Home trademark is used under license from Honeywell International Inc. All rights reserved.
Resideo Inc., 1985 Douglas Drive North Golden Valley, MN 55422
www.resideo.com 33-00445EFS—05 M.S. Rev. 04-19
Printed in the United States
Search for local rebates: HoneywellHome.com/Rebates
Download manuals:
Honeywell TH8732WFH5004 Round Smart Thermostat User Guide
Honeywell TH8732WFH5004 Round Smart Thermostat User Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…