The T87F Universal Thermostat provides tempera-ture control for 24 to 30 Vac residential heating, cooling or heating-cooling systems. For heating systems, the T87F mounts on the wallplate provided. For cooling only, or heating-cooling, order the 137421A (198170A if textured designer model) Heating-Cooling Wallplate with remote switching, or the Q539 Subbase, which provides switching at the thermostat location.
The spdt switch makes one set of contacts on a tem-perature fall to operate the heating system. The other set of contacts make on a temperature rise to operate the cooling system when the T87F is used to control cool-ing.
Heat anticipation is adjustable, 0.1 to 1.2A.
Mercury Notice
This control contains mercury in a sealed tube. Do not place control in the trash at the end of its useful life.
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of this control, or of an old control containing mercury in a sealed tube.
If you have questions, call Honeywell Inc. at 1-800-468-1502.
WHEN INSTALLING THIS PRODUCT…
CAUTION
IMPORTANT: An incorrectly leveled thermostat will cause the temperature control to deviate from set point.
Install the thermostat about 5 ft [1.5m] above the floor in an area with good air circulation at an average temperature.
Do not install the thermostat where it may be affected by:
All wiring must comply with local electrical codes and ordinances. Disconnect power supply before connecting wiring to prevent electrical shock or equipment damage.
The T87F is adaptable to most 2-wire, 24 to 30 volt heating systems, and to most 3-wire, 24 to 30 volt heating systems controlled by a Series 10 Thermostat. The following hookups are typical applications. See Figs. 3 through 7.When using the T87F for cooling control, refer to the hookups in the Q539 Subbase instructions.
For variations of these systems, refer to the installation instructions for the controlled equipment.
After wiring the wallplate, plug the hole to prevent drafts that may affect the thermostat.
MOUNTING THERMOSTAT TO WALLPLATE OR SUBBASE
To remove standard cover, pull ring outward with fingertips, pressing lightly on dial with thumbs.
To remove locking cover, loosen the three screws along the cover edge with the Allen wrench supplied. Remove the cover as indicated above.
Remove and discard the plastic insert protecting the mercury switch.
Align the thermostat over the wallplate and tighten the three captive mounting screws. These captive screws complete the electrical connections to the thermostat. Adjust heat anticipator to match current rating of primary control. See Fig. 8.
HEAT ANTICIPATOR SETTING
If the T87F is used for 3-wire, spdt, heating-only (Series 20) control (Fig. 6), set the heat anticipator for 1.2 (far left end of scale). A fixed resistor-type heater is provided in the 137421A or 198170A Wallplate for this application. For other control applications, proceed as follows.
Adjust anticipator to match current rating of primary control. Rating is usually stamped on the control nameplate. Move the indicator to the marking that matches this rating. Indicator may be moved with fingers or pencil point through the hole shown in Fig. 8. If the current rating is not given, proceed as follows before mounting the thermostat:
RECALIBRATION
The T87F is calibrated at the factory and no recalibration should be necessary. If the thermostat is accurately leveled and still appears to be out of calibration, order 104994A Calibration Wrench. Instructions for recalibrating are furnished with the wrench.
Turn down the temperature setting to the lowest point. If subbase or remote switching is used, move system switch to HEAT position. Raise the temperature setting until the heating equipment starts. This point should be at room temperature as indicated on the thermometer. Slowly turn back dial. Heating equipment should stop when the dial has been turned below room temperature.
CAUTION
If T87F controls cooling, move system switch (if used) to call for COOL and lower setting until cooling equipment starts. Raise setting above room temperature and cooling system should shut down. Make certain all equipment properly responds to the thermostat.
Automation and Control Solutions
HoneywellInternational Inc. 1985 Douglas Drive North Golden Valley, MN 55422
Honeywell Limited—Honeywell Limitée 35 Dynamic Drive
Scarborough, Ontario M1V 4Z9
www.honeywell.com/yourhome
Download Manual:
Honeywell T87F Non-Programmable Thermostat Installation Manual
OTHER MANUALS:
Honeywell T87F Non-Programmable Thermostat User Guide
HONEYWELL T87F Zone Thermostat INSTALLATION INSTRUCTIONS
Honeywell T87F Non-Programmable Thermostat Installation Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…