Honeywell

Honeywell T87F Non-Programmable Thermostat Installation Manual

Honeywell T87F Non-Programmable Thermostat

Application

The T87F Universal Thermostat provides tempera-ture control for 24 to 30 Vac residential heating, cooling or heating-cooling systems. For heating systems, the T87F mounts on the wallplate provided. For cooling only, or heating-cooling, order the 137421A (198170A if textured designer model) Heating-Cooling Wallplate with remote switching, or the Q539 Subbase, which provides switching at the thermostat location.
The spdt switch makes one set of contacts on a tem-perature fall to operate the heating system. The other set of contacts make on a temperature rise to operate the cooling system when the T87F is used to control cool-ing.
Heat anticipation is adjustable, 0.1 to 1.2A.

Mercury Notice
This control contains mercury in a sealed tube. Do not place control in the trash at the end of its useful life.
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of this control, or of an old control containing mercury in a sealed tube.
If you have questions, call Honeywell Inc. at 1-800-468-1502.

Installation and Setting

WHEN INSTALLING THIS PRODUCT…

  1. Read these instructions carefully. Failure to follow them could cause a hazardous condition.
  2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
  3. Installer must be a trained, experienced service technician.
  4. After installation is complete, check out product operation as provided in these instructions.

CAUTION

  1. Disconnect power supply to prevent electrical shock or equipment damage.
  2. To prevent interference with the thermostat linkage, keep wire length to a minimum and run wires as close as possible to the subbase.
  3. Do not overtighten thermostat captive mount-ing screws because damage to subbase threads can result.
  4. Do not short across coil terminals on relay. This can burn out the thermostat heat anticipator.

IMPORTANT: An incorrectly leveled thermostat will cause the temperature control to deviate from set point.

LOCATION

Install the thermostat about 5 ft [1.5m] above the floor in an area with good air circulation at an average temperature.
Do not install the thermostat where it may be affected by:

  • drafts, or dead spots behind doors and in corners.
  • hot or cold air from ducts.
  • radiant heat from sun or appliances.
  • concealed pipes and chimneys.
  • unheated (uncooled) areas such as an outside wall behind the thermostat.
    This thermostat is a precision instrument and was carefully adjusted at the factory. Handle it carefully.

MOUNTING WALLPLATE OR SUBBASE (Fig. 2)

IMPORTANT:

  • Use a spirit level to accurately level the wallplate or subbase as in Fig. 1. Inaccurate leveling may cause thermostat control deviation.
  • When using the T87F with a Q539 Subbase, follow the mounting and wiring instructions included with the subbase.
  1. Place the wall plate on the wall at the desired location. Pull the thermostat cable through the entrance hole.
  2. Fasten wallplate. Do not tighten the screws.
  3. Level according to Fig. 1 then tightens the screws.
  4. After wiring the wallplate, plug the hole to prevent drafts from affecting the thermostat.
    NOTE: To mount T87 Thermostat on an outlet box, order 129044A Adapter Ring Assembly.

WIRING

All wiring must comply with local electrical codes and ordinances. Disconnect power supply before connecting wiring to prevent electrical shock or equipment damage.
The T87F is adaptable to most 2-wire, 24 to 30 volt heating systems, and to most 3-wire, 24 to 30 volt heating systems controlled by a Series 10 Thermostat. The following hookups are typical applications. See Figs. 3 through 7.When using the T87F for cooling control, refer to the hookups in the Q539 Subbase instructions.
For variations of these systems, refer to the installation instructions for the controlled equipment.
After wiring the wallplate, plug the hole to prevent drafts that may affect the thermostat.

MOUNTING THERMOSTAT TO WALLPLATE OR SUBBASE
To remove standard cover, pull ring outward with fingertips, pressing lightly on dial with thumbs.
To remove locking cover, loosen the three screws along the cover edge with the Allen wrench supplied. Remove the cover as indicated above.
Remove and discard the plastic insert protecting the mercury switch.
Align the thermostat over the wallplate and tighten the three captive mounting screws. These captive screws complete the electrical connections to the thermostat. Adjust heat anticipator to match current rating of primary control. See Fig. 8.

HEAT ANTICIPATOR SETTING
If the T87F is used for 3-wire, spdt, heating-only (Series 20) control (Fig. 6), set the heat anticipator for 1.2 (far left end of scale). A fixed resistor-type heater is provided in the 137421A or 198170A Wallplate for this application. For other control applications, proceed as follows.
Adjust anticipator to match current rating of primary control. Rating is usually stamped on the control nameplate. Move the indicator to the marking that matches this rating. Indicator may be moved with fingers or pencil point through the hole shown in Fig. 8. If the current rating is not given, proceed as follows before mounting the thermostat:

  1. Connect an ac ammeter of appropriate range (0 to 2.0A, for example) between the R and W terminals on the wallplate or subbase.
  2. Let the system operate for one minute before reading the ammeter.
  3. Move the anticipator indicator to match the ammeter reading.
    A slightly higher setting to obtain longer burner-on times (fewer cycles per hour) may be desirable for some systems.

RECALIBRATION
The T87F is calibrated at the factory and no recalibration should be necessary. If the thermostat is accurately leveled and still appears to be out of calibration, order 104994A Calibration Wrench. Instructions for recalibrating are furnished with the wrench.

Checkout

HEATING

Turn down the temperature setting to the lowest point. If subbase or remote switching is used, move system switch to HEAT position. Raise the temperature setting until the heating equipment starts. This point should be at room temperature as indicated on the thermometer. Slowly turn back dial. Heating equipment should stop when the dial has been turned below room temperature.

COOLING

CAUTION

  1. Do not operate cooling if outdoor temperature is below 50° F [10° C]. Refer to manufacturer recommendations.
  2. Allow five-minute off-time after the compressor has been run to avoid compressor damage.

If T87F controls cooling, move system switch (if used) to call for COOL and lower setting until cooling equipment starts. Raise setting above room temperature and cooling system should shut down. Make certain all equipment properly responds to the thermostat.

Automation and Control Solutions

HoneywellInternational Inc. 1985 Douglas Drive North Golden Valley, MN 55422
Honeywell Limited—Honeywell Limitée 35 Dynamic Drive
Scarborough, Ontario M1V 4Z9
www.honeywell.com/yourhome

REFERENCE:

Download Manual:

Honeywell T87F Non-Programmable Thermostat Installation Manual

OTHER MANUALS:

Honeywell T87F Non-Programmable Thermostat User Guide

HONEYWELL T87F Zone Thermostat INSTALLATION INSTRUCTIONS

Honeywell T87F Non-Programmable Thermostat Installation Manual

wpx_thermostats

Recent Posts

Johnson Controls T7000e LCD Digital Thermostat Installation Guide

Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide

1 year ago

Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’S GUIDE

Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE

1 year ago

Hetta HS01RF WIRELESS THERMOSTAT KIT USER MANUAL

Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…

1 year ago

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat USER MANUAL

HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…

1 year ago

Honeywell RLV450 PROGRAMMABLE THERMOSTAT USER GUIDE

Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…

1 year ago

Honeywell RLV431 Programmable Thermostat User Guide

Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…

1 year ago